ANALISA DAN PENGATURAN ULANG RELAI JARAK PADA SALURAN UDARA TEGANGAN TINGGI (SUTT) 150 KV KERAMASAN – BUKIT ASAM Oleh : Fikriansyah 1 , Antonius Hamdadi 2 Jurusan Teknik Elektro, Fakultas Teknik, Unsri. Kampus Unsri Bukit Palembang Email : [email protected] ABSTRAK Salah satu Proteksi Utama ( Main Protection) pada sistem proteksi jaringan transmisi saluran udara tegangan tinggi (SUTT) 150 KV adalah Relai Jarak ( distance relay ) . Agar dapat melakukan setting relai jarak yang baik dan benar pada saluran transmisi maka diperlukan analisa perhitungan sesuai dengan standar perhitungan yang telah ditetapkan Pada perhitungan analisa relai jarak ini di hitung impedansi jaringan Z 1 , Z 2 , Z 0 , Z om dan faktor Kompensasi (K o) . Dengan hasil Z 1 = 0,208 < 60 0 ohm/km, Z 2 = 0,208 < 60 0 ohm/km, ohm/km , Z 0 = 0,523<54 0 ohm/km Z om = 0,556 < 68 0 ohm/km dan K o =0,62 < 68 0 Untuk perhitungan Zona Setting relai jarak dihitung zona 1 zona 2 dan zona 3. Untuk standar waktu (t) setting untuk zona 1 di setting 0 detik, zona 2 di setting 0,4 detik dan untuk zona 3 di setting 1.2 detik. Dari hasil penelitian untuk GI keramasan – Simpang Tiga mendapatkan kesimpulan bahwa setting zona 1 dan zona 2 dari hasil perhitungan dengan lapangan tidak terlalu jauh sehingga setting masih bisa di pakai sedangkan zona 3 terdapat perbedaan maka perlu dilakukan peninjauan kembali agar relai jarak bekerja dengan baik. Kata kunci : Proteksi, Impedansi, Relai Jarak, Zona Setting, waktu Setting ABSTRACK The Other equipment main protection at the system protection transmition network High Voltage overhead lines 150 KV are Distance Relay. So that can do setting distance relay that well and right at The transmition network so required calculation analysis suitable with calculation standar already decided. The Anlysis calculation distance relai was calculated network Impedansi Z 1 , Z 2 , Z 0 , Z om. And Kompensation (K o). The Result was Z 1 = 0,208 < 60 0 ohm/km, Z 2 = 0,208 < 60 0 ohm/km, ohm/km , Z 0 = 0,523 < 54 0 ohm/km Z om = 0,556 < 68 0 ohm/km and K o =0,62 < 68 0 For calculation setting zone distance relay was calculated First zone, second zone and Third Zone. For the standart setting time (t) setting for the First Zone was adjustabe 0 second, For second zone was adjustabe 0,4 second and for the Third Zone was adjustabe 1.2 second. From result research in The GI keramasan – Simpang Tiga was found conclusion that setting 1 zone and 2 zone form calculation result with actually in the field doesn’t too far so Setting in the filed can be used whereas for 3 zone available different so require reviewed so that distance relay work better Key Word : Protection, Impedansi, ditance relay, Setting Zone, Time Setting

Upload: fikri-yansyah

Post on 06-Nov-2015

44 views

Category:

Documents


6 download

DESCRIPTION

menjelaskan tentang perhitungan di dalam mensetting relai jarak. baik menghitung Impedansi positif , impedansi negatif dan impedansi urutan nol pada saluran transmisi.

TRANSCRIPT

ANALISA DAN PENGATURAN ULANG RELAI JARAK PADASALURAN UDARA TEGANGAN TINGGI (SUTT) 150 KVKERAMASAN BUKIT ASAM

Oleh : Fikriansyah1, Antonius Hamdadi2Jurusan Teknik Elektro, Fakultas Teknik, Unsri.Kampus Unsri Bukit PalembangEmail : [email protected]

ABSTRAK

Salah satu Proteksi Utama ( Main Protection) pada sistem proteksi jaringan transmisi saluran udara tegangan tinggi (SUTT) 150 KV adalah Relai Jarak ( distance relay ) . Agar dapat melakukan setting relai jarak yang baik dan benar pada saluran transmisi maka diperlukan analisa perhitungan sesuai dengan standar perhitungan yang telah ditetapkanPada perhitungan analisa relai jarak ini di hitung impedansi jaringan Z1 , Z2 , Z0 , Zom dan faktor Kompensasi (Ko) . Dengan hasil Z1 = 0,208 < 60 0 ohm/km, Z2 = 0,208 < 60 0 ohm/km, ohm/km , Z0 = 0,523