  • 8/8/2019 Abu Bakar Baginda Substation

    1/24

    EET 3086 SWITCHGEAR AND PROTECTION 1

    ABU BAKAR BAGINDA

    Substation

  • 8/8/2019 Abu Bakar Baginda Substation

    2/24

    2

    LIOW SER KHENG 1021179395

    LIM WEI LIANG 1021125410 SIOW JATSHERN 1021115960

    TAN CHEE SIANG 1021115778

  • 8/8/2019 Abu Bakar Baginda Substation

    3/24

    3

    ABU BAKAR BAGINDA

    Substation

    132kV substation

    Step down voltage to 33kV & 11kV and

    distribute to consumer.

    Getting generation supply from Serdang.

    In all TNB substation, the 3 phase system isindicate by red, yellow, blue colour code.

  • 8/8/2019 Abu Bakar Baginda Substation

    4/24

    4

    Substation Equipment

    Bus bar

    Generator

    Transformer

    Circuit Breaker

    Isolator

    Lightning arrester

    Current transformer

    Power transformer

  • 8/8/2019 Abu Bakar Baginda Substation

    5/24

    5

    Bus Bar

    This substation having 2 three phase bus bar which

    are main bus bar and reserve bus bar.

    The both bus bar are live.

    The maintenance of the bus bar are done every four

    years.

    During maintenance one bus bar is shut down and

    all the load switch to one bus bar only.

    The bus bar rating that used in the substation is

    3000A, 132kV.

  • 8/8/2019 Abu Bakar Baginda Substation

    6/24

    6

  • 8/8/2019 Abu Bakar Baginda Substation

    7/24

    7

    Surge/ Lightning Arrester

    The one we see in the substation is valve-typelightning arrester.

    It work as an insulator at normal system voltage but

    it become a good conductor of low resistance to limitlightning voltage to a value lower than the basicimpulse level of the equipment being protected. Itre-establishes itself as an insulator after thedischarge of the surge current.

    The rating for the lightning arrester is 20kA.

  • 8/8/2019 Abu Bakar Baginda Substation

    8/24

    8

  • 8/8/2019 Abu Bakar Baginda Substation

    9/24

    9

    Circuit Breaker

    The one we see in the substation is sulphur

    hexafluoride (SF6).

    It only occupied small space. The circuit breaker rating for this substation is

    1600A.

    There is one coupler circuit breaker in this

    substation and its rating is 3000A.

  • 8/8/2019 Abu Bakar Baginda Substation

    10/24

    10

  • 8/8/2019 Abu Bakar Baginda Substation

    11/24

    11

    Transformer

    The transformer step down the 132kV to 33kV and11kV.

    The transformer for stepping down 132kV to 33kV iswye-delta connected so it have a earthing

    transformer. The transformer for stepping down 132kV to 11kV is

    wye-wye connected so it no need the earthingtransformer.

    The earthing transformer is the supply to the controlroom.

    The rating for the 132/33kV transformer is 90MVAand the 132/11kV is 30 MVA.

  • 8/8/2019 Abu Bakar Baginda Substation

    12/24

    12

    132KV to 33KV

    132KV to 11KV

  • 8/8/2019 Abu Bakar Baginda Substation

    13/24

    13

    Current Transformer

    The current Transformer that we see in the

    substation is oil-filled type.

    The size is bigger than the circuit breakerwhich use the SF6 as the insulation.

    The current transformer ratio is 1600:1.

  • 8/8/2019 Abu Bakar Baginda Substation

    14/24

    14

  • 8/8/2019 Abu Bakar Baginda Substation

    15/24

    15

    Voltage/ Potential Transformer

    Voltage transformers are used to reduce the

    system voltage to levels low enough to suit

    the ratings of the protective relays. The rating of the voltage transformer used in

    this substation is 132kV:110V

  • 8/8/2019 Abu Bakar Baginda Substation

    16/24

    16

  • 8/8/2019 Abu Bakar Baginda Substation

    17/24

    17

    Isolator/ Disconnector

    Isolator is used to isolate the fault section.

    It only can be open after the circuit breaker is

    trips. If the isolator is open before the circuit

    breaker is trip, it may cause fire in the

    substation.

  • 8/8/2019 Abu Bakar Baginda Substation

    18/24

    18

  • 8/8/2019 Abu Bakar Baginda Substation

    19/24

    19

    Control Room

    The control of the substation is done in this room.

    The supply of the control room is come from theearthing transformer.

    In the control room is consist many type of relaywhich used for the protection.

    All the relay being used in this substation isnumerical relay.

    The phase to ground fault is the most common faultin this substation.

  • 8/8/2019 Abu Bakar Baginda Substation

    20/24

    20

  • 8/8/2019 Abu Bakar Baginda Substation

    21/24

    21

    Transformer Protection

    The transformer is control by the remote tap

    changing control panel which is automated.

    The transformer is protected using the transformer

    differential protection scheme.

    The back-up protection for the transformer is over

    current protection scheme.

    Since the primary protection is unit protection so the

    back-up protection cannot be unit protection.

  • 8/8/2019 Abu Bakar Baginda Substation

    22/24

    22

    Bus Bar Protection

    The bus bar is being protected using the current

    differential protection scheme.

    Current differential is the unit protection which will

    only detect the internal fault.

    The current transformer ratio have to be choose

    properly to avoid undesired trip due to the CT

    saturation when there is the external fault.

    The back-up protection is over current protection

    scheme.

  • 8/8/2019 Abu Bakar Baginda Substation

    23/24

    23

    Transmission Line Protection

    The transmission line is being protected

    using distance protection.

    MHO relay is used for the distanceprotection.

    Current transformer and voltage transformer

    are needed in this protection scheme in order

    to measured the impedance of the line.

  • 8/8/2019 Abu Bakar Baginda Substation

    24/24

    24

    Circuit Breaker Tripping

    For 132kV and below, 3-pole tripping method is inused and for above 132kV the single pole trippingmethod is in used.

    This substation is using the 3-pole tripping method. This mean all 3 phase will be tripped during the

    fault.

    For 3-pole tripping it only need a circuit breaker but

    for single pole tripping it need 3 circuit breakerbecause it need each for one phase.