ducted unit

Upload: woei-tding-chong

Post on 04-Apr-2018

259 views

Category:

Documents


8 download

TRANSCRIPT

  • 7/30/2019 Ducted Unit

    1/8

    SWPU SERIES

    DUCTEDCEILING

    MOUNTED

    WATER-COOLEDPACKAGED

    AIR-CONDITIONERS

    SLIMLINE

    Smar tw ise I nnovat ions...Towards Green, Qual i t y & Rel iabi l i t y Solut ions

    Smartech Sales & Services Sdn. Bhd.(829707-K)

    No.15, Jalan PJS 1/27, (Jalan Petaling Utama 6), Petaling Utama, Batu 7,

    Off Jalan Klang Lama, 46000 Petaling Jaya, Selangor.

    T: 603-7782 2788 / 7783 7288 F: 603-7782 3788

    W: www.smart-hvac.com.my

    Specifications in this catalogue are subject to change without notice in order that SMARTECH may bring the latest innovations to their customer.

    SWPU0110

  • 7/30/2019 Ducted Unit

    2/8

  • 7/30/2019 Ducted Unit

    3/8

    INTRODUCTION

    DUCTED CEILING MOUNTED WATER-COOLEDPACKAGE AIR-CONDITIONERS

    The Smartech SlimLine Water-cooled Packaged air-conditioners ranging incapacity from 20,000 Btu/hr to 260,000 Btu/hr, offers Architects, Design Engineers,Developers and building owners a versatile, flexible and economical type ofair-conditioning system for use in office buildings, factories, hospitals supermarkets,shopping malls, etc; instead of the higher cost Central Chilled water Air-conditioningsystem, utilizing Chillers, Cooling towers, Air-handling units and Fancoils. Comparedwith air-cooled split or packaged air-conditioners, the water-cooled packagedair-conditioners offer approximately 30% savings in operating cost.

    2

    The Ducted Ceiling Mounted SlimLine water-cooled packaged air-conditionerssaves valuable floor space when compared with floor mounted water-cooledpackaged air-conditioners.

    The Smartech SlimLine SWPUs with its rigid double-wall casing construction, highefficiency hermetic rotary or scroll compressors, cleanable shell & tubes condensers,hydrophillic coated aluminium fins evaporator coil, direct-drive or belt-driven blowerfans, balanced port design thermal expansion valves, factory prepiped and leaktested thick wall copper refrigerant pipings, factory prewired electrical and controlpanel, etc; are designed and manufactured to ensure efficient , reliable, low noiseand low vibration performance within the ceiling space.

    NOMENCLATURE

    SWPU 200T DDC P

    Smartech Water-CooledPackaged Unit

    Model Size

    Twin Compressors

    -

    P R-407c Green Refrigerant

    DDC-Ducted Direct Drive Motor,Ceiling Mounted

    DBC-Ducted Belt Drive Motor,Ceiling Mounted

    R-22 Refrigerant

    DIMENSIONAL DATASWPU 200T (DBC)

    SWPU 260T (DBC)

    13

    Note: All dimension are in inches. Unless otherwise specified.

    Note: All dimension are in inches. Unless otherwise specified.

    1

    2

    3 3

    CONDENSATEDRAIN 3/4" MPT

    CONDENSERINLET/OUTLET

    CONN J

    MOTOR

    HANGINGLUGS5/8" HOLES

    CONDENSER

    BLOWERFAN

    COOLINGCOIL

    FILTERRACK

    2" DUCTCOLLAR

    COMPRESSOR

    ELECTRICALPANEL

    89

    18 17

    18

    243

    3021

    243

    18

    7

    25

    3021

    2

    31318

    60

    1718182016

    8221

    21

    HANGINGLUGS5/8" HOLES

    CONDENSER

    BLOWERFAN

    MOTOR

    CONDENSATEDRAIN 3/4" MPT

    CONDENSERINLET/OUTLET

    CONN J

    COMPRESSOR

    ELECTRICALPANEL

    COOLINGCOIL

    FILTERRACK

    2" DUCTCOLLAR

    2

    1825

    21

    31318

    60

    2

    30

    7 21

    432

    43

    18

    18 13

    74

    3021

    1813 18 13

    67321 32

    1

  • 7/30/2019 Ducted Unit

    4/8

    3

    FEATURES

    The casing cabinetry consists of a rigid framework constructed fromheavy gauge welded steel channels, held rigidly together by double-wallpanels and supports;

    A. Casing

    The double wall panels, with sandwiched polyurethane insulation betweenthe walls are held tightly to the framework to form a rigid casing whichreduces noise breakout from within the unit;

    Selected double-wall panels near the Blower fan are insulated with 1/3lbs density fiberglass and internally lined with perforated GI liner to absorbnoise generated by the fan;

    With double-wall construction, it is easy to clean the inner surfaces toreduce risk of dirt and bacteria contamination;

    There is no erosion of internal insulation material which can contaminatethe air-stream. The double-wall construction SWPU is ideal for cleanroom applications, such as hospital, electronic factories, food processing andpharmaceutical factories;

    Casing panels are aesthetically coated with oven-baked polyester paint toprovide excellent finish and good corrosion resistance;

    Removable access panels are provided for ease of access to critical partsand components for service and repairs.

    B. Hermetic Rotary Compr essor (Size 21 to Size 32)

    Hermetic motor of single phase permanent split capacitor type, refrigerantcooled. Motor fitted with internal thermal protection;

    Compressor with internal suspension system and externally mounted onrubber grommets to eliminate vibration and ensure quiet operation;

    Compressor fitted with suction accumulator to protect against liquid sluggingat start-up

    The hermetic Rotary compressor design has high efficiency, low noise andproven reliability.

    C. Scroll Compressors (from size 38 to 260)

    Scroll hermetic type operating at 2950 rpm (50Hz);High efficiency (high EER), low noise and proven high reliability;

    No contact scroll design and suction gas cooled motor ensure long servicelife;

    With internal line break motor protector or solid state motor protector;Unit with twin compressors and dual refrigerant circuits, besides providingfor system redundancy, reduces current inrush during start-ups and bycycling on/off of two compressors to match building load, less energy isbeing used when room load requires lesser cooling capacity.

    Consists of outer carbon steel shell with internal bundle of copper finnedtubes;

    Water travels within the copper finned tubes while hot discharge gas envelopesthe outer finned surface of the copper tubes before condensing to liquid;

    D. Cleanable Shell & Tube Condenser

    Each condenser is built with integral sub-cooling chamber to maximizesystem efficiency;

    Each condenser is provided with a fusible plug which meltswhen temperature reaches 175F, releases system refr igerantgas and avoids explosion in case of fire;

    Complete condenser is leak and pressure tested on bothwater and refrigerant sides prior to assembly.

    DIMENSIONAL DATASWPU 164T (DBC)

    SWPU 195 (DBC)

    3 48 3

    24

    11

    1614

    49

    HANGINGLUGS5/8" HOLES

    CONDENSER

    BLOWERFAN

    MOTOR

    CONDENSATEDRAIN 3/4"MPT

    CONDENSERINLET/OUTLET

    CONN J

    28

    55

    1314

    14

    ELECTRICALPANEL

    COMPRESSOR

    497

    12 13 3

    28

    14

    33

    25

    COOLINGCOIL

    43

    41

    41

    41

    41

    167

    167 2

    1

    2" DUCTCOLLAR

    Note: All dimension are in inches. Unless otherwise specified.

    Note: All dimension are in inches. Unless otherwise specified.

    FILTERRACK

    12

    ELECTRICALPANEL

    COMPRESSOR 18 13

    30

    74

    18

    2

    21

    43

    21

    2 43

    18

    2" DUCTCOLLAR

    21

    7

    3025

    31312

    54

    21

    3 67 21

    3

    13 12 18 13

    CONDENSATEDRAIN 3/4" MPT

    CONDENSERINLET/OUTLET

    CONN J

    HANGINGLUGS5/8" HOLES

    CONDENSER

    BLOWERFAN

    2

    3

    141

  • 7/30/2019 Ducted Unit

    5/8

    4

    FEATURES contd

    E. Evaporator Coil

    Constructed from staggered rows of copper tubes mechanicallyexpanded into die formed aluminium fins;The aluminium fins are precoated with low surface tensionsubstance which speeds up the drainage of condensate,eliminates moisture carry-over, maintain the aluminium finssurface dry and clean, and prevent mould formation. The coatingalso improves the corrosion resistance of the aluminium fins andprevents oxidation of the aluminium surface, thus maintaininggood heat rejection.

    Coils are leak and pressure tested to 450 psig when immersedin water;Complete coil is internally evacuated, dehydrated prior to assembly.

    F. Direct-Drive Blower-Motor Assembly (Size 21 to Size 58)

    Blower of galvanized steel construction, DWDI forward curve bladesdesign, statically and dynamically balanced;

    Direct Drive motor resiliently mounted on blower inlet to assuresmooth and vibration free performance;

    Single Phase permanent split capacitor motor with permanentlylubricated ball-bearing;Motor provided with thermal overload protection.

    G. Blower Fan & Drive Package for Ducted Belt Drive units(Size 72 to Size 260)

    Fan is of Centrifugal forward curved design, with double inletdouble width, AMCA certified, suitable for Class II operation;

    Pillow block heavy duty bearings to ensure long operating life;Single large diameter fan is used, to reduce noise level,eliminates the need for common transition piece and prevent airunbalance;Complete fan-motor & drive package assembly is resiliently isolatedfrom unit casing by either rubber or spring vibration isolators;

    All fan wheels are statically and dynamically balanced to ISO1940and AMCA-204-G2.5 Standard;Optional non-overloading backward airfoil fan can be providednon-loading.

    H. Control and Safety Protection

    Balanced port thermal expansion valve is provided for eachrefrigerant circuit to control liquid refrigerant flow while maintainingadequate suction superheat, over a wide variation of condensinghead pressures;High-low pressure cut-out to protect compressor against highdischarge pressure and low refrigerant charge;

    Liquid line filter drier to ensure system dryness and prevent acidformation.

    I. Filters

    Side loading filter rack, 1 filters is provided.

    J. Optional Accessories

    Factory prewired starters and control panel including single ormulti-steps thermostat and indicating lights;1 prefilters and 15 bag filters section;Mixing Box section with fresh air and return air dampers;Suction stop valves, discharge stop valves and liquid stop valvesfor each circuit;R407c refrigerant

    DIMENSIONAL DATASWPU 100 & 130 (DBC)

    SWPU 150 & 165 (DBC)

    11

    3 48 3

    24

    11

    1614

    49

    HANGINGLUGS5/8" HOLES

    CONDENSER

    BLOWERFAN

    MOTOR

    CONDENSATEDRAIN 3/4" MPT

    CONDENSERINLET/OUTLET

    CONN J

    28

    55

    1314

    14

    ELECTRICALPANEL

    COMPRESSOR

    497

    12 13 3

    28

    14

    33

    25

    COOLINGCOIL

    43

    41

    41

    41

    41

    167

    167 2

    1

    2" DUCTCOLLAR

    Note: All dimension are in inches. Unless otherwise specified.

    Note: All dimension are in inches. Unless otherwise specified.

    FILTERRACK

    COMPRESSOR

    ELECTRICALPANEL

    30

    63

    16

    16

    14 3

    21

    167

    COOLINGCOIL

    2" DUCTCOLLAR

    FILTERRACK

    52

    12 13 32

    1625

    30

    3 7

    21

    21

    167

    HANGINGLUGS5/8" HOLES

    CONDENSER

    BLOWERFAN

    MOTOR

    CONDENSATEDRAIN 3/4" MPT

    CONDENSERINLET/OUTLET

    CONNJ

    27

    10

    1816 14

  • 7/30/2019 Ducted Unit

    6/8

    5

    Notes:

    MODELSTANDARDCAPACITY

    MBH

    kWINPUT

    AI R ON EVA P. WAT ER TEM PER AT URE OF F C ON DE NS ER - F

    STANDARDCFM

    WBTEMP.

    F

    80 95 110

    TOTALMBH

    SENSMBH

    kWTOTALMBH

    SENSMBH

    kWTOTALMBH

    SENSMBH

    kW

    SWPU 21DDC

    21.0 1.28 660

    72 23.67 12.64 1.22 22.27 11.85 1.31 20.13 10.76 1.37

    67 23.53 16.73 1.16 21.00 15.56 1.28 19.90 14.80 1.34

    62 20.56 20.60 1.16 19.00 19.00 1.25 18.16 18.20 1.31

    57 18.17 18.17 1.13 16.80 16.80 1.25 15.97 15.97 1.31

    SWPU 24DDC

    24.0 1.65 800

    72 27.01 14.36 1.57 25.45 13.52 1.69 22.97 12.23 1.76

    67 25.75 19.09 1.50 24.00 17.79 1.65 22.74 16.80 1.72

    62 23.50 23.50 1.50 21.71 21.71 1.61 20.76 20.76 1.68

    57 20.76 20.76 1.46 19.20 19.20 1.61 18.25 18.25 1.68

    SWPU 28DDC

    28.0 2.08 930

    72 31.51 16.76 1.98 29.69 15.78 2.13 26.80 14.27 2.22

    67 30.04 22.27 1.89 28.00 20.76 2.08 26.53 19.69 2.18

    62 27.42 27.42 1.89 25.33 25.33 2.03 24.22 24.22 2.13

    57 24.22 24.22 1.84 22.40 22.40 2.03 21.29 21.29 2.13

    SWPU 32DDC

    32.0 2.38 1060

    72 36.01 19.15 2.27 33.93 18.03 2.43 30.63 16.30 2.54

    67 34.34 25.45 2.16 32.00 23.72 2.38 30.32 22.50 2.49

    62 31.34 31.34 2.16 28.95 28.95 2.33 27.68 27.68 2.43

    57 27.68 27.68 2.11 25.60 25.60 2.33 24.33 24.30 2.43

    SWPU 38DDC

    38.0 2.52 1260

    72 42.77 22.73 2.41 40.29 21.41 2.58 36.37 19.36 2.70

    67 40.78 30.21 2.29 38.00 28.16 2.52 36.01 26.72 2.64

    62 37.21 37.21 2.29 34.38 34.38 2.46 32.87 32.87 2.58

    57 32.88 32.88 2.23 30.40 30.40 2.46 28.89 28.89 2.58

    SWPU 48DDC

    48.0 2.70 1600

    72 53.39 28.72 2.58 50.89 27.04 2.76 45.94 24.45 2.88

    67 51.51 38.17 2.45 48.00 35.58 2.70 45.49 33.75 2.82

    62 47.01 47.01 2.45 43.43 43.43 2.63 41.52 41.52 2.76

    57 41.52 41.49 2.38 38.40 38.40 2.63 36.49 36.49 2.76

    SWPU 58DDC

    58.0 6.50 1900

    72 65.27 34.71 6.20 61.50 32.69 6.65 55.51 29.95 6.94

    67 62.24 46.12 5.91 58.00 42.99 6.50 54.97 40.78 6.79

    62 56.80 56.80 5.92 52.48 52.48 6.35 50.17 50.17 6.66

    57 50.17 50.17 5.76 46.40 46.40 6.35 44.10 44.10 6.66

    SWPU 72DBC

    72.0 3.70 2400

    72 80.90 43.10 3.50 76.30 40.50 3.80 68.90 36.60 3.90

    67 77.30 57.30 3.40 72.00 53.40 3.70 68.20 50.60 3.90

    62 70.60 70.60 3.40 65.10 65.10 3.60 62.20 62.20 3.80

    57 62.20 62.20 3.40 57.60 57.60 3.60 54.70 54.70 3.80

    SWPU 82DBC

    82.0 4.20 2500

    72 92.30 44.80 4.00 86.90 41.90 4.30 75.50 39.80 4.40

    67 88.00 57.10 3.80 82.00 54.90 4.20 77.70 53.30 4.30

    62 80.30 68.60 3.80 74.20 66.10 4.10 70.90 64.30 4.30

    57 70.90 70.90 3.70 65.60 65.60 4.10 62.30 62.30 4.30

    PERFORMANCE TABLE

    1) Total MBH - Rating are gross capacities. For net c apacities, deduct evaporator blower motor heat.2) Sensible MBH - Capacities are based on 80F (26.6C) air on evaporator.3) kW - Compressor kW input

    DIMENSIONAL DATASWPU 21 - 58 (DDC)

    SWPU 72 - 82 (DBC)

    10

    Note: All dimension are in inches. Unless otherwise specified.

    Note: All dimension are in inches. Unless otherwise specified.

    4 45 4

    49

    24

    10

    15 1441

    53

    24

    1114

    3

    41

    4114

    167

    12 13 3

    24

    497

    41

    14

    3167

    21 FILTER

    RACK

    COOLINGCOIL

    2" DUCTCOLLAR

    ELECTRICALPANEL

    COMPRESSOR

    CONDENSATEDRAIN 3/4" MPT

    CONDENSERINLET/OUTLET

    CONN J

    HANGINGLUGS5/8" HOLES

    CONDENSER

    BLOWERFAN

    MOTOR

    CONDENSERINLET/OUTLETCONN J

    CONDENSATEDRAIN 3/4" MPT

    ACCESSPANEL

    G E

    AB

    H

    F

    C

    K

    FILTERRACK

    COOLINGCOIL

    10

    3

    3721 16

    7

    DIRECTDRIVE

    MOTOR

    ACCESSPANEL

    4 NOS.HANGING

    LUGS5/8" HOLES

    COMPRESSOR

    ELECTRICALPANEL

    2" DUCTCOLLAR

    ACCESSPANEL

    L M

    N

    6

    3

    D5

    MODEL A B C D E F G H J K L M N

    SWPU 21DDC 43 27 21 26 10 11 8 10 7 12 15

    SWPU 24DDC 43 27 21 32 10 11 8 10 7 12 15

    SWPU 28DDC 43 27 23 36 9 10 8 1 12 7 12 15

    SWPU 32DDC 43 27 23 36 9 10 8 1 12 7 12 15

    SWPU 38DDC 43 27 23 36 11 10 8 1 12 7 12 17

    SWPU 48DDC 58 27 24 52 11 10 10 12 10 16 17

    SWPU 58DDC 58 27 24 52 11 10 10 12 10 16 17

    38

    38

    38

    38

    38

    38

    38

    18

    18

    34

    34

    34

    3166

    3166

    3916

    3169

    3169

    3169

    3169

    34

    34

    141

    141

  • 7/30/2019 Ducted Unit

    7/8

    PERFORMANCE TABLE

    MODELSTANDARDCAPACITY

    MBH

    kWINPUT

    AIR ON EVAP. WATER TEMPERATURE OFF CONDENSER - F

    STANDARDCFM

    WBTEMP.

    F

    80 95 110

    TOTALMBH

    SENSMBH

    kWTOTALMBH

    SENSMBH

    kWTOTALMBH

    SENSMBH

    kW

    SWPU100DBC

    100.0 5.20 3200

    72 112.50 60.00 4.90 106.00 56.40 5.30 95.70 53.30 5.50

    67 107.30 79.80 4.70 100.00 74.50 5.20 94.80 70.50 5.40

    62 98.00 97.30 4.70 91.70 91.20 5.00 86.50 86.50 5.30

    57 86.60 86.60 4.60 80.10 80.10 5.00 76.00 76.00 5.30

    SWPU130DBC

    130.0 6.70 4000

    72 146.30 78.40 6.40 137.80 73.80 6.90 130.00 69.60 7.20

    67 139.50 103.60 6.10 130.00 96.50 6.70 123.10 91.40 7.00

    62 127.30 126.20 6.10 119.20 118.20 6.60 112.40 112.40 6.90

    57 112.40 112.40 6.00 104.30 104.30 6.60 98.80 98.80 6.90

    SWPU150DBC

    150.0 7.60 4500

    72 168.80 79.60 7.30 159.00 74.90 7.80 150.00 70.70 8.20

    67 161.00 105.00 6.90 150.00 97.90 7.60 142.00 92.70 7.90

    62 146.90 128.00 6.90 137.50 119.80 7.50 129.70 114.00 7.80

    57 129.70 114.00 6.80 120.30 105.70 7.50 114.00 100.10 7.80

    SWPU164TDBC

    164.0 8.40 5200

    72 184.30 105.30 8.00 173.70 99.10 8.60 163.90 93.30 8.90

    67 175.90 142.60 7.80 164.00 132.90 8.40 155.50 126.00 8.80

    62 160.50 160.50 7.70 150.40 150.40 8.20 141.80 141.80 8.60

    57 141.70 141.70 7.40 131.10 131.10 8.20 124.60 124.60 8.60

    SWPU165DBC

    165.0 8.60 5200

    72 185.50 105.90 8.20 174.80 99.70 8.80 164.90 93.90 9.10

    67 177.00 143.50 8.00 165.00 133.70 8.60 156.40 126.80 9.00

    62 161.50 161.50 7.90 151.30 151.30 8.40 142.60 142.60 8.80

    57 142.60 142.60 7.60 131.90 131.90 8.40 125.40 125.40 8.80

    SWPU195DBC

    195.0 10.00 6000

    72 219.30 86.70 9.60 206.70 110.00 10.30 195.00 103.70 10.60

    67 209.20 154.10 9.10 195.00 143.60 10.00 184.80 136.10 10.40

    62 190.90 187.40 9.10 178.70 175.50 9.70 168.60 168.60 10.30

    57 167.90 167.90 8.90 156.30 156.30 9.70 148.20 148.20 10.30

    SWPU200TDBC

    200.0 10.40 6000

    72 226.20 131.40 9.90 213.20 123.90 10.80 200.00 116.20 11.10

    67 212.20 175.30 9.40 200.00 165.30 10.40 187.80 155.20 10.90

    62 196.00 196.00 9.40 185.80 185.80 10.00 161.80 161.80 10.70

    57 177.80 177.80 9.20 157.60 157.60 10.00 154.50 154.50 10.70

    SWPU260TDBC

    260.0 13.40 7200

    72 292.50 154.40 12.80 275.50 145.40 13.90 259.90 137.20 14.20

    67 275.80 202.40 12.20 260.00 190.80 13.40 246.40 180.90 14.00

    62 254.40 239.40 12.20 237.40 237.40 13.00 224.80 224.80 13.90

    57 231.00 231.00 12.00 208.40 208.40 13.00 197.50 197.50 13.90

    Notes: 1) Total MBH - Rating are gross capacities. For net capacities, deduct evapor ator blower motor heat.2) Sensible MBH - Capacities are based on 80F (26.6C) air on evaporator.3) kW - Compressor kW input.

    6

    SWPU 195 DBC

    CFM0.50" WG 1.00" WG 1.50" WG 2.00" WG 2.50" WG

    RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP

    5400 745 2.17 868 2.74 983 3.32 1104 4.04 1229 4.89

    6000 791 2.79 905 3.40 1012 4.03 1115 4.70 1225 5.53

    6600 839 3.52 946 4.19 1047 4.89 1140 5.57 1235 6.34

    7200 887 4.38 988 5.10 1082 5.84 1173 6.60 1258 7.36

    SWPU 260T DBC

    CFM0.50" WG 1.00" WG 1.50" WG 2.00" WG 2.50" WG

    RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP

    6500 792 3.17 903 3.81 1006 4.50 1103 5.17 1198 5.91

    7200 850 4.12 949 4.81 1045 5.54 1137 6.30 1224 7.05

    7900 997 5.99 1089 6.78 1174 7.58 1258 8.43

    8600 1048 7.34 1133 8.20 1215 9.06 1293 9.96

    SWPU 200T DBC

    CFM0.50" WG 1.00" WG 1.50" WG 2.00" WG 2.50" WG

    RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP

    5400 745 2.17 868 2.74 983 3.32 1104 4.04 1229 4.89

    6000 791 2.79 905 3.40 1012 4.03 1115 4.70 1225 5.53

    6600 839 3.52 946 4.19 1047 4.89 1140 5.57 1235 6.34

    7200 887 4.38 988 5.10 1082 5.84 1173 6.60 1258 7.36

    9

    BLOWER PERFORMANCE TABLE contd

    % of NominalAir Flowrates

    Total CapacitySensibleCapacity

    80% 0.960 0.900

    90% 0.980 0.950

    100% 1.000 1.000

    110% 1.015 1.045

    120% 1.025 1.090

    Correction FactorsA) VARIATION in Air Flowrates

    Altitude abovesea level - ft

    Total CapacitySensibleCapacity

    0 1.00 1.00

    2000 0.99 0.93

    4000 0.97 0.88

    6000 0.95 0.82

    8000 0.93 0.76

    B) VARIATION in Altitude above SEA LEVEL

    Dry Bulb FWET BULB F

    57 F 62 F 67 F 72 F

    75 F 0.84 0.81 0.78 0.74

    80 F 1.00 1.00 1.00 1.00

    85 F 1.16 1.21 1.21 1.26

    C) VARIATION in Dry Bulb Temperature on Sensible Capacity

    If after applying the correction factor, thecalculated sensible capacity exceeds totalcooling capacity, than the sensible capacitymust be adjusted to be equal the totalcooling capacity.

    Note:

  • 7/30/2019 Ducted Unit

    8/8

    MODEL BLOWER MODEL

    Air flowrates (cfms) vs External Available Static Pressure WG

    0.2" 0.3" 0.4" 0.5" 0.6" 0.7" 0.8" 1.00"

    SWPU 21 DDCKDD 8/8,4P 165W

    870 830 730 660 510 435 N.A. N.A.

    (Alternative)KDD 8/84P 180W

    N.A. 880 810 730 605 480 N.A. N.A.

    SWPU 24 DDCKDD 8/84P 180W

    980 910 860 780 670 555 N.A. N.A.

    SWPU 28DDC KDD 9/7T4P 245W

    1060 1050 1040 970 910 870 850 N.A.

    SWPU 32 DDCKDD 9/7, Hi.

    4P 245W1280 1270 1240 1210 1150 1100 1060 N.A.

    (Alternative)KDD 9/7, Med.

    4P 245W1130 1115 1095 1070 1010 940 N.A. N.A.

    SWPU 38 DDCKDD 9/9T, Hi.

    4P 350W1420 1390 1360 1320 1280 1200 1130 N.A.

    SWPU 48 DDCKDD 9/9, Med.

    4P 550W1700 1690 1680 1670 1650 1600 1560 1470

    SWPU 58 DDCKDD 9/9, Hi.

    4P 550W2120 2110 2090 2060 2020 1980 1860 1810

    BLOWER PERFORMANCE TABLE

    Note:1. Internal losses allowed for wet coils and 1" filters.

    SWPU 72 DBC

    CFM0.50" WG 1.00" WG 1.50" WG 2.00" WG 2.50" WG

    RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP

    1800 958 0.56 1193 0.82 1433 1.15

    2250 1029 0.86 1245 1.17 1431 1.48 1618 1.85 1811 2.31

    2500 1071 1.07 1274 1.40 1456 1.74 1620 2.09 1788 2.52

    2750 1129 1.34 1316 1.69 1492 2.07 1649 2.44 1798 2.83

    SWPU 82 DBC

    CFM 0.50" WG 1.00" WG 1.50" WG 2.00" WG 2.50" WGRPM BHP RPM BHP RPM BHP RPM BHP RPM BHP

    2250 983 0.81 1205 1.10 1395 1.42 1580 1.77 1773 2.21

    2500 1050 1.05 1254 1.37 1439 1.72 1604 2.05 1771 2.48

    2750 1099 1.29 1286 1.64 1465 2.00 1625 2.39 1774 2.77

    3000 1155 1.58 1328 1.95 1498 2.35 1656 2.77 1799 3.17

    7

    SWPU 100 DBC

    CFM0.50" WG 1.00" WG 1.50" WG 2.00" WG 2.50" WG

    RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP

    2800 861 0.94 1040 1.26 1203 1.62 1391 2.11 1578 2.67

    3200 934 1.30 1095 1.65 1246 2.04 1388 2.46 1552 3.01

    3600 991 1.69 1141 2.09 1279 2.50 1412 2.94 1537 3.41

    4000 1052 2.16 1192 2.62 1322 3.06 1445 3.52 1564 4.01

    SWPU 130 DBC

    CFM0.50" WG 1.00" WG 1.50" WG 2.00" WG 2.50" WG

    RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP

    3600 939 1.56 1094 1.96 1235 2.36 1371 2.79 1497 3.25

    4000 1012 2.05 1156 2.50 1289 2.94 1413 3.40 1534 3.88

    4400 1072 2.59 1207 3.07 1332 3.56 1449 4.05 1562 4.55

    4800 1138 3.25 1264 3.76 1382 4.28 1494 4.83 1600 5.36

    SWPU 150 DBC

    CFM0.50" WG 1.00" WG 1.50" WG 2.00" WG 2.50" WG

    RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP

    4000 850 1.72 1006 2.21 1156 2.79 1302 3.44 1441 4.17

    4500 901 2.24 1046 2.78 1178 3.38 1313 4.04 1442 4.77

    5000 957 2.87 1088 3.46 1214 4.09 1333 4.78 1454 5.50

    5500 1017 3.62 1136 4.28 1255 4.94 1366 5.65 1474 6.42

    8

    SWPU 164T DBC

    CFM0.50" WG 1.00" WG 1.50" WG 2.00" WG 2.50" WG

    RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP

    4400 869 2.05 1017 2.58 1153 3.17 1291 3.81 1423 4.52

    4900 925 2.64 1058 3.22 1187 3.84 1308 4.51 1432 5.22

    5400 984 3.36 1105 4.00 1226 4.64 1339 5.34 1449 6.09

    5900 1043 4.20 1154 4.87 1266 5.58 1376 6.30 1477 7.07

    SWPU 165 DBC

    CFM0.50" WG 1.00" WG 1.50" WG 2.00" WG 2.50" WG

    RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP

    4800 894 2.43 1030 3.01 1162 3.60 1286 4.27 1412 4.97

    5200 945 2.99 1070 3.60 1196 4.23 1312 4.91 1427 5.64

    5600 998 3.64 1115 4.28 1233 4.95 1345 5.65 1451 6.40

    6000 1050 4.36 1160 5.03 1270 5.76 1379 6.48 1480 7.25

    BLOWER PERFORMANCE TABLE contd