jkr panduan teknik mekanikal ms1525:2007

81
ID CKM.BPK.EE/PTM/09/01 VERSI 01 TARIKH 1 JUN 2009 PANDUAN TEKNIK MEKANIKAL PTM 1/2009 GARIS PANDUAN PEMATUHAN KEPADA MS 1525:2007 Bahagian Pembangunan Kepakaran Cawangan Kejuruteraan Mekanikal Ibu Pejabat JKR Malaysia UNIT KECEKAPAN TENAGA DAN TENAGA DIPERBAHARUI

Upload: alex-chin

Post on 12-Jan-2016

1.373 views

Category:

Documents


255 download

DESCRIPTION

Malaysia JKR mechanical guideline MS1525:2007

TRANSCRIPT

Page 1: JKR Panduan Teknik Mekanikal MS1525:2007

ID CKM.BPK.EE/PTM/09/01

VERSI 01

TARIKH 1 JUN 2009

PANDUAN TEKNIK MEKANIKAL

PTM 1/2009

GARIS PANDUAN PEMATUHAN KEPADA MS 1525:2007

Bahagian Pembangunan Kepakaran Cawangan Kejuruteraan Mekanikal

Ibu Pejabat JKR Malaysia

UN

IT K

EC

EK

APA

N T

EN

AG

A D

AN

TE

NA

GA

DIP

ER

BA

HA

RU

I

Page 2: JKR Panduan Teknik Mekanikal MS1525:2007

PTM.01-2009: REV 1 Tarikh: 1 hb Jun 2009

__________________________________________________________________________________

Seksyen Pembangunan Kepakaran Cawangan Kejuruteraan Mekaniakal

JADUAL KANDUNGAN 1. LATARBELAKANG....................................................................................... 2 2. TUJUAN ....................................................................................................... 2 3. SKOP............................................................................................................ 2 4. TARIKH KUATKUASA.................................................................................. 3 5. TANGGUNGJAWAB..................................................................................... 3 6. KAEDAH PEMATUHAN ............................................................................... 3

LAMPIRAN A: MS 1525:2007

LAMPIRAN B: DESIGN COMPLIANCE CHECKLIST

LAMPIRAN C: SAMPLE OF SUPPORT EVIDENCE DOCUMENTS

LAMPIRAN D: BORANG JKR.PK(0).02-2 (BORANG KAJIAN

SEMULA/VERIFIKASI/VALIDASI)

Page 3: JKR Panduan Teknik Mekanikal MS1525:2007

PTM.01-2009: REV 1 Tarikh: 1 hb Jun 2009

__________________________________________________________________________________

Seksyen Pembangunan Kepakaran Cawangan Kejuruteraan Mekaniakal

2

1. LATARBELAKANG Malaysia sebagai sebuah negara yang pesat membangun telah mewujudkan

permintaan yang tinggi kepada tenaga domestik dan juga sumber asli negara.

Operasi bangunan adalah di antara pengguna tenaga yang tinggi dan

penyumbang kepada pencemaran alam sekitar bersama-sama sektor lain

seperti pengangkutan dan industri pembuatan. Bagi mengurangkan kos tenaga

dan pemcemaran kepada alam sekitar, aspek kecekapan tenaga perlu diberi

penekanan sewajarnya.

Bagi mengalakkan kecekapan tenaga di dalam rekabentuk bangunan baru,

Malaysian Standard MS 1525:2007 –Code of Practise on Energy Efficiency and

Use of Renewable Energy for Non-Residential Buildings telah diperkenalkan dan

ianya mengariskan kriteria dan piawaian minima untuk kecekapan tenaga di

dalam bangunan di samping menggalakkan aplikasi tenaga lestari didalam

bangunan. Garispanduan Bangunan Piawai 2008, yang dikeluarkan oleh Unit

Perancang Ekonomi, Jabatan Perdana Menteri telah mewajibkan pematuhan

rekabentuk bangunan kepada MS 1525:2007.

2. TUJUAN Tujuan garis panduan ini adalah untuk memastikan rekabentuk sistem

mekanikal dan sistem sokongan mematuhi keperluan minimum MS 1525:2007.

3. SKOP Skop perlaksanaan;

i. Jenis Bangunan - Bangunan baru bukan kediaman yang mempunyai kadar

rekabentuk puncak tenaga elektrik melebihi 10W/m2.

- Keperluan Khas: Energy Management Control System perlu

dipasang bagi keluasan ruang hawa dingin melebihi 4000 m2 .

Page 4: JKR Panduan Teknik Mekanikal MS1525:2007

PTM.01-2009: REV 1 Tarikh: 1 hb Jun 2009

__________________________________________________________________________________

Seksyen Pembangunan Kepakaran Cawangan Kejuruteraan Mekaniakal

3

ii. Kaedah Rekabentuk

- Semua projek yang direkabentuk samada yang dijalankan secara

reka & tender atau reka & bina.

4. TARIKH KUATKUASA Semua projek yang menerima ringkasan projek selepas 1hb Mei 2009.

5. TANGGUNGJAWAB Head of Design Team (HODT) adalah bertanggungjawab untuk memastikan

pematuhan kepada garis panduan ini.

6. KAEDAH PEMATUHAN HODT hendaklah menggunakan senarai semak berserta dokumen-dokumen

sokongan berkaitan seperti di Lampiran B, C & D. Senarai semak perlu

disediakan di peringkat Verifikasi Rekabentuk dan dikepilkan bersama-sama

dengan Borang JKR.PK(0).02-2 (Borang Kajian Semula/Verifikasi/Validasi).

Page 5: JKR Panduan Teknik Mekanikal MS1525:2007

PTM.01-2009: REV 1 Tarikh: 1 hb Jun 2009

__________________________________________________________________________________

Seksyen Pembangunan Kepakaran Cawangan Kejuruteraan Mekaniakal

4

SENARAI LAMPIRAN Lampiran A: MS 1525:2007

Lampiran B: Senarai Semak

Lampiran C: Contoh Dokumen Sokongan

Lampiran D: Borang JKR.PK(0).02-2 -Borang Kajian Semula/Verifikasi/Validasi

Page 6: JKR Panduan Teknik Mekanikal MS1525:2007

LAMPIRAN A: MS 1525:2007

Page 7: JKR Panduan Teknik Mekanikal MS1525:2007
Page 8: JKR Panduan Teknik Mekanikal MS1525:2007
Page 9: JKR Panduan Teknik Mekanikal MS1525:2007
Page 10: JKR Panduan Teknik Mekanikal MS1525:2007
Page 11: JKR Panduan Teknik Mekanikal MS1525:2007
Page 12: JKR Panduan Teknik Mekanikal MS1525:2007
Page 13: JKR Panduan Teknik Mekanikal MS1525:2007
Page 14: JKR Panduan Teknik Mekanikal MS1525:2007
Page 15: JKR Panduan Teknik Mekanikal MS1525:2007
Page 16: JKR Panduan Teknik Mekanikal MS1525:2007
Page 17: JKR Panduan Teknik Mekanikal MS1525:2007
Page 18: JKR Panduan Teknik Mekanikal MS1525:2007
Page 19: JKR Panduan Teknik Mekanikal MS1525:2007
Page 20: JKR Panduan Teknik Mekanikal MS1525:2007
Page 21: JKR Panduan Teknik Mekanikal MS1525:2007
Page 22: JKR Panduan Teknik Mekanikal MS1525:2007
Page 23: JKR Panduan Teknik Mekanikal MS1525:2007
Page 24: JKR Panduan Teknik Mekanikal MS1525:2007
Page 25: JKR Panduan Teknik Mekanikal MS1525:2007
Page 26: JKR Panduan Teknik Mekanikal MS1525:2007
Page 27: JKR Panduan Teknik Mekanikal MS1525:2007
Page 28: JKR Panduan Teknik Mekanikal MS1525:2007
Page 29: JKR Panduan Teknik Mekanikal MS1525:2007
Page 30: JKR Panduan Teknik Mekanikal MS1525:2007
Page 31: JKR Panduan Teknik Mekanikal MS1525:2007
Page 32: JKR Panduan Teknik Mekanikal MS1525:2007
Page 33: JKR Panduan Teknik Mekanikal MS1525:2007
Page 34: JKR Panduan Teknik Mekanikal MS1525:2007
Page 35: JKR Panduan Teknik Mekanikal MS1525:2007
Page 36: JKR Panduan Teknik Mekanikal MS1525:2007
Page 37: JKR Panduan Teknik Mekanikal MS1525:2007
Page 38: JKR Panduan Teknik Mekanikal MS1525:2007
Page 39: JKR Panduan Teknik Mekanikal MS1525:2007
Page 40: JKR Panduan Teknik Mekanikal MS1525:2007
Page 41: JKR Panduan Teknik Mekanikal MS1525:2007
Page 42: JKR Panduan Teknik Mekanikal MS1525:2007
Page 43: JKR Panduan Teknik Mekanikal MS1525:2007
Page 44: JKR Panduan Teknik Mekanikal MS1525:2007
Page 45: JKR Panduan Teknik Mekanikal MS1525:2007
Page 46: JKR Panduan Teknik Mekanikal MS1525:2007
Page 47: JKR Panduan Teknik Mekanikal MS1525:2007
Page 48: JKR Panduan Teknik Mekanikal MS1525:2007
Page 49: JKR Panduan Teknik Mekanikal MS1525:2007
Page 50: JKR Panduan Teknik Mekanikal MS1525:2007
Page 51: JKR Panduan Teknik Mekanikal MS1525:2007
Page 52: JKR Panduan Teknik Mekanikal MS1525:2007
Page 53: JKR Panduan Teknik Mekanikal MS1525:2007
Page 54: JKR Panduan Teknik Mekanikal MS1525:2007
Page 55: JKR Panduan Teknik Mekanikal MS1525:2007
Page 56: JKR Panduan Teknik Mekanikal MS1525:2007
Page 57: JKR Panduan Teknik Mekanikal MS1525:2007
Page 58: JKR Panduan Teknik Mekanikal MS1525:2007
Page 59: JKR Panduan Teknik Mekanikal MS1525:2007
Page 60: JKR Panduan Teknik Mekanikal MS1525:2007
Page 61: JKR Panduan Teknik Mekanikal MS1525:2007
Page 62: JKR Panduan Teknik Mekanikal MS1525:2007

LAMPIRAN B: DESIGN COMPLIANCE CHECKLIST

Page 63: JKR Panduan Teknik Mekanikal MS1525:2007

PART 1PART 2PART 3PART 4PART 5PART 6PART 7PART 8PART 9

PART 1

PART 1PART 2

PART 1

MECHANICAL SERVICES MS 1525:2007 DESIGN COMPLIANCE CHECKLIST

SECTION 1: AIR-CONDITIONING AND MECHANICAL VENTILATION SYSTEM

CABLING

ACMV SYSTEM

LOAD CALCULATIONSSYSTEMS AND EQUIPMENT SIZINGSEPARATE AIR DISTRIBUTION SYSTEMS CONTROLS

ENERGY MANAGEMENT SYSTEM (EMS) REQUIREMENTS

PIPING INSULATIONAIR HANDLING DUCT SYSTEM INSULATIONDUCT CONSTRUCTIONBALANCING

SECTION 2: AIR LEAKAGE

SECTION 3: ELECTRIC POWER AND DISTRIBUTION

SECTION 4: ENERGY MANAGEMENT SYSTEM

AIR LEAKAGE

ALTERNATIVE CURRENT (A.C) ELECTRIC MOTORS

Page 64: JKR Panduan Teknik Mekanikal MS1525:2007

PART 1 EXPLAINATORY NOTES

SUPPORTING EVIDENCE (to be attached together with the checklist)

S1-1-1 Heat load calculation shall be performed for each air side system (minimum) or if using computerised heat load calculation, each space shall be calculated independantly. Rule of Thumb method of using btu/hr.sq.ft is not acceptable

S1-1-2

Design temp: 24ºC

Design RH: 55%

S1-1-3 -Only required if using peak load calculation method (spreadsheet)

- For computerised heat load calculation (hourly analysis) , hourly weather data shall be used

S1-1-4

Self explainatory

PART 2 EXPLAINATORY NOTES

SUPPORTING EVIDENCE (to be attached together with the checklist)

S1-2-1 Oversizing will result in drop in efficiency and shall be avoided. SE-1

S1-2-2Say if 1000 TR chillers are selected to serve 800TR building cooling load, multi compressors shall be provided. Another example is chiller serving day and night load.

S1-2-3

Self explainatory

The ACMV system equipment sizing is determined according to latest edition of the ASHRAE handbook or other equivalent publication e.g CIBSE

SYSTEMS AND EQUIPMENT SIZING

For chiller design load (plant capacity) greater than 1000 kWr (280 RT), a minimum of two(2) chillers or a single multi-compressor chiller shall be provided to meet the required load.

LOAD CALCULATIONS

Redundancy in capacity of equipment, if incorporated into the sizing of duty equipment should include efficiency devices such as variable speed drive, high efficiency motor,efficient unloading devices, multi compressors etc so as not to diminish the equipment/system efficiency when operaring at varying loads.

Indoor design conditions of an air-cond space for comfort cooling should be as follows:

i). Dry bulb temperature; 33.3ºC

ii). Wet bulb temperature; 27.2ºC

Outdoor air-ventilation rates should comply with Third Schedule (By Law 41) Article 12(1) of Uniform Building by Laws, 1984. Exception: Outdoor air quantites may exceed those shown, if required due to special occupancy or process requirements or source control of air contamination or indoor air quality consideration.

ACMV system and equipment sizing is sized to provide no more than the space and loads calculated.

MECHANICAL SERVICES MS 1525:2007 DESIGN COMPLIANCE REQUIREMENTS

Operating hours

BUILDING PARTICULARS

Building Purpose:

PROOF OF COMPLIANCE TO MS 1525: 2007 ( CODE OF PRACTISE ON ENERGY EFFICIENCY AND USE OF RENEWABLE ENERGY FOR NON-RESIDENTIAL BUILDINGS)

SECTION 1: AIR-CONDITIONING AND MECHANICAL VENTILATION SYSTEM

Name of development:

Total gross floor area (m2)

Total air conditioning area (m2)

SE-1

SE-2

i). Recommended design dry bulb temperature; 23ºC - 26ºC

ii). Minimum dry bulb temperature; 22ºC

iii). Recommended design relative humidity; 55% - 70%

iv). Recommended air movement; 0.15 m/s - 0.5 m/s (Max 0.7 m/s)

The recommended outdoor design conditions shall be as follows:

Page 65: JKR Panduan Teknik Mekanikal MS1525:2007

MECHANICAL SERVICES MS 1525:2007 DESIGN COMPLIANCE REQUIREMENTS

Operating hours

BUILDING PARTICULARS

Building Purpose:

PROOF OF COMPLIANCE TO MS 1525: 2007 ( CODE OF PRACTISE ON ENERGY EFFICIENCY AND USE OF RENEWABLE ENERGY FOR NON-RESIDENTIAL BUILDINGS)

SECTION 1: AIR-CONDITIONING AND MECHANICAL VENTILATION SYSTEM

Name of development:

Total gross floor area (m2)

Total air conditioning area (m2)

S1-2-4

Energy Management Control System shall be provided for air conditioning system serving area greater than 4000m².

SE-2

S1-2-5

Self explainatory Refer specification

PART 3 EXPLAINATORY NOTES

SUPPORTING EVIDENCE (to be attached together with the checklist)

S1-3-1

Self explainatory

S1-3-2

Separate system required for comfort cooling and process cooling.

S1-3-3 Perimeter zone has higher Sensible Heat Factor (SHF) thus requires more air flow with higher supply air temperature. Interior zone has lower SHF and requires lower air flow with lower supply air temperature.

S1-3-4

Self explainatory

PART 4 EXPLAINATORY NOTES

SUPPORTING EVIDENCE (to be attached together with the checklist)

S1-4-1No specific requirement to have thermostat control for each circuit (compressors). It is suggested that at least load modulation up to 50%. E.g for 4 nos of compressors, 2 compressors should be provided with multistage thermostate.

Refer specification

CONTROLS

SEPARATE AIR DISTRIBUTION SYSTEMS

Zones which are expected to operate non-simultaneously for more than 750 hrs per year should be served by separate air distribution systems. (e.g 24/7 space and 8/5 space). Alternatively off-hour controls should be provided (see 1-4-7)

Separate air distribution systems should be considered for areas of the building having substantially different cooling charateristics, such as perimeter zones (3m room depth) in contrast to the interior zones.

Multiple unit of the same equipment type, such as multiple chillers, with combined capacities exceeding the design load shall be specified to operate concurrently only if controls are provided which sequence or otherwise optimally control the operation of each unit based on the required cooling load (Energy Management Control System)

Each system should be provided with at least one (1) thermostat. Each thermostat should be capable to set between 22ºC to 27ºC. Multi stage thermostat should be provided for equipment exceeding 35/65 kWr (multicompressors).

For air conditioned space requiring exhaust air volume in excess of 3400 m3/h (2000 cfm), not less than 85% of non conditioned make-up air should be introduced directly into the space concerned unless the exhausted conditioned air is utilised for secondary cooling purposes. Altenatively,heat recovery devices should be provided.

Individual air-cooled or water cooled Direct Expansion (DX) units greater than 35 kWr (10 RT) (reciprocating compressor) or 65 kWr (18 RT) (scroll compressor) should consists of either multi compressors or single compressor with step/variable unloaders.

SE-3

Zones with special process temperature and/or humidity requirements should be served by separate air distribution system/s from those serving zones requiring only comfort cooling or should include supplementary provisions so that primary system/s may be specifically controlled for comfort purposes only. Exception is for zones requiring comfort only which are served by a system primarily used for process temperature and humidity control, need not be served by a separate system if the total supply air to these zones is no more than 25% of the total system supply air, or the total air conditioned floor area of the zones is less than 100 m 2.

Page 66: JKR Panduan Teknik Mekanikal MS1525:2007

MECHANICAL SERVICES MS 1525:2007 DESIGN COMPLIANCE REQUIREMENTS

Operating hours

BUILDING PARTICULARS

Building Purpose:

PROOF OF COMPLIANCE TO MS 1525: 2007 ( CODE OF PRACTISE ON ENERGY EFFICIENCY AND USE OF RENEWABLE ENERGY FOR NON-RESIDENTIAL BUILDINGS)

SECTION 1: AIR-CONDITIONING AND MECHANICAL VENTILATION SYSTEM

Name of development:

Total gross floor area (m2)

Total air conditioning area (m2)

S1-4-2

Self explainatory SE-3

S1-4-3

Self explainatory

S1-4-4

Thermostat shall be located within zone with substantially highest cooling load requirements.

S1-4-5Alternatives system including using heat pipes, condenser water, desuperheaeter heat reclaim, heat recovery wheel etc. No restriction for process cooling.

S1-4-6

Thermostat shall be located within zone with highest cooling load requirements.

S-1-4-7

Self explainatory

S1-4-8

E.g: All system above 2kWe shall be provided with at least timer or remote controller.

At least one thermostate for regulation of space temperature shall be provided each separate zone (as stipulated in Section 1-Part 3) and system. As a minimum, each floor of a building should be considered as a separate zone. On a multistorey building where the perimeter system offsets only the transmission gains of the exterior wall, an entire side of uniform exposure may be zones separately. A readily accesible manual or automatic means should be provided to partially restrict or shut off the cooling input (for the exposure) to each floor.

For multi zone system, other than those employing the variable air volume for temperature control, should be provided with controls that will automatically reset the off-coil supply to the highest temperature that will satisfy the zone requiring the coolest air.

Each system should be equipped with a readily accesible means of shutting off or reducing the energy used during the periods on non-use or alternate uses of the building spaces or zones served by the system via either manually adjustable automatic timing devices, manual devices for use by operating personnel or automatic control system.

It is recommended that consideration be given to the use of recovery systems which will conserve energy (provided the amount expended is less than the amount recovered) when the energy transfer potential and the operating hours are considered. Recovered energy in the excess of the new source of energy expended in the recovery process may be used for control of temperature and humidity. Examples include the use of condenser water for reheat, desuperheater heaet reclaim, heat recovery wheel, heat pipe or any other energy recovery technology.

For off-hour control, ACMV system should be equipped with automatic conrtrol to reduce the energy-use when equipment shutdown during period of non-use. Eg: timer, scheduler. Exception:-

Systems employing reheat where permitted in S-1-4-5 and serving multiple zones, other than those employing variable air volume for temperature control, should be provided with controls that will automatically reset the system cold air supply to the highest temperature level that will satisfy the zone requiring the coolest air. single zone reheat systems should be controlled to sequence reheat and cooling.

In a system requiring moisture removal to maintain specific selected relative humidity in spaces or zones, no new source of energy such as electric reheat should be used to produce a space relative humidity below 70% for comfort cooling purpose.

SE-4

a). System serving area which are expected to operate continuously.b). Equipment with connected load less than 2kWe may be controlled by manual off-hour control.

Page 67: JKR Panduan Teknik Mekanikal MS1525:2007

MECHANICAL SERVICES MS 1525:2007 DESIGN COMPLIANCE REQUIREMENTS

Operating hours

BUILDING PARTICULARS

Building Purpose:

PROOF OF COMPLIANCE TO MS 1525: 2007 ( CODE OF PRACTISE ON ENERGY EFFICIENCY AND USE OF RENEWABLE ENERGY FOR NON-RESIDENTIAL BUILDINGS)

SECTION 1: AIR-CONDITIONING AND MECHANICAL VENTILATION SYSTEM

Name of development:

Total gross floor area (m2)

Total air conditioning area (m2)

Motorised damper provides less resistance to air flow compared to gravity dampers. It should be interlocked with AHU operation.

S1-4-10

Self explainatory

S1-4-11Self explainatory

S1-4-12 For central systems and plants, controls and

devices shall be provided to allow stable system and equipment operation for any length of time while serving only the smallest isolation areas

served by the system or plant.

S1-4-13

E.g lift motor room ventilation system-thermostat,

S1-4-14

Self explainatory

PART 5 EXPLAINATORY NOTES

SUPPORTING EVIDENCE (to be attached together with the checklist)

S1-5-1

Self explainatory Refer specification

For fan system with air-flow rate exceeding 17000 m 3/hr and operating more than 750 hours a year, the power required by the motor for entire fan system should not exceed 0.45 W per m 3/hr of air flow rate.

PIPING INSULATION

Each mechanical ventilation system (supply and/or exhaust) should be equipped with a readily accessible switch or other means for shut-off or volume reduction when ventilation is not required. Examples of such devices would include timer switch control, thermostat control, duty cycle programming and CO/CO2 sensor control.

All piping installed to serve buildings and within buildings should be adequately insulated to prevent excessive energy losses. Additional insulation with vapour barriers may be required to prevent condensation under some conditions. Refer JKR specification.

Systems that serve zones which can be expected to operate non-simultaneously for more than 750 hours per year should include isolation devices and controls to shut off the supply of cooling to each zone independently. Isolation is not required for zones expected to operate continuously.

Zones may be grouped into a single isolation area provided the total conditioned floor area does not exceed 250 sq.m per group nor include more than one floor unless variable air volume or equivalent devices are incorporated. Use of outside economy air cycle design where feasible should be considered.

d) where restricted by process requirements such as combustion air intakes

For buildings where occupancy patterns are not known at time of system design, isolation areas should be pre-designed.

a). System serving areas which are expected to operate continuously.

SE-3

S1-4-9 Outdoor air supply and exhaust system should be provided with motorised or gravity dampers or other means to automatic shut-off during period of non-use.Exception:

b). System which have design air flow rate of 1800cu.m/h or less.

c). Gravity and other non-electrical ventilation which can be controlled by readily accessible manual dampers control..

Page 68: JKR Panduan Teknik Mekanikal MS1525:2007

MECHANICAL SERVICES MS 1525:2007 DESIGN COMPLIANCE REQUIREMENTS

Operating hours

BUILDING PARTICULARS

Building Purpose:

PROOF OF COMPLIANCE TO MS 1525: 2007 ( CODE OF PRACTISE ON ENERGY EFFICIENCY AND USE OF RENEWABLE ENERGY FOR NON-RESIDENTIAL BUILDINGS)

SECTION 1: AIR-CONDITIONING AND MECHANICAL VENTILATION SYSTEM

Name of development:

Total gross floor area (m2)

Total air conditioning area (m2)

PART 6 EXPLAINATORY NOTES

SUPPORTING EVIDENCE (to be attached together with the checklist)

Self explainatory

PART 7 EXPLAINATORY NOTES

SUPPORTING EVIDENCE (to be attached together with the checklist)

S1-7-1

Self explainatory Refer specification

S1-7-2

SMACNA recommendationRefer specification or standard detail

drawings

S1-7-3

Self explainatory Refer specification

S1-7-4

Self explainatory Refer specification

S1-7-5

Self explainatory Refer specification

PART 8 EXPLAINATORY NOTES

SUPPORTING EVIDENCE (to be attached together with the checklist)

S1-8-1

Self explainatory SE-2 & SE-3

When low pressure supply air ducts are located outside of the conditioned space (except return air plenums), all transverse joints should be sealed using mastic plus tape or equivalent material. For fibrous glass ductwork, pressure sensitive tape is acceptable.

Automatic or manual dampers installed for the purpose of shutting off outside air intake for ventilation air should be designed with tight shut-off characteristics to minimise air leakage.

High pressure and medium pressure ducts should be leak tested in accordance with HVAC Air Duct Leakage Test Manual published by SMACNA or any other equivalent standards, with the rate of leakage not to exceed the maximum rate specified.

All ductwork was constructed and erected in accordance with ANSI/SMACNA 006-2006 HVAC Duct Construction Standards-Metal and Flexible published by SMACNA or other equivalent duct construction standards.

DUCT CONSTRUCTION

All AHU & FCU shall have minimum straight duct length of 2 1/2 times duct diameter or longest side for rectrangular duct after the fan outlet before any bend.

The system design should provide means for balancing the air and water system such as but limited to dampers, temperature and pressure test connections and balancing valve.

BALANCING

AIR HANDLING DUCT SYSTEM INSULATION

a). Where the design temperature differential between the air in the duct and the surrounding air is 8ºC or less provided that the duct is within the air-conditioned space. b). When the heat gain or loss of the ducts, without insulation, will not increase the energy requirements of the buildings.

S1-6-1 All ducts, plenums and enclosures installed in or on buildings should be adequately insulated to prevent excessive energy losses. Additional insulation with vapour barriers may be required to prevent condensation under some conditions. Exceptions: Duct insulation is not required in the following cases:-

Refer specification

c). Within ACMV equipment.

d). Exhaust air ducts subject to qualification as in (a) above.

Page 69: JKR Panduan Teknik Mekanikal MS1525:2007

MECHANICAL SERVICES MS 1525:2007 DESIGN COMPLIANCE REQUIREMENTS

Operating hours

BUILDING PARTICULARS

Building Purpose:

PROOF OF COMPLIANCE TO MS 1525: 2007 ( CODE OF PRACTISE ON ENERGY EFFICIENCY AND USE OF RENEWABLE ENERGY FOR NON-RESIDENTIAL BUILDINGS)

SECTION 1: AIR-CONDITIONING AND MECHANICAL VENTILATION SYSTEM

Name of development:

Total gross floor area (m2)

Total air conditioning area (m2)

PART 9 EXPLAINATORY NOTES

SUPPORTING EVIDENCE (to be attached together with the checklist)

S1-9-1

Self explainatory Refer specification

S1-9-2Self explainatory Refer specification

S1-9-3

Self explainatory Refer specification

An operation and maintenance manual (OMM) and as-built drawing should be provided to the owner. The manual should include basic data relating to the operation and maintenance of ACMV systems and equipment. Required routine maintenance action should be clearly identified. Where applicable, ACMV controls information such as diagrams, schematics, control sequence descriptions and maintenance and calibration information should be included.

ACMV SYSTEM

ACMV components standard rating temperature and minimum COP to comply with MS1525 Table 18, Table 19, Table 20, Table 21, table 22 and table 23.

ACMV control system shoud be tested (T&C) to assure that control elements are calibrated and in proper working condition.

Page 70: JKR Panduan Teknik Mekanikal MS1525:2007

PART 1EXPLAINATORY NOTES

SUPPORTING EVIDENCE (to be attached together with

the checklist)S2-1-1

Architects to be advised SE-3 (coordination with architects)

S2-1-2

Self explainatory SE-3

S2-1-3

Self explainatory SE-3 (coordination with architects)

Self explainatory

Total gross floor area (m2)

PROOF OF COMPLIANCE TO MS 1525: 2007 ( CODE OF PRACTISE ON ENERGY EFFICIENCY AND USE OF RENEWABLE ENERGY FOR NON-RESIDENTIAL BUILDINGS)

BUILDING PARTICULARSName of development:

AIR LEAKAGE

Building Purpose:Operating hours

S2-1-4 Door that separates conditioned space from exterior should be protected by an enclosed vestibule, with all doors opening into and out of the vestibules equipped with slef closing devices. Vestibules shall should be designed so that in passing through the vestibule, it is not necessary for the interior and exterior doors to open at the same time. Interior and exterior doors should have a minimum distance between them of not less than 2.5 meters when in closed position.

MECHANICAL SERVICES MS 1525:2007 DESIGN COMPLIANCE CHECKLIST

SE-3 (coordination with architects)

i. Doors in buildings less than four storeys above groundii. Door not intended to be used as a building entrance door, such as mechanical or electrical equipment rooms.

iii. Doors opening directly from a residential unit.

Total air conditioning area (m2)

SECTION 2: AIR LEAKAGE

iv. Doors that open directly from a space less than 300 sq.meter in area.

v. Doors in building entrances with revolving doors

vi. Doors used in primarily to facilitate vehicular movement or material handling and adjacent personnel doors.

Provide advisory label for all openable fenestrations and doors between conditioned space and non conditioned space.

Any duct connection between air conditioned space to outside air should have motorised damper in between to prevent air leakagesinto air conditioned space when the duct is not in operation.

If false ceiling is used as return air plenum to the AHU, partition to be provided in the false ceiling space between air conditioned space and naturally ventilated space to prevent air leakage.

Page 71: JKR Panduan Teknik Mekanikal MS1525:2007

PART 1 EXPLAINATORY NOTES ACCEPTANCE CRITERIA

SUPPORTING EVIDENCE (to be

attached together with the checklist)

S3-1-1

Self explainatory Yes Refer specification

S3-1-2

Self explainatory Yes Refer specification

S3-1-3

Self explainatory Yes Refer specification

S3-1-4Variable speed drive should only be considered for highly variable

and high loads.Yes Refer specification

PART 2 EXPLAINATORY NOTES ACCEPTANCE CRITERIA

SUPPORTING EVIDENCE (to be

attached together with the checklist)

S3-2-1

Self explainatory Yes Refer specification

S3-1-2

Self explainatory Yes Refer specification

All inverters or devices with electronic switching gates shall be of at least th 12-pulse type. The 24-pulse type is recommended to minimse harmonic distortion.

Motors used more than 2000 hours per years shall be EFF1. All other motor operating less than 2000 hours shall be EFF2 (excluding motor used for fire protection system or any other emergency system). Refer to Table 15 and Table 16 of MS 1525 for EFF 1 and EFF 2 efficiency classification.

If specific circumstances apply , motor continuous rating should not normally exceed 30 % of its estimated maximum load .

Power factor for motors shall be corrected to better than 0.85 when operating at duty point.

Where applicable , inverter controlled motor drives shall be used to control the speed of the motor for variable load. Soft starters shall be specified for motors exceeding 7.5 h.p/ 5.0 kW.

The cross section of cable and wires should comply with the provisions of MS IEC 60364 on Electrical Installations of Buildings.

CABLING

MECHANICAL SERVICES MS 1525:2007 DESIGN COMPLIANCE CHECKLIST

Total air conditioning area (m2)

Total gross floor area (m2)

PROOF OF COMPLIANCE TO MS 1525: 2007 ( CODE OF PRACTISE ON ENERGY EFFICIENCY AND USE OF RENEWABLE ENERGY FOR NON-RESIDENTIAL BUILDINGS)

BUILDING PARTICULARSName of development:

SECTION 3: ELECTRIC POWER AND DISTRIBUTION

ALTERNATIVE CURRENT (A.C) ELECTRIC MOTORS

Building Purpose:Operating hours

Page 72: JKR Panduan Teknik Mekanikal MS1525:2007

PART 1

EXPLAINATORY NOTES

SUPPORTING EVIDENCE (to be attached together

with the checklist)

Refer specification

PROOF OF COMPLIANCE TO MS 1525: 2007 ( CODE OF PRACTISE ON ENERGY EFFICIENCY AND USE OF RENEWABLE ENERGY FOR NON-RESIDENTIAL BUILDINGS)

BUILDING PARTICULARS

S4-1-1

Name of development:

Total air conditioning area (m2)

SECTION 4: ENERGY MANAGEMENT SYSTEM

MECHANICAL SERVICES MS 1525:2007 DESIGN COMPLIANCE CHECKLIST

iii). Temporary override of the time schedules to accommodate changes in usage.iv). Chilled water leaving and entering temperature reset v).Control loop set point reset algorithm.

Building Purpose:

ENERGY MANAGEMENT SYSTEM (EMS) REQUIREMENTS (ONLY APPLICABLE FOR BUILDINGS WITH AIR

CONDITIONED AREA EXCEEDING 4000m2)

Operating hours

Total gross floor area (m2)

Can be achieved via Building Automation System and Chiller Multiple Control System

(Note: High level interfacing is required for Item iv -viii. Alternatively, they can also be executed by chiller control panel/multiple chiller controller.

The EMS should be supplied with full complement of energy management features including but not limited to:-

i). Direct digital control algorithms.ii). Starting and stopping of equipment based on a time schedule.

viv). HVAC Energy (Electrical & Thermal) tracking and reporting (Historical data) i.e Refrigeration Plant, pumps, cooling tower, AHU/FCU

vi).Chiller sequencing and optimisation algorithm.vii).Demand limiting algorithm.viii).Duty cycle algorithm.

Page 73: JKR Panduan Teknik Mekanikal MS1525:2007

Support Documents List

Index Description Submitted (Y/N)

SE-1 Peak Air Conditioning load calculation OR computerised air conditioning load load calculation using E20-II, TRACE 700, CAMEL, IES or any equivalent softwares

SE-2 HVAC Piping & Instrumentation Diagram (PNID)

SE-3 Air Distribution Layout Drawings

SE-4 AHU Control Schematic

Page 74: JKR Panduan Teknik Mekanikal MS1525:2007

LAMPIRAN C: SAMPLE OF SUPPORT EVIDENCE

DOCUMENTS

Page 75: JKR Panduan Teknik Mekanikal MS1525:2007
Page 76: JKR Panduan Teknik Mekanikal MS1525:2007
Page 77: JKR Panduan Teknik Mekanikal MS1525:2007
Page 78: JKR Panduan Teknik Mekanikal MS1525:2007
Page 79: JKR Panduan Teknik Mekanikal MS1525:2007

LAMPIRAN D: Borang JKR.PK(0).02-2 (Borang

Kajian Semula / Verifikasi / Validasi)

Page 80: JKR Panduan Teknik Mekanikal MS1525:2007

REKOD KAJIAN SEMULA / VERIFIKASI

/ VALIDASI REKABENTUK

JKR.PK(O).02-2

@ HAKCIPTA JKR MALAYSIA DOKUMEN TERKAWAL

Borang JKR.PK(O).02-2

KAJIAN SEMULA / VERIFIKASI / VALIDASI (*)

TAJUK PROJEK

NO. PROJEK

NO. FAIL

SKOP PERBINCANGAN

TEMPAT/ TARIKH/MASA

KEHADIRAN Nama Jawatan

Page 81: JKR Panduan Teknik Mekanikal MS1525:2007

REKOD KAJIAN SEMULA / VERIFIKASI

/ VALIDASI REKABENTUK

JKR.PK(O).02-2

@ HAKCIPTA JKR MALAYSIA DOKUMEN TERKAWAL

Bil.

No. Lukisan/ Spesifikasi (*) Ulasan

(Guna lampiran tambahan jika perlu) (*) Potong yang tidak berkenaan. Diluluskan oleh, …………………………………… HOPT/ HODT* Tanda tangan, Tarikh Nota: * - mengikut peringkat mana yang berkenaan.