hi essence cable spec

67
1/67 HI-ESSENCE CABLE SDN. BHD. Factory address: Lot 13662, Kerteh Plastic Park, Kemaman, Terengganu. Office address: No.2, Jalan Puteri 5/16, Bandar Puteri, 47100 Puchong, Selangor. Tel:60-3-8061 3793 Fax:60-3-8061 2493 URL:http://www.he-cable.com HE Specification For TYPE H1 : CU/XLPE/SCT/PVC/SWA(AWA)/PVC CABLE TYPE P2 : CU/XLPE/PVC/SWA(AWA)/PVC CABLE TYPE P3 : CU/XLPE/PVC/SWB(TCWB)/PVC CABLE TYPE P4A : CU/EPR/EVA/SWB(TCWB)/EVA CABLE TYPE P4B : CU/EPR/EVA/SWA(AWA)/EVA CABLE TYPE P5 : CU/MICA/EPR/EVA/SWB(TCWB)/EVA CABLE TYPE I1 : CU/PE/IOSCR/PE/SWB/LSFH INSTRUMENT CABLE TYPE I2 : CU/PE/OSCR/PE/SWB/LSFH INSTRUMENT CABLE TYPE I3 : CU/PE/IOSCR/PE/SWB/LSFH INSTRUMENT CABLE TYPE I4 : CU/PE/OSCR/PE/SWB/LSFH INSTRUMENT CABLE TYPE F1 : CU/MICA/EPR/IOSCR/EVA/SWB/EVA INSTRUMENT CABLE TYPE F2 : CU/MICA/EPR/OSCR/EVA/SWB/EVA INSTRUMENT CABLE TYPE F3 : CU/MICA/EPR/IOSCR/EVA/SWB/EVA INSTRUMENT CABLE TYPE F4 : CU/MICA/EPR/OSCR/EVA/SWB/EVA INSTRUMENT CABLE TYPE TEL1 : CU/MICA/SiR/OSCR/LSFH/SWB/LSFH INSTRUMENT CABLE

Upload: ncean

Post on 18-Jan-2016

518 views

Category:

Documents


58 download

DESCRIPTION

Cable selection guide

TRANSCRIPT

Page 1: Hi Essence Cable Spec

Doc: HEDoc: HEDoc: HEDoc: HE----SPECSPECSPECSPEC Rev: Rev: Rev: Rev: 4444 ((((02020202/201/201/201/2011111))))

1/67

HI-ESSENCE CABLE SDN. BHD. Factory address: Lot 13662, Kerteh Plastic Park, Kemaman, Terengganu.

Office address: No.2, Jalan Puteri 5/16, Bandar Puteri, 47100 Puchong, Selangor.

Tel:60-3-8061 3793 Fax:60-3-8061 2493 URL:http://www.he-cable.com

HE

Specification

For

TYPE H1 : CU/XLPE/SCT/PVC/SWA(AWA)/PVC CABLE

TYPE P2 : CU/XLPE/PVC/SWA(AWA)/PVC CABLE

TYPE P3 : CU/XLPE/PVC/SWB(TCWB)/PVC CABLE

TYPE P4A : CU/EPR/EVA/SWB(TCWB)/EVA CABLE

TYPE P4B : CU/EPR/EVA/SWA(AWA)/EVA CABLE

TYPE P5 : CU/MICA/EPR/EVA/SWB(TCWB)/EVA CABLE

TYPE I1 : CU/PE/IOSCR/PE/SWB/LSFH INSTRUMENT CABLE

TYPE I2 : CU/PE/OSCR/PE/SWB/LSFH INSTRUMENT CABLE

TYPE I3 : CU/PE/IOSCR/PE/SWB/LSFH INSTRUMENT CABLE

TYPE I4 : CU/PE/OSCR/PE/SWB/LSFH INSTRUMENT CABLE

TYPE F1 : CU/MICA/EPR/IOSCR/EVA/SWB/EVA INSTRUMENT CABLE

TYPE F2 : CU/MICA/EPR/OSCR/EVA/SWB/EVA INSTRUMENT CABLE

TYPE F3 : CU/MICA/EPR/IOSCR/EVA/SWB/EVA INSTRUMENT CABLE

TYPE F4 : CU/MICA/EPR/OSCR/EVA/SWB/EVA INSTRUMENT CABLE

TYPE TEL1 : CU/MICA/SiR/OSCR/LSFH/SWB/LSFH INSTRUMENT CABLE

Page 2: Hi Essence Cable Spec

Doc: HEDoc: HEDoc: HEDoc: HE----SPECSPECSPECSPEC Rev: Rev: Rev: Rev: 4444 ((((02020202/201/201/201/2011111))))

2/67

HI-ESSENCE CABLE SDN. BHD. Factory address: Lot 13662, Kerteh Plastic Park, Kemaman, Terengganu.

Office address: No.2, Jalan Puteri 5/16, Bandar Puteri, 47100 Puchong, Selangor.

Tel:60-3-8061 3793 Fax:60-3-8061 2493 URL:http://www.he-cable.com

HE

CROSS-LINKED POLYETHYLENE INSULATED ARMOURED PVC SHEATHED

FLAME RETARDANT CABLE

TYPE H1 : CU/XLPE/SCT/PVC/SWA/PVC CABLE

TYPE H1 : CU/XLPE/SCT/PVC/AWA/PVC CABLE DESCRIPTION

Single core and three-core cables with copper conductor, XLPE insulated, copper tape screened, flame

retardant PVC bedding, galvanized steel wire armoured and flame retardant PVC outer sheath.

Cables are rated at 6/10 (12) kV

CONSTRUCTION

1 Conductor

Plain annealed circular compacted stranded copper conductor, conform to IEC 60228 class 2.

2 Conductor screen

Extruded layer of semi-conductive compound.

3 Insulation

XLPE (cross-linked polyethylene)

4 Insulation screen

4a. Non-metallic part

Extruded layer of semi-conductive compound.

4b. Metallic part

Copper tape screen (SCT).

5 Colour for core identification

Single core - Natural

Three cores - Red, yellow and blue tapes shall be applied between non-metallic and metallic part of

insulation screen.

6 Cabling

Three insulated screened cores are laid up together and filled with non-hygroscopic material compatible with

the insulation.

7 Bedding

Flame retardant PVC compound, colour black.

8 Armour

Single core -- Aluminium wires shall be applied over the PVC bedding.

Multi-core -- Galvanized steel wires shall be applied over the PVC bedding.

9 Outer sheath

Flame retardant PVC compound, colour red. CABLE MARKING

manufacturer’s name, rated voltage, cable type, conductor size, manufacture year.

SPECIFICATIONS

IEC 60502-2

IEC 60332-3 Cat A

IEC 60754 (HCL emission 17% maximum by weight)

ASTM D 2863(Oxygen index greater than 30%)

Page 3: Hi Essence Cable Spec

Doc: HEDoc: HEDoc: HEDoc: HE----SPECSPECSPECSPEC Rev: Rev: Rev: Rev: 4444 ((((02020202/201/201/201/2011111))))

3/67

HI-ESSENCE CABLE SDN. BHD. Factory address: Lot 13662, Kerteh Plastic Park, Kemaman, Terengganu.

Office address: No.2, Jalan Puteri 5/16, Bandar Puteri, 47100 Puchong, Selangor.

Tel:60-3-8061 3793 Fax:60-3-8061 2493 URL:http://www.he-cable.com

HE

TYPE H1::::CU/XLPE/SCT/PVC/AWA/PVC CABLE – SINGLE CORE

6/10 (12) kV

Conductor Nominal

thickness

of

insulation

Metallic

screening

Nominal

thickness

of

bedding

Nominal

diameter

of

aluminium

wire

Nominal

thickness

of

outer

sheath

Approx.

overall

diameter

Maximum

Conductor

Resistance

(at 20℃℃℃℃)

Current rating

Nominal

Cross-

sectional

area

No./dia.

of

wire

Approx.

outer

diameter

Approx.

thickness

of

copper tape

In air

at 40℃℃℃℃

In ground

at 25℃℃℃℃

mm2 No./mm mm mm mm mm mm mm mm ΩΩΩΩ/km A A

50 c.c. 8.2 3.4 0.1 1.2 1.6 1.9 28.4 0.387 215 205

70 c.c. 10.0 3.4 0.1 1.2 1.6 1.9 30.2 0.268 270 255

95 c.c. 11.6 3.4 0.1 1.2 1.6 2.0 32.0 0.193 325 305

120 c.c. 13.1 3.4 0.1 1.2 2.0 2.0 34.3 0.153 375 345

150 c.c. 14.5 3.4 0.1 1.2 2.0 2.1 35.9 0.124 430 390

185 c.c. 16.3 3.4 0.1 1.2 2.0 2.2 37.9 0.0991 495 435

240 c.c. 18.6 3.4 0.1 1.2 2.0 2.2 40.2 0.0754 585 505

300 c.c. 21.0 3.4 0.1 1.2 2.0 2.3 42.8 0.0601 665 570

400 c.c. 23.2 3.4 0.1 1.3 2.5 2.4 48.5 0.0470 770 645

500 c.c. 26.0 3.4 0.1 1.3 2.5 2.5 51.5 0.0366 890 725

630 c.c. 30.0 3.4 0.1 1.4 2.5 2.7 56.6 0.0283 1030 815

Note:c.c. -- compacted circular stranded conductor

Conductor

Size

Maximum

Conductor

Resistance

50Hz at 90℃℃℃℃

Reactance

(50Hz)

mm2 ΩΩΩΩ/km ΩΩΩΩ/km

50 0.494 0.132

70 0.342 0.125

95 0.247 0.118

120 0.196 0.113

150 0.159 0.111

185 0.127 0.107

240 0.0976 0.102

300 0.0785 0.0991

400 0.0624 0.0957

500 0.0499 0.0942

630 0.0402 0.0921

Page 4: Hi Essence Cable Spec

Doc: HEDoc: HEDoc: HEDoc: HE----SPECSPECSPECSPEC Rev: Rev: Rev: Rev: 4444 ((((02020202/201/201/201/2011111))))

4/67

HI-ESSENCE CABLE SDN. BHD. Factory address: Lot 13662, Kerteh Plastic Park, Kemaman, Terengganu.

Office address: No.2, Jalan Puteri 5/16, Bandar Puteri, 47100 Puchong, Selangor.

Tel:60-3-8061 3793 Fax:60-3-8061 2493 URL:http://www.he-cable.com

HE

TYPE H1::::CU/XLPE/SCT/PVC/SWA/PVC CABLE – THREE CORES

6/10 (12) kV

Conductor Nominal

thickness

of

insulation

Metallic

screening

Nominal

thickness

of

bedding

Nominal

diameter

of

steel

wire

Nominal

thickness

of

outer

sheath

Approx.

overall

diameter

Maximum

Conductor

Resistance

(at 20℃℃℃℃)

Current rating

Nominal

Cross-

sectional

area

No./dia.

of

wire

Approx.

outer

diameter

Approx.

thickness

of

copper tape

In air

at 40℃℃℃℃

In ground

at 25℃℃℃℃

mm2 No./mm mm mm mm mm mm mm mm ΩΩΩΩ/km A A

50 c.c. 8.2 3.4 0.1 1.4 2.5 2.7 53.1 0.387 200 200

70 c.c. 10.0 3.4 0.1 1.5 2.5 2.8 57.4 0.268 250 245

95 c.c. 11.6 3.4 0.1 1.5 2.5 2.9 61.1 0.193 300 290

120 c.c. 13.1 3.4 0.1 1.6 2.5 3.0 64.7 0.153 345 330

150 c.c. 14.5 3.4 0.1 1.7 2.5 3.2 68.4 0.124 390 365

185 c.c. 16.3 3.4 0.1 1.7 3.15 3.3 73.8 0.0991 445 410

240 c.c. 18.6 3.4 0.1 1.8 3.15 3.5 79.4 0.0754 520 475

300 c.c. 21.0 3.4 0.1 1.9 3.15 3.7 85.1 0.0601 585 525

400 c.c. 23.2 3.4 0.1 2.1 3.15 3.9 94.1 0.0470 665 590

Note:c.c. -- compacted circular stranded conductor.

Conductor

Size

Maximum

Conductor

Resistance

50Hz at 90℃℃℃℃

Reactance

(50Hz)

mm2 ΩΩΩΩ/km ΩΩΩΩ/km

50 0.494 0.108

70 0.342 0.102

95 0.247 0.0976

120 0.196 0.0944

150 0.160 0.0915

185 0.128 0.0888

240 0.0986 0.0856

300 0.0798 0.0833

400 0.0641 0.0809

Page 5: Hi Essence Cable Spec

Doc: HEDoc: HEDoc: HEDoc: HE----SPECSPECSPECSPEC Rev: Rev: Rev: Rev: 4444 ((((02020202/201/201/201/2011111))))

5/67

HI-ESSENCE CABLE SDN. BHD. Factory address: Lot 13662, Kerteh Plastic Park, Kemaman, Terengganu.

Office address: No.2, Jalan Puteri 5/16, Bandar Puteri, 47100 Puchong, Selangor.

Tel:60-3-8061 3793 Fax:60-3-8061 2493 URL:http://www.he-cable.com

HE

CROSS-LINKED POLYETHYLENE INSULATED ARMOURED PVC SHEATHED

FLAME RETARDANT CABLE

TYPE P2::::CU/XLPE/PVC/SWA/PVC CABLE

TYPE P2::::CU/XLPE/PVC/AWA/PVC CABLE DESCRIPTION

Single core and multi-core cables with copper conductor, XLPE insulated, flame retardant PVC inner covering,

galvanized steel wire armoured and flame retardant PVC outer sheath.

Cables are rated at 0.6/1 (1.2) kV

CONSTRUCTION

1 Conductor

Plain annealed circular or compacted stranded copper conductor, conform to IEC 60228 class 2.

2 Insulation

XLPE (cross-linked polyethylene)

3 Colour for core identification

Single core - Natural

Two core - Red, black

Three core - Red, yellow and blue

Four core - Red, yellow, blue and black

Five core & above White(natural) core with black numbering

4 Cabling

Two, three, four, five or more insulated cores are laid up together, if necessary filled with non-hygroscopic

material compatible with the insulation.

5 Inner covering

Flame retardant PVC compound, colour black.

6 Armour

Single core -- Aluminium wires shall be applied over the PVC inner covering.

Multi-core -- Galvanized steel wires shall be applied over the PVC inner covering.

7 Outer sheath

Flame retardant PVC compound, colour black. CABLE MARKING

manufacturer’s name, rated voltage, cable type, conductor size, manufacture year. SPECIFICATIONS

IEC 60502-1

IEC 60332-3 Cat A

IEC 60754 (HCL emission 17﹪maximum by weight)

ASTM D 2863(Oxygen index greater than 30﹪)

Page 6: Hi Essence Cable Spec

Doc: HEDoc: HEDoc: HEDoc: HE----SPECSPECSPECSPEC Rev: Rev: Rev: Rev: 4444 ((((02020202/201/201/201/2011111))))

6/67

HI-ESSENCE CABLE SDN. BHD. Factory address: Lot 13662, Kerteh Plastic Park, Kemaman, Terengganu.

Office address: No.2, Jalan Puteri 5/16, Bandar Puteri, 47100 Puchong, Selangor.

Tel:60-3-8061 3793 Fax:60-3-8061 2493 URL:http://www.he-cable.com

HE

TYPE P2::::CU/XLPE/PVC/AWA/PVC CABLE – SINGLE CORE

0.6/1 (1.2) kV

Conductor Nominal

thickness

of

insulation

Approx.

thickness

of

inner

covering

Nominal

diameter

of

aluminium

wire

Nominal

thickness

of

outer

sheath

Approx.

overall

diameter

Approx.

cable

weight

Maximum

Conductor

Resistance

(at 20℃℃℃℃)

Current rating

Nominal

cross-

sectional

area

No./dia.

of

wire

Approx.

outer

diameter

In air

at 40℃℃℃℃

In ground

at 25℃℃℃℃

mm2 No./mm mm mm mm mm mm mm kg/km ΩΩΩΩ/km A A

16 7/-- 5.0 0.7 1.0 0.8 1.8 14.4 345 1.15 100 115

25 7/-- 6.1 0.9 1.0 0.8 1.8 15.9 460 0.727 135 150

35 7/-- 7.1 0.9 1.0 0.8 1.8 16.9 565 0.524 165 170

50 19/-- 8.2 1.0 1.0 1.25 1.8 19.1 750 0.387 200 205

70 19/-- 10.0 1.1 1.0 1.25 1.8 21.1 980 0.268 255 250

95 19/-- 11.6 1.1 1.0 1.25 1.8 22.7 1245 0.193 310 300

120 37/-- 13.1 1.2 1.0 1.6 1.8 25.2 1560 0.153 365 340

150 37/-- 14.5 1.4 1.0 1.6 1.8 27.0 1865 0.124 415 385

185 37/-- 16.3 1.6 1.0 1.6 1.8 29.2 2250 0.0991 480 435

240 61/-- 18.6 1.7 1.0 1.6 1.9 31.9 2835 0.0754 570 500

300 61/-- 21.0 1.8 1.0 1.6 1.9 34.6 3455 0.0601 650 565

400 61/-- 23.2 2.0 1.2 2.0 2.1 38.8 4440 0.0470 760 635

500 61/-- 26.0 2.2 1.2 2.0 2.2 42.2 5535 0.0366 870 715

630 61/-- 30.0 2.4 1.2 2.0 2.3 46.9 6995 0.0283 995 800

Conductor

Size

Maximum

Conductor

Resistance

50Hz at 90℃℃℃℃

Reactance

(50Hz)

mm2 ΩΩΩΩ/km ΩΩΩΩ/km

16 1.47 0.126

25 0.927 0.119

35 0.668 0.114

50 0.494 0.112

70 0.342 0.106

95 0.247 0.101

120 0.196 0.1

150 0.159 0.098

185 0.128 0.096

240 0.0982 0.093

300 0.0793 0.091

400 0.0632 0.092

500 0.0509 0.09

630 0.0415 0.087

Page 7: Hi Essence Cable Spec

Doc: HEDoc: HEDoc: HEDoc: HE----SPECSPECSPECSPEC Rev: Rev: Rev: Rev: 4444 ((((02020202/201/201/201/2011111))))

7/67

HI-ESSENCE CABLE SDN. BHD. Factory address: Lot 13662, Kerteh Plastic Park, Kemaman, Terengganu.

Office address: No.2, Jalan Puteri 5/16, Bandar Puteri, 47100 Puchong, Selangor.

Tel:60-3-8061 3793 Fax:60-3-8061 2493 URL:http://www.he-cable.com

HE

TYPE P2::::CU/XLPE/PVC/SWA/PVC CABLE – TWO CORES

0.6/1 (1.2) kV

Conductor Nominal

thickness

of

insulation

Approx.

thickness

of

inner

covering

Nominal

diameter

of

steel

wire

Nominal

thickness

of

outer

sheath

Approx.

overall

diameter

Approx.

cable

weight

Maximum

Conductor

Resistance

(at 20℃℃℃℃)

Current rating

Nominal

cross-

sectional

area

No./dia.

of

wire

Approx.

outer

diameter

In air

at 40℃℃℃℃

In ground

at 25℃℃℃℃

mm2 No./mm mm mm mm mm mm mm kg/km ΩΩΩΩ/km A A

1.5 7/0.53 1.59 0.7 1.0 0.8 1.8 14.1 325 12.1 29 33

2.5 7/0.67 2.01 0.7 1.0 0.8 1.8 14.9 375 7.41 38 45

4 7/0.85 2.55 0.7 1.0 0.8 1.8 16.1 445 4.61 45 59

6 7/1.04 3.12 0.7 1.0 0.8 1.8 17.1 540 3.08 58 75

10 7/-- 3.8 0.7 1.0 1.25 1.8 19.9 795 1.83 79 98

16 7/-- 5.0 0.7 1.0 1.25 1.8 22.3 985 1.15 105 125

25 7/-- 6.1 0.9 1.0 1.6 1.8 26.0 1445 0.727 140 160

35 7/-- 7.1 0.9 1.0 1.6 1.8 28.0 1730 0.524 170 195

50 19/-- 8.2 1.0 1.0 1.6 1.8 30.6 2080 0.387 210 230

70 19/-- 10.0 1.1 1.0 1.6 2.0 35.0 2720 0.268 260 280

95 19/-- 11.6 1.1 1.2 2.0 2.1 39.6 3705 0.193 320 335

120 37/-- 13.1 1.2 1.2 2.0 2.2 43.4 4410 0.153 370 380

150 37/-- 14.5 1.4 1.2 2.0 2.3 47.2 5215 0.124 425 425

185 37/-- 16.3 1.6 1.4 2.5 2.5 54.0 6790 0.0991 485 480

240 61/-- 18.6 1.7 1.4 2.5 2.7 59.4 8320 0.0754 575 555

300 61/-- 21.0 1.8 1.6 2.5 2.8 65.4 10025 0.0601 650 620

400 61/-- 23.2 2.0 1.6 2.5 3.1 71.3 12155 0.0470 745 695

Note:--: compacted circular stranded conductor.

Conductor

Size

Maximum

Conductor

Resistance

50Hz at 90℃℃℃℃

Reactance

(50Hz)

mm2 ΩΩΩΩ/km ΩΩΩΩ/km

1.5 15.43 0.101

2.5 9.45 0.094

4 5.88 0.089

6 3.93 0.084

10 2.33 0.08

16 1.47 0.076

25 0.927 0.076

35 0.669 0.074

50 0.494 0.074

70 0.342 0.072

95 0.247 0.071

120 0.196 0.071

150 0.16 0.071

185 0.128 0.071

240 0.0987 0.0704

300 0.0798 0.07

400 0.064 0.0699

Page 8: Hi Essence Cable Spec

Doc: HEDoc: HEDoc: HEDoc: HE----SPECSPECSPECSPEC Rev: Rev: Rev: Rev: 4444 ((((02020202/201/201/201/2011111))))

8/67

HI-ESSENCE CABLE SDN. BHD. Factory address: Lot 13662, Kerteh Plastic Park, Kemaman, Terengganu.

Office address: No.2, Jalan Puteri 5/16, Bandar Puteri, 47100 Puchong, Selangor.

Tel:60-3-8061 3793 Fax:60-3-8061 2493 URL:http://www.he-cable.com

HE

TYPE P2::::CU/XLPE/PVC/SWA/PVC CABLE – THREE CORES

0.6/1 (1.2) kV

Conductor Nominal

thickness

of

insulation

Approx.

thickness

of

inner

covering

Nominal

diameter

of

steel

wire

Nominal

thickness

of

outer

sheath

Approx.

overall

diameter

Approx.

cable

weight

Maximum

Conductor

Resistance

(at 20℃℃℃℃)

Current rating

Nominal

cross-

sectional

area

No./dia.

of

wire

Approx.

outer

diameter

In air

at 40℃℃℃℃

In ground

at 25℃℃℃℃

mm2 No./mm mm mm mm mm mm mm kg/km ΩΩΩΩ/km A A

1.5 7/0.53 1.59 0.7 1.0 0.8 1.8 14.7 360 12.1 21 28

2.5 7/0.67 2.01 0.7 1.0 0.8 1.8 15.5 420 7.41 27 37

4 7/0.85 2.55 0.7 1.0 0.8 1.8 16.8 500 4.61 38 48

6 7/1.04 3.12 0.7 1.0 0.8 1.8 17.9 620 3.08 49 60

10 7/-- 3.8 0.7 1.0 1.25 1.8 20.8 925 1.83 65 81

16 7/-- 5.0 0.7 1.0 1.25 1.8 23.4 1175 1.15 89 105

25 7/-- 6.1 0.9 1.0 1.6 1.8 27.3 1725 0.727 120 135

35 7/-- 7.1 0.9 1.0 1.6 1.8 29.5 2100 0.524 145 160

50 19/-- 8.2 1.0 1.0 1.6 1.9 32.5 2590 0.387 175 190

70 19/-- 10.0 1.1 1.2 2.0 2.0 38.2 3715 0.268 225 235

95 19/-- 11.6 1.1 1.2 2.0 2.2 42.1 4675 0.193 275 280

120 37/-- 13.1 1.2 1.2 2.0 2.3 46.1 5650 0.153 315 320

150 37/-- 14.5 1.4 1.4 2.5 2.5 52.3 7230 0.124 365 355

185 37/-- 16.3 1.6 1.4 2.5 2.6 57.3 8675 0.0991 420 405

240 61/-- 18.6 1.7 1.6 2.5 2.8 63.4 10815 0.0754 490 465

300 61/-- 21.0 1.8 1.6 2.5 3.0 69.8 13090 0.0601 555 515

400 61/-- 23.2 2.0 1.6 2.5 3.2 75.8 15930 0.0470 635 580

Conductor

Size

Maximum

Conductor

Resistance

50Hz at 90℃℃℃℃

Reactance

(50Hz)

mm2 ΩΩΩΩ/km ΩΩΩΩ/km

1.5 15.43 0.101

2.5 9.45 0.094

4 5.88 0.089

6 3.93 0.084

10 2.33 0.08

16 1.47 0.076

25 0.927 0.076

35 0.669 0.074

50 0.494 0.074

70 0.343 0.072

95 0.248 0.071

120 0.197 0.071

150 0.16 0.071

185 0.129 0.071

240 0.0996 0.0704

300 0.0809 0.07

400 0.0653 0.0699

Page 9: Hi Essence Cable Spec

Doc: HEDoc: HEDoc: HEDoc: HE----SPECSPECSPECSPEC Rev: Rev: Rev: Rev: 4444 ((((02020202/201/201/201/2011111))))

9/67

HI-ESSENCE CABLE SDN. BHD. Factory address: Lot 13662, Kerteh Plastic Park, Kemaman, Terengganu.

Office address: No.2, Jalan Puteri 5/16, Bandar Puteri, 47100 Puchong, Selangor.

Tel:60-3-8061 3793 Fax:60-3-8061 2493 URL:http://www.he-cable.com

HE

TYPE P2::::CU/XLPE/PVC/SWA/PVC CABLE –FOUR CORES

0.6/1 (1.2) kV

Conductor Nominal

thickness

of

insulation

Approx.

thickness

of

inner

covering

Nominal

diameter

of

steel

wire

Nominal

thickness

of

outer

sheath

Approx.

overall

diameter

Approx.

cable

weight

Maximum

Conductor

Resistance

(at 20℃℃℃℃)

Current rating

Nominal

cross-

sectional

area

No./dia.

of

wire

Approx.

outer

diameter

In air

at 40℃℃℃℃

In ground

at 25℃℃℃℃

mm2 No./mm mm mm mm mm mm mm kg/km ΩΩΩΩ/km A A

1.5 7/0.53 1.59 0.7 1.0 0.8 1.8 15.5 405 12.1 21 28

2.5 7/0.67 2.01 0.7 1.0 0.8 1.8 16.4 475 7.41 27 37

4 7/0.85 2.55 0.7 1.0 0.8 1.8 17.9 580 4.61 38 48

6 7/1.04 3.12 0.7 1.0 1.25 1.8 20.0 835 3.08 49 60

10 7/-- 3.8 0.7 1.0 1.25 1.8 22.2 1080 1.83 65 81

16 7/-- 5.0 0.7 1.0 1.6 1.8 25.8 1530 1.15 89 105

25 7/-- 6.1 0.9 1.0 1.6 1.8 29.4 2065 0.727 120 135

35 7/-- 7.1 0.9 1.0 1.6 1.9 32.0 2545 0.524 145 160

50 19/-- 8.2 1.0 1.0 1.6 2.0 35.4 3180 0.387 175 190

70 19/-- 10.0 1.1 1.2 2.0 2.2 41.8 4580 0.268 225 235

95 19/-- 11.6 1.1 1.2 2.0 2.3 45.9 5820 0.193 275 280

120 37/-- 13.1 1.2 1.4 2.5 2.5 52.5 7540 0.153 315 320

150 37/-- 14.5 1.4 1.4 2.5 2.6 57.0 8975 0.124 365 355

185 37/-- 16.3 1.6 1.4 2.5 2.8 62.8 10815 0.0991 420 405

240 61/-- 18.6 1.7 1.6 2.5 3.0 69.7 13590 0.0754 490 465

300 61/-- 21.0 1.8 1.6 2.5 3.2 76.6 16440 0.0601 555 515

400 61/-- 23.2 2.0 1.8 3.15 3.5 85.2 21265 0.0470 635 580

Note:--: compacted circular stranded conductor

Conductor

Size

Maximum

Conductor

Resistance

50Hz at 90℃℃℃℃

Reactance

(50Hz)

mm2 ΩΩΩΩ/km ΩΩΩΩ/km

1.5 15.43 0.101

2.5 9.45 0.094

4 5.88 0.089

6 3.93 0.084

10 2.33 0.08

16 1.47 0.076

25 0.927 0.076

35 0.669 0.074

50 0.494 0.074

70 0.343 0.072

95 0.248 0.071

120 0.197 0.071

150 0.16 0.071

185 0.129 0.071

240 0.0996 0.0704

300 0.0809 0.07

400 0.0653 0.0699

Page 10: Hi Essence Cable Spec

Doc: HEDoc: HEDoc: HEDoc: HE----SPECSPECSPECSPEC Rev: Rev: Rev: Rev: 4444 ((((02020202/201/201/201/2011111))))

10/67

HI-ESSENCE CABLE SDN. BHD. Factory address: Lot 13662, Kerteh Plastic Park, Kemaman, Terengganu.

Office address: No.2, Jalan Puteri 5/16, Bandar Puteri, 47100 Puchong, Selangor.

Tel:60-3-8061 3793 Fax:60-3-8061 2493 URL:http://www.he-cable.com

HE

TYPE P2::::CU/XLPE/PVC/SWA/PVC CABLE –FIVE CORES

0.6/1 (1.2) kV

Conductor Nominal

thickness

of

insulation

Approx.

thickness

of

inner

covering

Nominal

diameter

of

steel

wire

Nominal

thickness

of

outer

sheath

Approx.

overall

diameter

Approx.

cable

weight

Maximum

Conductor

Resistance

(at 20℃℃℃℃)

Current rating

Nominal

cross-

sectional

area

No./dia.

of

wire

Approx.

outer

diameter

In air

at 40℃℃℃℃

In ground

at 25℃℃℃℃

mm2 No./mm mm mm mm mm mm mm kg/km ΩΩΩΩ/km A A

1.5 7/0.53 1.59 0.7 1.0 0.8 1.8 16.4 445 12.1 19 23

2.5 7/0.67 2.01 0.7 1.0 0.8 1.8 17.5 530 7.41 22 30

4 7/0.85 2.55 0.7 1.0 1.25 1.8 20.0 790 4.61 31 40

6 7/1.04 3.12 0.7 1.0 1.25 1.8 21.3 940 3.08 40 49

10 7/-- 3.8 0.7 1.0 1.25 1.8 23.7 1230 1.83 53 67

16 7/-- 5.0 0.7 1.0 1.6 1.8 27.7 1755 1.15 73 86

25 7/-- 6.1 0.9 1.0 1.6 1.8 31.7 2375 0.727 99 111

35 7/-- 7.1 0.9 1.0 1.6 1.9 34.6 2955 0.524 119 132

50 19/-- 8.2 1.0 1.2 2.0 2.1 39.7 4040 0.387 144 156

70 19/-- 10.0 1.1 1.2 2.0 2.3 45.5 5365 0.268 185 195

95 19/-- 11.6 1.1 1.4 2.5 2.4 51.9 7335 0.193 227 231

Conductor

Size

Maximum

Conductor

Resistance

50Hz at 90℃℃℃℃

Reactance

(50Hz)

mm2 ΩΩΩΩ/km ΩΩΩΩ/km

1.5 15.43 0.101

2.5 9.45 0.094

4 5.88 0.089

6 3.93 0.084

10 2.33 0.08

16 1.47 0.076

25 0.927 0.076

35 0.669 0.074

50 0.494 0.074

70 0.343 0.072

95 0.248 0.071

Page 11: Hi Essence Cable Spec

Doc: HEDoc: HEDoc: HEDoc: HE----SPECSPECSPECSPEC Rev: Rev: Rev: Rev: 4444 ((((02020202/201/201/201/2011111))))

11/67

HI-ESSENCE CABLE SDN. BHD. Factory address: Lot 13662, Kerteh Plastic Park, Kemaman, Terengganu.

Office address: No.2, Jalan Puteri 5/16, Bandar Puteri, 47100 Puchong, Selangor.

Tel:60-3-8061 3793 Fax:60-3-8061 2493 URL:http://www.he-cable.com

HE

TYPE P2::::CU/XLPE/PVC/SWA/PVC CABLE –MULTI-CORES(1.5 mm2)

0.6/1 (1.2) kV

No.

of core

Conductor Nominal

thickness

of

insulation

Approx.

thickness

of

inner

covering

Nominal

diameter

of

steel

wire

Nominal

thickness

of

outer

sheath

Approx.

overall

diameter

Approx.

cable

weight

Maximum

Conductor

Resistance

ΩΩΩΩ/km

Current rating

Nominal

cross-

sectional

area

No./dia.

of

wire

Approx.

outer

diameter

In air

at 40℃℃℃℃

In

ground

at 25℃℃℃℃

C mm2 No./mm mm mm mm mm mm mm kg/km 20℃℃℃℃ 90℃℃℃℃ A A

6 1.5 7/0.53 1.59 0.7 1.0 0.8 1.8 17.3 495

12.1 15.43

17 21

7 1.5 7/0.53 1.59 0.7 1.0 0.8 1.8 17.3 510 16 19

8 1.5 7/0.53 1.59 0.7 1.0 1.25 1.8 19.1 690 15 18

9 1.5 7/0.53 1.59 0.7 1.0 1.25 1.8 20.1 750 15 17

10 1.5 7/0.53 1.59 0.7 1.0 1.25 1.8 21.3 815 14 16

11 1.5 7/0.53 1.59 0.7 1.0 1.25 1.8 21.3 835 14 16

12 1.5 7/0.53 1.59 0.7 1.0 1.25 1.8 21.8 865 13 16

13 1.5 7/0.53 1.59 0.7 1.0 1.25 1.8 22.6 920 13 15

14 1.5 7/0.53 1.59 0.7 1.0 1.25 1.8 22.6 935 13 15

15 1.5 7/0.53 1.59 0.7 1.0 1.25 1.8 23.5 995 12 14

16 1.5 7/0.53 1.59 0.7 1.0 1.25 1.8 23.5 1010 12 14

17 1.5 7/0.53 1.59 0.7 1.0 1.25 1.8 24.4 1065 12 14

18 1.5 7/0.53 1.59 0.7 1.0 1.25 1.8 24.4 1085 12 14

19 1.5 7/0.53 1.59 0.7 1.0 1.25 1.8 24.4 1100 12 13

20 1.5 7/0.53 1.59 0.7 1.0 1.6 1.8 26.0 1315 11 13

21 1.5 7/0.53 1.59 0.7 1.0 1.6 1.8 26.0 1330 11 13

24 1.5 7/0.53 1.59 0.7 1.0 1.6 1.8 28.2 1490 10 11

27 1.5 7/0.53 1.59 0.7 1.0 1.6 1.8 28.7 1565 9 10

30 1.5 7/0.53 1.59 0.7 1.0 1.6 1.8 29.5 1655 8 9

37 1.5 7/0.53 1.59 0.7 1.0 1.6 1.8 31.3 1880 7 8

TYPE P2::::CU/XLPE/PVC/SWA/PVC CABLE –MULTI-CORES(2.5 mm2)

0.6/1 (1.2) kV

No.

of core

Conductor Nominal

thickness

of

insulation

Approx

thickness

of

inner

covering

Nominal

diameter

of

steel

wire

Nominal

thickness

of

outer

sheath

Approx.

overall

diameter

Approx.

cable

weight

Maximum

Conductor

Resistance

ΩΩΩΩ/km

Current rating

Nominal

cross-

sectional

area

No./dia.

of

wire

Approx.

outer

diameter

In air

at 40℃℃℃℃

In

ground

at 25℃℃℃℃

C mm2 No./mm mm mm mm mm mm mm kg/km 20℃℃℃℃ 90℃℃℃℃ A A

6 2.5 7/0.67 2.01 0.7 1.0 1.25 1.8 19.4 725

7.41 9.45

20 27

7 2.5 7/0.67 2.01 0.7 1.0 1.25 1.8 19.4 745 19 25

8 2.5 7/0.67 2.01 0.7 1.0 1.25 1.8 20.4 825 18 24

9 2.5 7/0.67 2.01 0.7 1.0 1.25 1.8 21.4 895 17 23

10 2.5 7/0.67 2.01 0.7 1.0 1.25 1.8 22.9 985 16 22

11 2.5 7/0.67 2.01 0.7 1.0 1.25 1.8 22.9 1015 15 21

12 2.5 7/0.67 2.01 0.7 1.0 1.25 1.8 23.4 1050 15 21

13 2.5 7/0.67 2.01 0.7 1.0 1.25 1.8 24.3 1120 15 20

14 2.5 7/0.67 2.01 0.7 1.0 1.25 1.8 24.3 1145 14 20

15 2.5 7/0.67 2.01 0.7 1.0 1.6 1.8 26.1 1365 14 19

16 2.5 7/0.67 2.01 0.7 1.0 1.6 1.8 26.1 1395 14 19

17 2.5 7/0.67 2.01 0.7 1.0 1.6 1.8 27.1 1480 13 18

18 2.5 7/0.67 2.01 0.7 1.0 1.6 1.8 27.1 1505 13 18

19 2.5 7/0.67 2.01 0.7 1.0 1.6 1.8 27.1 1530 13 18

20 2.5 7/0.67 2.01 0.7 1.0 1.6 1.8 28.2 1620 13 17

21 2.5 7/0.67 2.01 0.7 1.0 1.6 1.8 28.2 1645 12 17

24 2.5 7/0.67 2.01 0.7 1.0 1.6 1.8 30.6 1835 11 15

27 2.5 7/0.67 2.01 0.7 1.0 1.6 1.8 31.1 1940 10 14

Page 12: Hi Essence Cable Spec

Doc: HEDoc: HEDoc: HEDoc: HE----SPECSPECSPECSPEC Rev: Rev: Rev: Rev: 4444 ((((02020202/201/201/201/2011111))))

12/67

HI-ESSENCE CABLE SDN. BHD. Factory address: Lot 13662, Kerteh Plastic Park, Kemaman, Terengganu.

Office address: No.2, Jalan Puteri 5/16, Bandar Puteri, 47100 Puchong, Selangor.

Tel:60-3-8061 3793 Fax:60-3-8061 2493 URL:http://www.he-cable.com

HE

TYPE P2::::CU/XLPE/PVC/SWA/PVC CABLE –MULTI-CORES(4 mm2)

0.6/1 (1.2) kV

No.

of core

Conductor Nominal

thickness

of

insulation

Approx.

thickness

of

inner

covering

Nominal

diameter

of

steel

wire

Nominal

thickness

of

outer

sheath

Approx.

overall

diameter

Approx.

cable

weight

Maximum

Conductor

Resistance

ΩΩΩΩ/km

Current rating

Nominal

cross-

sectional

area

No./dia.

of

wire

Approx.

outer

diameter

In air

at 40℃℃℃℃

In

ground

at 25℃℃℃℃

C mm2 No./mm mm mm mm mm mm mm kg/km 20℃℃℃℃ 90℃℃℃℃ A A

6 4 7/0.85 2.55 0.7 1.0 1.25 1.8 21.2 885

4.61 5.88

28 36

7 4 7/0.85 2.55 0.7 1.0 1.25 1.8 21.2 925 26 33

8 4 7/0.85 2.55 0.7 1.0 1.25 1.8 22.5 1020 25 31

9 4 7/0.85 2.55 0.7 1.0 1.25 1.8 23.7 1120 23 29

10 4 7/0.85 2.55 0.7 1.0 1.6 1.8 26.0 1375 22 28

11 4 7/0.85 2.55 0.7 1.0 1.6 1.8 26.0 1420 22 28

12 4 7/0.85 2.55 0.7 1.0 1.6 1.8 26.6 1475 21 27

13 4 7/0.85 2.55 0.7 1.0 1.6 1.8 27.7 1575 21 26

14 4 7/0.85 2.55 0.7 1.0 1.6 1.8 27.7 1615 20 26

15 4 7/0.85 2.55 0.7 1.0 1.6 1.8 28.9 1720 20 25

16 4 7/0.85 2.55 0.7 1.0 1.6 1.8 28.9 1755 19 24

17 4 7/0.85 2.55 0.7 1.0 1.6 1.8 30.1 1860 19 24

18 4 7/0.85 2.55 0.7 1.0 1.6 1.8 30.1 1900 19 24

19 4 7/0.85 2.55 0.7 1.0 1.6 1.8 30.1 1935 18 23

20 4 7/0.85 2.55 0.7 1.0 1.6 1.8 31.4 2060 18 22

21 4 7/0.85 2.55 0.7 1.0 1.6 1.8 31.4 2100 17 22

24 4 7/0.85 2.55 0.7 1.0 1.6 1.9 34.4 2380 16 20

27 4 7/0.85 2.55 0.7 1.0 1.6 1.9 35.0 2525 14 18

Note:--: compacted circular stranded conductor

Page 13: Hi Essence Cable Spec

Doc: HEDoc: HEDoc: HEDoc: HE----SPECSPECSPECSPEC Rev: Rev: Rev: Rev: 4444 ((((02020202/201/201/201/2011111))))

13/67

HI-ESSENCE CABLE SDN. BHD. Factory address: Lot 13662, Kerteh Plastic Park, Kemaman, Terengganu.

Office address: No.2, Jalan Puteri 5/16, Bandar Puteri, 47100 Puchong, Selangor.

Tel:60-3-8061 3793 Fax:60-3-8061 2493 URL:http://www.he-cable.com

HE

CROSS-LINKED POLYETHYLENE INSULATED BRAIDED PVC SHEATHED FLAME

RETARDANT CABLE

TYPE P3 : CU/XLPE/PVC/SWB/PVC CABLE

TYPE P3 : CU/XLPE/PVC/TCWB/PVC CABLE DESCRIPTION

Single core and multi-core cables with copper conductor, XLPE insulated, flame retardant PVC inner covering,

galvanized steel wire braided and flame retardant PVC outer sheath.

Cables are rated at 0.6/1 (1.2) kV

CONSTRUCTION

1 Conductor

Plain annealed circular compacted stranded copper conductor, conform to IEC 60228 class 2.

2 Insulation

XLPE (cross-linked polyethylene)

3 Colour for core identification

Single core - Natural

Two core - Red, black

Three core - Red, yellow and blue

Four core - Red, yellow, blue and black

Five core & above - White(natural) core with black numbering

4 Cabling

Two, three, four, five or more insulated cores are laid up together, if necessary filled with non-hygroscopic

material compatible with the insulation.

5 Inner covering

Flame retardant PVC compound, colour black.

6 Armour

Single core – Tinned copper wires shall be braided over the PVC inner covering.

Multi-core -- Galvanized steel wires shall be braided over the PVC inner covering.

7 Outer sheath

Flame retardant PVC compound, colour black. CABLE MARKING

Manufacturer’s name, rated voltage, cable type, conductor size, manufacture year.

SPECIFICATIONS

IEC 60092, IEC 60092-353

IEC 60332-3 Cat A

IEC 60754 (HCL emission 17% maximum by weight)

ASTM D 2863(Oxygen index greater than 30%)

Page 14: Hi Essence Cable Spec

Doc: HEDoc: HEDoc: HEDoc: HE----SPECSPECSPECSPEC Rev: Rev: Rev: Rev: 4444 ((((02020202/201/201/201/2011111))))

14/67

HI-ESSENCE CABLE SDN. BHD. Factory address: Lot 13662, Kerteh Plastic Park, Kemaman, Terengganu.

Office address: No.2, Jalan Puteri 5/16, Bandar Puteri, 47100 Puchong, Selangor.

Tel:60-3-8061 3793 Fax:60-3-8061 2493 URL:http://www.he-cable.com

HE

TYPE P3::::CU/XLPE/PVC/TCWB/PVC CABLE – SINGLE CORE

0.6/1 (1.2) kV

Conductor Nominal

thickness

of

insulation

Approx.

thickness

of

inner

covering

Nominal

diameter

of

tinned

copper

wire

Nominal

thickness

of

outer

sheath

Approx.

overall

diameter

Approx.

cable

weight

Maximum

Conductor

Resistance

(at 20℃℃℃℃)

Current

rating

(In air

at 40℃℃℃℃)

Nominal

cross-

sectional

area

No./dia.

of

wire

Approx.

outer

diameter

mm2 No./mm mm mm mm mm mm mm kg/km ΩΩΩΩ/km A

16 c.c 5.0 0.7 1.0 0.3 1.2 12.6 330 1.15 100

25 c.c 6.1 0.9 1.0 0.3 1.2 14.1 445 0.727 135

35 c.c 7.1 0.9 1.0 0.3 1.3 15.3 555 0.524 165

50 c.c 8.2 1.0 1.0 0.3 1.3 16.6 695 0.387 200

70 c.c 10.0 1.1 1.0 0.3 1.4 18.8 930 0.268 255

95 c.c 11.6 1.1 1.0 0.3 1.5 20.8 1215 0.193 310

120 c.c 13.1 1.2 1.0 0.3 1.5 22.6 1475 0.153 365

150 c.c 14.5 1.4 1.0 0.3 1.6 24.6 1775 0.124 415

185 c.c 16.3 1.6 1.0 0.3 1.7 27.0 2175 0.0991 480

240 c.c 18.6 1.7 1.0 0.3 1.8 29.7 2755 0.0754 570

300 c.c 21.0 1.8 1.0 0.3 1.9 32.6 3380 0.0601 650

400 c.c 23.2 2.0 1.2 0.3 2.0 35.8 4245 0.0470 760

500 c.c 26.0 2.2 1.2 0.3 2.1 39.2 5320 0.0366 870

630 c.c 30.0 2.4 1.2 0.3 2.3 44.1 6780 0.0283 995

Conductor

Size

Maximum

Conductor

Resistance

50Hz at 90℃℃℃℃

Reactance

(50Hz)

mm2 ΩΩΩΩ/km ΩΩΩΩ/km

16 1.47 0.117

25 0.927 0.112

35 0.668 0.108

50 0.494 0.104

70 0.342 0.099

95 0.247 0.096

120 0.196 0.094

150 0.159 0.092

185 0.128 0.091

240 0.0982 0.089

300 0.0793 0.087

400 0.0632 0.087

500 0.0509 0.085

630 0.0415 0.083

Page 15: Hi Essence Cable Spec

Doc: HEDoc: HEDoc: HEDoc: HE----SPECSPECSPECSPEC Rev: Rev: Rev: Rev: 4444 ((((02020202/201/201/201/2011111))))

15/67

HI-ESSENCE CABLE SDN. BHD. Factory address: Lot 13662, Kerteh Plastic Park, Kemaman, Terengganu.

Office address: No.2, Jalan Puteri 5/16, Bandar Puteri, 47100 Puchong, Selangor.

Tel:60-3-8061 3793 Fax:60-3-8061 2493 URL:http://www.he-cable.com

HE

TYPE P3::::CU/XLPE/PVC/SWB/PVC CABLE – TWO CORES

0.6/1 (1.2) kV

Conductor Nominal

thickness

of

insulation

Approx.

thickness

of

inner

covering

Nominal

diameter

of

steel

wire

Nominal

thickness

of

outer

sheath

Approx.

overall

diameter

Approx.

cable

weight

Maximum

Conductor

Resistance

(at 20℃℃℃℃)

Current

rating

(In air

at 40℃℃℃℃)

Nominal

cross-

sectional

area

No./dia.

of

wire

Approx.

outer

diameter

mm2 No./mm mm mm mm mm mm mm kg/km ΩΩΩΩ/km A

1.5 7/0.53 1.59 0.7 1.0 0.3 1.2 12.4 215 12.1 29

2.5 7/0.67 2.01 0.7 1.0 0.3 1.2 13.2 250 7.41 38

4 7/0.85 2.55 0.7 1.0 0.3 1.2 14.4 310 4.61 45

6 7/1.04 3.12 0.7 1.0 0.3 1.3 15.6 375 3.08 58

10 c.c 3.8 0.7 1.0 0.3 1.3 17.5 495 1.83 79

16 c.c 5.0 0.7 1.0 0.3 1.4 20.1 660 1.15 105

25 c.c 6.1 0.9 1.0 0.3 1.5 23.5 930 0.727 140

35 c.c 7.1 0.9 1.0 0.3 1.6 25.7 1175 0.524 170

50 c.c 8.2 1.0 1.0 0.3 1.7 28.5 1485 0.387 210

70 c.c 10.0 1.1 1.0 0.3 1.9 32.9 2025 0.268 260

95 c.c 11.6 1.1 1.2 0.3 2.0 36.7 2655 0.193 320

120 c.c 13.1 1.2 1.2 0.3 2.1 40.5 3255 0.153 370

150 c.c 14.5 1.4 1.2 0.3 2.3 44.5 3950 0.124 425

185 c.c 16.3 1.6 1.4 0.3 2.5 49.9 4925 0.0991 485

240 c.c 18.6 1.7 1.4 0.3 2.6 55.1 6220 0.0754 575

Note:c.c. -- compacted circular stranded conductor.

Conductor

Size

Maximum

Conductor

Resistance

50Hz at 90℃℃℃℃

Reactance

(50Hz)

mm2 ΩΩΩΩ/km ΩΩΩΩ/km

1.5 15.43 0.103

2.5 9.45 0.0961

4 5.88 0.0899

6 3.93 0.0853

10 2.33 0.078

16 1.47 0.0767

25 0.927 0.077

35 0.669 0.0746

50 0.494 0.0738

70 0.342 0.0726

95 0.247 0.0708

120 0.196 0.0709

150 0.16 0.0719

185 0.128 0.072

240 0.0987 0.0713

300 0.0798 0.0707

400 0.064 0.0704

Page 16: Hi Essence Cable Spec

Doc: HEDoc: HEDoc: HEDoc: HE----SPECSPECSPECSPEC Rev: Rev: Rev: Rev: 4444 ((((02020202/201/201/201/2011111))))

16/67

HI-ESSENCE CABLE SDN. BHD. Factory address: Lot 13662, Kerteh Plastic Park, Kemaman, Terengganu.

Office address: No.2, Jalan Puteri 5/16, Bandar Puteri, 47100 Puchong, Selangor.

Tel:60-3-8061 3793 Fax:60-3-8061 2493 URL:http://www.he-cable.com

HE

TYPE P3::::CU/XLPE/PVC/SWB/PVC CABLE – THREE CORES

0.6/1 (1.2) kV

Conductor Nominal

thickness

of

insulation

Approx.

thickness

of

inner

covering

Nominal

diameter

of

steel

wire

Nominal

thickness

of

outer

sheath

Approx.

overall

diameter

Approx.

cable

weight

Maximum

Conductor

Resistance

(at 20℃℃℃℃)

Current

rating

(In air

at 40℃℃℃℃)

Nominal

cross-

sectional

area

No./dia.

of

wire

Approx.

outer

diameter

mm2 No./mm mm mm mm mm mm mm kg/km ΩΩΩΩ/km A

1.5 7/0.53 1.59 0.7 1.0 0.3 1.2 12.9 245 12.1 21

2.5 7/0.67 2.01 0.7 1.0 0.3 1.2 13.7 290 7.41 27

4 7/0.85 2.55 0.7 1.0 0.3 1.3 15.2 365 4.61 38

6 7/1.04 3.12 0.7 1.0 0.3 1.3 16.3 450 3.08 49

10 c.c 3.8 0.7 1.0 0.3 1.4 18.5 620 1.83 65

16 c.c 5.0 0.7 1.0 0.3 1.4 21.1 820 1.15 89

25 c.c 6.1 0.9 1.0 0.3 1.6 24.9 1195 0.727 120

35 c.c 7.1 0.9 1.0 0.3 1.7 27.3 1530 0.524 145

50 c.c 8.2 1.0 1.0 0.3 1.8 30.3 1960 0.387 175

70 c.c 10.0 1.1 1.2 0.3 2.0 35.4 2725 0.268 225

95 c.c 11.6 1.1 1.2 0.3 2.1 39.1 3560 0.193 275

120 c.c 13.1 1.2 1.2 0.3 2.2 43.1 4390 0.153 315

150 c.c 14.5 1.4 1.4 0.3 2.4 47.8 5390 0.124 365

185 c.c 16.3 1.6 1.4 0.3 2.6 53.2 6670 0.0991 420

240 c.c 18.6 1.7 1.6 0.3 2.8 59.3 8565 0.0754 490

Conductor

Size

Maximum

Conductor

Resistance

50Hz at 90℃℃℃℃

Reactance

(50Hz)

mm2 ΩΩΩΩ/km ΩΩΩΩ/km

1.5 15.43 0.103

2.5 9.45 0.0961

4 5.88 0.0899

6 3.93 0.0853

10 2.33 0.078

16 1.47 0.0767

25 0.927 0.077

35 0.669 0.0746

50 0.494 0.0738

70 0.343 0.0726

95 0.248 0.0708

120 0.197 0.0709

150 0.16 0.0719

185 0.129 0.072

240 0.0996 0.0713

Page 17: Hi Essence Cable Spec

Doc: HEDoc: HEDoc: HEDoc: HE----SPECSPECSPECSPEC Rev: Rev: Rev: Rev: 4444 ((((02020202/201/201/201/2011111))))

17/67

HI-ESSENCE CABLE SDN. BHD. Factory address: Lot 13662, Kerteh Plastic Park, Kemaman, Terengganu.

Office address: No.2, Jalan Puteri 5/16, Bandar Puteri, 47100 Puchong, Selangor.

Tel:60-3-8061 3793 Fax:60-3-8061 2493 URL:http://www.he-cable.com

HE

TYPE P3::::CU/XLPE/PVC/SWB/PVC CABLE –FOUR CORES

0.6/1 (1.2) kV

Conductor Nominal

thickness

of

insulation

Approx.

thickness

of

inner

covering

Nominal

diameter

of

steel

wire

Nominal

thickness

of

outer

sheath

Approx.

overall

diameter

Approx.

cable

weight

Maximum

Conductor

Resistance

(at 20℃℃℃℃)

Current

rating

(In air

at 40℃℃℃℃)

Nominal

cross-

sectional

area

No./dia.

of

wire

Approx.

outer

diameter

mm2 No./mm mm mm mm mm mm mm kg/km ΩΩΩΩ/km A

1.5 7/0.53 1.59 0.7 1.0 0.3 1.2 13.7 280 12.1 21

2.5 7/0.67 2.01 0.7 1.0 0.3 1.2 14.6 335 7.41 27

4 7/0.85 2.55 0.7 1.0 0.3 1.3 16.3 435 4.61 38

6 7/1.04 3.12 0.7 1.0 0.3 1.3 17.5 540 3.08 49

10 c.c 3.8 0.7 1.0 0.3 1.4 19.9 750 1.83 65

16 c.c 5.0 0.7 1.0 0.3 1.5 23.2 1030 1.15 89

25 c.c 6.1 0.9 1.0 0.3 1.7 27.2 1495 0.727 120

35 c.c 7.1 0.9 1.0 0.3 1.8 29.8 1925 0.524 145

50 c.c 8.2 1.0 1.0 0.3 1.9 33.2 2485 0.387 175

70 c.c 10.0 1.1 1.2 0.3 2.1 38.8 3465 0.268 225

95 c.c 11.6 1.1 1.2 0.3 2.2 42.9 4560 0.193 275

120 c.c 13.1 1.2 1.4 0.3 2.4 48.0 5700 0.153 315

150 c.c 14.5 1.4 1.4 0.3 2.6 52.9 6970 0.124 365

185 c.c 16.3 1.6 1.4 0.3 2.8 58.7 8600 0.0991 420

240 c.c 18.6 1.7 1.6 0.3 3.0 65.6 11095 0.0754 490

Note:c.c. -- compacted circular stranded conductor.

Conductor

Size

Maximum

Conductor

Resistance

50Hz at 90℃℃℃℃

Reactance

(50Hz)

mm2 ΩΩΩΩ/km ΩΩΩΩ/km

1.5 15.43 0.103

2.5 9.45 0.0961

4 5.88 0.0899

6 3.93 0.0853

10 2.33 0.078

16 1.47 0.0767

25 0.927 0.077

35 0.669 0.0746

50 0.494 0.0738

70 0.343 0.0726

95 0.248 0.0708

120 0.197 0.0709

150 0.16 0.0719

185 0.129 0.072

240 0.0996 0.0713

Page 18: Hi Essence Cable Spec

Doc: HEDoc: HEDoc: HEDoc: HE----SPECSPECSPECSPEC Rev: Rev: Rev: Rev: 4444 ((((02020202/201/201/201/2011111))))

18/67

HI-ESSENCE CABLE SDN. BHD. Factory address: Lot 13662, Kerteh Plastic Park, Kemaman, Terengganu.

Office address: No.2, Jalan Puteri 5/16, Bandar Puteri, 47100 Puchong, Selangor.

Tel:60-3-8061 3793 Fax:60-3-8061 2493 URL:http://www.he-cable.com

HE

TYPE P3::::CU/XLPE/PVC/SWB/PVC CABLE –FIVE CORES

0.6/1 (1.2) kV

Conductor Nominal

thickness

of

insulation

Approx.

thickness

of

inner

covering

Nominal

diameter

of

steel

wire

Nominal

thickness

of

outer

sheath

Approx.

overall

diameter

Approx.

cable

weight

Maximum

Conductor

Resistance

(at 20℃℃℃℃)

Current

rating

(In air

at 40℃℃℃℃)

Nominal

cross-

sectional

area

No./dia.

of

wire

Approx.

outer

diameter

mm2 No./mm mm mm mm mm mm mm kg/km ΩΩΩΩ/km A

1.5 7/0.53 1.59 0.7 1.0 0.3 1.2 14.6 310 12.1 19

2.5 7/0.67 2.01 0.7 1.0 0.3 1.3 15.9 385 7.41 22

4 7/0.85 2.55 0.7 1.0 0.3 1.3 17.5 495 4.61 31

6 7/1.04 3.12 0.7 1.0 0.3 1.4 19.0 625 3.08 40

10 c.c 3.8 0.7 1.0 0.3 1.5 21.8 890 1.83 53

16 c.c 5.0 0.7 1.0 0.3 1.6 25.3 1215 1.15 73

25 c.c 6.1 0.9 1.0 0.3 1.7 29.5 1755 0.727 99

35 c.c 7.1 0.9 1.0 0.3 1.9 32.6 2290 0.524 119

50 c.c 8.2 1.0 1.2 0.3 2.0 36.7 2990 0.387 144

70 c.c 10.0 1.1 1.2 0.3 2.2 42.5 4130 0.268 185

95 c.c 11.6 1.1 1.4 0.3 2.4 47.6 5520 0.193 227

Conductor

Size

Maximum

Conductor

Resistance

50Hz at 90℃℃℃℃

Reactance

(50Hz)

mm2 ΩΩΩΩ/km ΩΩΩΩ/km

1.5 15.43 0.103

2.5 9.45 0.0961

4 5.88 0.0899

6 3.93 0.0853

10 2.33 0.078

16 1.47 0.0767

25 0.927 0.077

35 0.669 0.0746

50 0.494 0.0738

70 0.343 0.0726

95 0.248 0.0708

Page 19: Hi Essence Cable Spec

Doc: HEDoc: HEDoc: HEDoc: HE----SPECSPECSPECSPEC Rev: Rev: Rev: Rev: 4444 ((((02020202/201/201/201/2011111))))

19/67

HI-ESSENCE CABLE SDN. BHD. Factory address: Lot 13662, Kerteh Plastic Park, Kemaman, Terengganu.

Office address: No.2, Jalan Puteri 5/16, Bandar Puteri, 47100 Puchong, Selangor.

Tel:60-3-8061 3793 Fax:60-3-8061 2493 URL:http://www.he-cable.com

HE

TYPE P3::::CU/XLPE/PVC/SWB/PVC CABLE –MULTI-CORES(1.5 mm2)

0.6/1 (1.2) kV

No.

of core

Conductor Nominal

thickness

of

insulation

Approx.

thickness

of

inner

covering

Nominal

diameter

of

steel

wire

Nominal

thickness

of

outer

sheath

Approx.

overall

diameter

Approx.

cable

weight

Maximum

Conductor

Resistance

ΩΩΩΩ/km

Current

rating

(In air

at 40℃℃℃℃)

Nominal

cross-

sectional

area

No./dia.

of

wire

Approx.

outer

diameter

C mm2 No./mm mm mm mm mm mm mm kg/km 20℃℃℃℃ 90℃℃℃℃ A

6 1.5 7/0.53 1.59 0.7 1.0 0.3 1.3 15.7 355

12.1 15.43

17

7 1.5 7/0.53 1.59 0.7 1.0 0.3 1.3 15.7 370 16

8 1.5 7/0.53 1.59 0.7 1.0 0.3 1.3 16.6 410 15

9 1.5 7/0.53 1.59 0.7 1.0 0.3 1.4 17.8 440 15

10 1.5 7/0.53 1.59 0.7 1.0 0.3 1.4 19.0 500 14

11 1.5 7/0.53 1.59 0.7 1.0 0.3 1.4 19.0 520 14

12 1.5 7/0.53 1.59 0.7 1.0 0.3 1.4 19.5 545 13

13 1.5 7/0.53 1.59 0.7 1.0 0.3 1.4 20.3 585 13

14 1.5 7/0.53 1.59 0.7 1.0 0.3 1.4 20.3 600 13

15 1.5 7/0.53 1.59 0.7 1.0 0.3 1.5 21.6 660 12

16 1.5 7/0.53 1.59 0.7 1.0 0.3 1.5 21.6 675 12

17 1.5 7/0.53 1.59 0.7 1.0 0.3 1.5 22.5 720 12

18 1.5 7/0.53 1.59 0.7 1.0 0.3 1.5 22.5 735 12

19 1.5 7/0.53 1.59 0.7 1.0 0.3 1.5 22.5 750 12

20 1.5 7/0.53 1.59 0.7 1.0 0.3 1.5 23.4 795 11

21 1.5 7/0.53 1.59 0.7 1.0 0.3 1.5 23.4 810 11

24 1.5 7/0.53 1.59 0.7 1.0 0.3 1.6 25.8 930 10

27 1.5 7/0.53 1.59 0.7 1.0 0.3 1.6 26.3 995 9

30 1.5 7/0.53 1.59 0.7 1.0 0.3 1.7 27.3 1080 8

37 1.5 7/0.53 1.59 0.7 1.0 0.3 1.7 29.1 1255 7

TYPE P3::::CU/XLPE/PVC/SWB/PVC CABLE –MULTI-CORES(2.5 mm2)

0.6/1 (1.2) kV

No.

of core

Conductor Nominal

thickness

of

insulation

Approx.

thickness

of

inner

covering

Nominal

diameter

of

steel

wire

Nominal

thickness

of

outer

sheath

Approx.

overall

diameter

Approx.

cable

weight

Maximum

Conductor

Resistance

ΩΩΩΩ/km

Current

rating

(In air

at 40℃℃℃℃)

Nominal

cross-

sectional

area

No./dia.

of

wire

Approx.

outer

diameter

C mm2 No./mm mm mm mm mm mm mm kg/km 20℃℃℃℃ 90℃℃℃℃ A

6 2.5 7/0.67 2.01 0.7 1.0 0.3 1.3 16.9 435 7.41 9.45

20

7 2.5 7/0.67 2.01 0.7 1.0 0.3 1.3 16.9 460 19

8 2.5 7/0.67 2.01 0.7 1.0 0.3 1.4 18.2 525 18

9 2.5 7/0.67 2.01 0.7 1.0 0.3 1.4 19.6 560 17

10 2.5 7/0.67 2.01 0.7 1.0 0.3 1.5 21.0 650 16

11 2.5 7/0.67 2.01 0.7 1.0 0.3 1.5 21.0 680 15

12 2.5 7/0.67 2.01 0.7 1.0 0.3 1.5 21.5 710 15

13 2.5 7/0.67 2.01 0.7 1.0 0.3 1.5 22.4 765 15

14 2.5 7/0.67 2.01 0.7 1.0 0.3 1.5 22.4 790 14

15 2.5 7/0.67 2.01 0.7 1.0 0.3 1.5 23.5 845 14

16 2.5 7/0.67 2.01 0.7 1.0 0.3 1.5 23.5 870 14

17 2.5 7/0.67 2.01 0.7 1.0 0.3 1.6 24.7 940 13

18 2.5 7/0.67 2.01 0.7 1.0 0.3 1.6 24.7 960 13

19 2.5 7/0.67 2.01 0.7 1.0 0.3 1.6 24.7 985 13

20 2.5 7/0.67 2.01 0.7 1.0 0.3 1.6 25.8 1045 13

21 2.5 7/0.67 2.01 0.7 1.0 0.3 1.6 25.8 1070 12

24 2.5 7/0.67 2.01 0.7 1.0 0.3 1.7 28.4 1230 11

27 2.5 7/0.67 2.01 0.7 1.0 0.3 1.7 28.9 1315 10

Page 20: Hi Essence Cable Spec

Doc: HEDoc: HEDoc: HEDoc: HE----SPECSPECSPECSPEC Rev: Rev: Rev: Rev: 4444 ((((02020202/201/201/201/2011111))))

20/67

HI-ESSENCE CABLE SDN. BHD. Factory address: Lot 13662, Kerteh Plastic Park, Kemaman, Terengganu.

Office address: No.2, Jalan Puteri 5/16, Bandar Puteri, 47100 Puchong, Selangor.

Tel:60-3-8061 3793 Fax:60-3-8061 2493 URL:http://www.he-cable.com

HE

TYPE P3::::CU/XLPE/PVC/SWB/PVC CABLE –MULTI-CORES(4 mm2)

0.6/1 (1.2) kV

No.

of core

Conductor Nominal

thickness

of

insulation

Approx.

thickness

of

inner

covering

Nominal

diameter

of

steel

wire

Nominal

thickness

of

outer

sheath

Approx.

overall

diameter

Approx.

cable

weight

Maximum

Conductor

Resistance

ΩΩΩΩ/km

Current

rating

(In air

at 40℃℃℃℃)

Nominal

cross-

sectional

area

No./dia.

of

wire

Approx.

outer

diameter

C mm2 No./mm mm mm mm mm mm mm kg/km 20℃℃℃℃ 90℃℃℃℃ A

6 4 7/0.85 2.55 0.7 1.0 0.3 1.4 18.9 575 4.61 5.88

28

7 4 7/0.85 2.55 0.7 1.0 0.3 1.4 18.9 610 26

8 4 7/0.85 2.55 0.7 1.0 0.3 1.5 20.6 700 25

9 4 7/0.85 2.55 0.7 1.0 0.3 1.5 21.8 775 23

10 4 7/0.85 2.55 0.7 1.0 0.3 1.5 23.4 855 22

11 4 7/0.85 2.55 0.7 1.0 0.3 1.5 23.4 900 22

12 4 7/0.85 2.55 0.7 1.0 0.3 1.6 24.2 955 21

13 4 7/0.85 2.55 0.7 1.0 0.3 1.6 25.3 1030 21

14 4 7/0.85 2.55 0.7 1.0 0.3 1.6 25.3 1070 20

15 4 7/0.85 2.55 0.7 1.0 0.3 1.6 26.5 1150 20

16 4 7/0.85 2.55 0.7 1.0 0.3 1.6 26.5 1185 19

17 4 7/0.85 2.55 0.7 1.0 0.3 1.7 27.9 1280 19

18 4 7/0.85 2.55 0.7 1.0 0.3 1.7 27.9 1315 19

19 4 7/0.85 2.55 0.7 1.0 0.3 1.7 27.9 1355 18

20 4 7/0.85 2.55 0.7 1.0 0.3 1.7 29.2 1435 18

21 4 7/0.85 2.55 0.7 1.0 0.3 1.7 29.2 1475 17

24 4 7/0.85 2.55 0.7 1.0 0.3 1.8 32.2 1690 16

27 4 7/0.85 2.55 0.7 1.0 0.3 1.9 33.0 1840 14

Note:c.c. -- compacted circular stranded conductor.

Page 21: Hi Essence Cable Spec

Doc: HEDoc: HEDoc: HEDoc: HE----SPECSPECSPECSPEC Rev: Rev: Rev: Rev: 4444 ((((02020202/201/201/201/2011111))))

21/67

HI-ESSENCE CABLE SDN. BHD. Factory address: Lot 13662, Kerteh Plastic Park, Kemaman, Terengganu.

Office address: No.2, Jalan Puteri 5/16, Bandar Puteri, 47100 Puchong, Selangor.

Tel:60-3-8061 3793 Fax:60-3-8061 2493 URL:http://www.he-cable.com

HE

ETHYLENE PROPYLENE RUBBER INSULATED BRAIDED EVA SHEATHED

FLAME RETARDANT CABLE

TYPE P4A : CU/EPR/EVA/SWB/EVA CABLE

TYPE P4A : CU/EPR/EVA/TCWB/EVA CABLE DESCRIPTION

Single core and multi-core cables with copper conductor, EPR insulated, flame retardant low smoke free

halogen compound EVA inner covering, galvanized steel wire braided and flame retardant low smoke free

halogen compound EVA outer sheath.

Cables are rated at 0.6/1 (1.2) kV

CONSTRUCTION

1 Conductor

Plain annealed circular stranded copper conductor, conform to IEC 60228 class 2.

2 Insulation

EPR (Ethylene propylene rubber)

3 Colour for core identification

Single core - Black

Two core - Red, black

Three core - Red, yellow and blue

Four core - Red, yellow, blue and black

Five core & above - White core with black numbering

4 Cabling

Two, three, four, five or more insulated cores are laid up together, if necessary filled with non-hygroscopic

material compatible with the insulation.

5 Inner covering

Flame retardant low smoke free halogen compound EVA, colour black.

6 Armour

Single core -- Tinned copper wires shall be braided over the EVA inner covering.

Multi-core -- Galvanized steel wires shall be braided over the EVA inner covering.

7 Outer sheath

Flame retardant low smoke free halogen compound EVA, colour black. CABLE MARKING

manufacturer’s name, rated voltage, cable type, conductor size, manufacture year. SPECIFICATIONS

IEC 60092, IEC 60092-353

IEC 60332-3 Cat A

IEC 60754 (HCL emission 0.5% maximum by weight)

ASTM D 2863(Oxygen index greater than 30%)

Page 22: Hi Essence Cable Spec

Doc: HEDoc: HEDoc: HEDoc: HE----SPECSPECSPECSPEC Rev: Rev: Rev: Rev: 4444 ((((02020202/201/201/201/2011111))))

22/67

HI-ESSENCE CABLE SDN. BHD. Factory address: Lot 13662, Kerteh Plastic Park, Kemaman, Terengganu.

Office address: No.2, Jalan Puteri 5/16, Bandar Puteri, 47100 Puchong, Selangor.

Tel:60-3-8061 3793 Fax:60-3-8061 2493 URL:http://www.he-cable.com

HE

TYPE P4A::::TCU/EPR/EVA/TCWB/EVA CABLE – SINGLE CORE

0.6/1 (1.2) kV

Conductor Nominal

thickness

of

insulation

Approx.

thickness

of

inner

covering

Nominal

diameter

of

tinned copper

wire

Nominal

thickness

of

outer

sheath

Approx.

overall

diameter

Approx.

cable

weight

Maximum

Conductor

Resistance

(at 20℃℃℃℃)

Current

rating

(In air

at 40℃℃℃℃)

Nominal

cross-

sectional

area

No./dia.

of

wire

Approx.

outer

diameter

mm2 No./mm mm mm mm mm mm mm kg/km ΩΩΩΩ/km A

16 7/1.70 5.10 1.0 1.0 0.3 1.2 13.5 385 1.16 100

25 7/2.14 6.42 1.2 1.0 0.3 1.3 15.5 530 0.734 134

35 7/2.52 7.56 1.2 1.0 0.3 1.3 16.7 655 0.529 164

50 19/1.78 8.90 1.4 1.0 0.3 1.4 18.6 825 0.391 199

70 19/2.14 10.70 1.4 1.0 0.3 1.4 20.4 1070 0.270 254

95 19/2.52 12.60 1.6 1.0 0.3 1.5 23.2 1415 0.195 308

120 37/2.03 14.21 1.6 1.0 0.3 1.6 25.0 1705 0.154 364

150 37/2.25 15.75 1.8 1.0 0.3 1.6 27.0 2030 0.126 412

185 37/2.52 17.64 2.0 1.0 0.3 1.7 29.4 2470 0.100 478

240 61/2.25 20.25 2.2 1.0 0.3 1.8 32.7 3135 0.0762 567

Conductor

Size

Maximum

Conductor

Resistance

50Hz at 90℃℃℃℃

Reactance

(50Hz)

mm2 ΩΩΩΩ/km ΩΩΩΩ/km

16 1.48 0.12

25 0.936 0.115

35 0.674 0.109

50 0.499 0.106

70 0.345 0.1

95 0.25 0.098

120 0.197 0.095

150 0.162 0.093

185 0.129 0.091

240 0.0992 0.089

Page 23: Hi Essence Cable Spec

Doc: HEDoc: HEDoc: HEDoc: HE----SPECSPECSPECSPEC Rev: Rev: Rev: Rev: 4444 ((((02020202/201/201/201/2011111))))

23/67

HI-ESSENCE CABLE SDN. BHD. Factory address: Lot 13662, Kerteh Plastic Park, Kemaman, Terengganu.

Office address: No.2, Jalan Puteri 5/16, Bandar Puteri, 47100 Puchong, Selangor.

Tel:60-3-8061 3793 Fax:60-3-8061 2493 URL:http://www.he-cable.com

HE

TYPE P4A::::TCU/EPR/EVA/SWB/EVA CABLE – TWO CORES

0.6/1 (1.2) kV

Conductor Nominal

thickness

of

insulation

Approx.

thickness

of

inner

covering

Nominal

diameter

of

steel

wire

Nominal

thickness

of

outer

sheath

Approx.

overall

diameter

Approx.

cable

weight

Maximum

Conductor

Resistance

(at 20℃℃℃℃)

Current

rating

(In air

at 40℃℃℃℃)

Nominal

cross-

sectional

area

No./dia.

of

wire

Approx.

outer

diameter

mm2 No./mm mm mm mm mm mm mm kg/km ΩΩΩΩ/km A

1.5 7/0.53 1.59 1.0 1.0 0.3 1.2 13.8 265 12.2 29

2.5 7/0.67 2.01 1.0 1.0 0.3 1.2 14.6 305 7.56 38

4 7/0.85 2.55 1.0 1.0 0.3 1.3 16.0 375 4.70 45

6 7/1.04 3.12 1.0 1.0 0.3 1.3 17.0 440 3.11 58

10 7/1.35 4.05 1.0 1.0 0.3 1.4 19.9 605 1.84 79

16 7/1.70 5.10 1.0 1.0 0.3 1.5 22.3 800 1.16 105

25 7/2.14 6.42 1.2 1.0 0.3 1.6 26.1 1125 0.734 139

35 7/2.52 7.56 1.2 1.0 0.3 1.7 28.7 1410 0.529 169

50 19/1.78 8.90 1.4 1.0 0.3 1.8 32.3 1795 0.391 209

70 19/2.14 10.70 1.4 1.0 0.3 1.9 36.1 2350 0.270 259

95 19/2.52 12.60 1.6 1.2 0.3 2.1 41.7 3165 0.195 318

120 37/2.03 14.21 1.6 1.2 0.3 2.2 45.1 3795 0.154 369

150 37/2.25 15.75 1.8 1.2 0.3 2.3 49.3 4560 0.126 422

185 37/2.52 17.64 2.0 1.4 0.3 2.5 54.7 5650 0.100 483

Conductor

Size

Maximum

Conductor

Resistance

50Hz at 90℃℃℃℃

Reactance

(50Hz)

mm2 ΩΩΩΩ/km ΩΩΩΩ/km

1.5 15.56 0.114

2.5 9.64 0.106

4 5.99 0.099

6 3.97 0.093

10 2.34 0.087

16 1.48 0.083

25 0.936 0.082

35 0.675 0.079

50 0.499 0.079

70 0.345 0.076

95 0.25 0.075

120 0.197 0.0738

150 0.16 0.0738

185 0.129 0.0736

Page 24: Hi Essence Cable Spec

Doc: HEDoc: HEDoc: HEDoc: HE----SPECSPECSPECSPEC Rev: Rev: Rev: Rev: 4444 ((((02020202/201/201/201/2011111))))

24/67

HI-ESSENCE CABLE SDN. BHD. Factory address: Lot 13662, Kerteh Plastic Park, Kemaman, Terengganu.

Office address: No.2, Jalan Puteri 5/16, Bandar Puteri, 47100 Puchong, Selangor.

Tel:60-3-8061 3793 Fax:60-3-8061 2493 URL:http://www.he-cable.com

HE

TYPE P4A::::TCU/EPR/EVA/SWB/EVA CABLE – THREE CORES

0.6/1 (1.2) kV

Conductor Nominal

thickness

of

insulation

Approx.

thickness

of

inner

covering

Nominal

diameter

of

steel

wire

Nominal

thickness

of

outer

sheath

Approx.

overall

diameter

Approx.

cable

weight

Maximum

Conductor

Resistance

(at 20℃℃℃℃)

Current

rating

(In air

at 40℃℃℃℃)

Nominal

cross-

sectional

area

No./dia.

of

wire

Approx.

outer

diameter

mm2 No./mm mm mm mm mm mm mm kg/km ΩΩΩΩ/km A

1.5 7/0.53 1.59 1.0 1.0 0.3 1.2 14.4 305 12.2 21

2.5 7/0.67 2.01 1.0 1.0 0.3 1.3 15.5 365 7.56 27

4 7/0.85 2.55 1.0 1.0 0.3 1.3 16.7 440 4.70 38

6 7/1.04 3.12 1.0 1.0 0.3 1.4 18.0 540 3.11 49

10 7/1.35 4.05 1.0 1.0 0.3 1.4 20.9 745 1.84 65

16 7/1.70 5.10 1.0 1.0 0.3 1.5 23.4 1000 1.16 89

25 7/2.14 6.42 1.2 1.0 0.3 1.6 27.5 1430 0.734 119

35 7/2.52 7.56 1.2 1.0 0.3 1.7 30.3 1820 0.529 144

50 19/1.78 8.90 1.4 1.0 0.3 1.9 34.4 2350 0.391 174

70 19/2.14 10.70 1.4 1.2 0.3 2.0 38.9 3160 0.270 224

95 19/2.52 12.60 1.6 1.2 0.3 2.2 44.4 4215 0.195 274

120 37/2.03 14.21 1.6 1.2 0.3 2.3 48.1 5100 0.154 314

150 37/2.25 15.75 1.8 1.4 0.3 2.5 53.4 6245 0.126 362

Conductor

Size

Maximum

Conductor

Resistance

50Hz at 90℃℃℃℃

Reactance

(50Hz)

mm2 ΩΩΩΩ/km ΩΩΩΩ/km

1.5 15.56 0.114

2.5 9.64 0.106

4 5.99 0.099

6 3.97 0.093

10 2.34 0.087

16 1.48 0.083

25 0.936 0.082

35 0.675 0.079

50 0.499 0.079

70 0.345 0.076

95 0.25 0.075

120 0.197 0.0738

150 0.16 0.0738

Page 25: Hi Essence Cable Spec

Doc: HEDoc: HEDoc: HEDoc: HE----SPECSPECSPECSPEC Rev: Rev: Rev: Rev: 4444 ((((02020202/201/201/201/2011111))))

25/67

HI-ESSENCE CABLE SDN. BHD. Factory address: Lot 13662, Kerteh Plastic Park, Kemaman, Terengganu.

Office address: No.2, Jalan Puteri 5/16, Bandar Puteri, 47100 Puchong, Selangor.

Tel:60-3-8061 3793 Fax:60-3-8061 2493 URL:http://www.he-cable.com

HE

TYPE P4A::::TCU/EPR/EVA/SWB/EVA CABLE –FOUR CORES

0.6/1 (1.2) kV

Conductor Nominal

thickness

of

insulation

Approx.

thickness

of

inner

covering

Nominal

diameter

of

steel

wire

Nominal

thickness

of

outer

sheath

Approx.

overall

diameter

Approx.

cable

weight

Maximum

Conductor

Resistance

(at 20℃℃℃℃)

Current

rating

(In air

at 40℃℃℃℃)

Nominal

cross-

sectional

area

No./dia.

of

wire

Approx.

outer

diameter

mm2 No./mm mm mm mm mm mm mm kg/km ΩΩΩΩ/km A

1.5 7/0.53 1.59 1.0 1.0 0.3 1.3 15.6 360 12.2 21

2.5 7/0.67 2.01 1.0 1.0 0.3 1.3 16.5 425 7.56 27

4 7/0.85 2.55 1.0 1.0 0.3 1.4 18.2 535 4.70 38

6 7/1.04 3.12 1.0 1.0 0.3 1.4 19.4 645 3.11 49

10 7/1.35 4.05 1.0 1.0 0.3 1.5 22.9 925 1.84 65

16 7/1.70 5.10 1.0 1.0 0.3 1.6 25.6 1245 1.16 89

25 7/2.14 6.42 1.2 1.0 0.3 1.7 30.1 1795 0.734 119

35 7/2.52 7.56 1.2 1.0 0.3 1.8 33.2 2295 0.529 144

50 19/1.78 8.90 1.4 1.2 0.3 2.0 38.1 3015 0.391 174

70 19/2.14 10.70 1.4 1.2 0.3 2.1 42.7 4025 0.270 224

95 19/2.52 12.60 1.6 1.2 0.3 2.3 48.8 5390 0.195 274

120 37/2.03 14.21 1.6 1.4 0.3 2.5 53.7 6635 0.154 314

Conductor

Size

Maximum

Conductor

Resistance

50Hz at 90℃℃℃℃

Reactance

(50Hz)

mm2 ΩΩΩΩ/km ΩΩΩΩ/km

1.5 15.56 0.114

2.5 9.64 0.106

4 5.99 0.099

6 3.97 0.093

10 2.34 0.087

16 1.48 0.083

25 0.936 0.082

35 0.675 0.079

50 0.499 0.079

70 0.345 0.076

95 0.25 0.075

120 0.197 0.0738

Page 26: Hi Essence Cable Spec

Doc: HEDoc: HEDoc: HEDoc: HE----SPECSPECSPECSPEC Rev: Rev: Rev: Rev: 4444 ((((02020202/201/201/201/2011111))))

26/67

HI-ESSENCE CABLE SDN. BHD. Factory address: Lot 13662, Kerteh Plastic Park, Kemaman, Terengganu.

Office address: No.2, Jalan Puteri 5/16, Bandar Puteri, 47100 Puchong, Selangor.

Tel:60-3-8061 3793 Fax:60-3-8061 2493 URL:http://www.he-cable.com

HE

TYPE P4A::::TCU/EPR/EVA/SWB/EVA CABLE –FIVE CORES

0.6/1 (1.2) kV

Conductor Nominal

thickness

of

insulation

Approx.

thickness

of

inner

covering

Nominal

diameter

of

steel

wire

Nominal

thickness

of

outer

sheath

Approx.

overall

diameter

Approx.

cable

weight

Maximum

Conductor

Resistance

(at 20℃℃℃℃)

Current

rating

(In air

at 40℃℃℃℃)

Nominal

cross-

sectional

area

No./dia.

of

wire

Approx.

outer

diameter

mm2 No./mm mm mm mm mm mm mm kg/km ΩΩΩΩ/km A

1.5 7/0.53 1.59 1.0 1.0 0.3 1.3 16.7 400 12.2 19

2.5 7/0.67 2.01 1.0 1.0 0.3 1.4 17.9 485 7.56 22

4 7/0.85 2.55 1.0 1.0 0.3 1.4 19.6 605 4.70 31

6 7/1.04 3.12 1.0 1.0 0.3 1.5 21.3 760 3.11 40

10 7/1.35 4.05 1.0 1.0 0.3 1.5 24.8 1070 1.84 53

16 7/1.70 5.10 1.0 1.0 0.3 1.6 27.7 1420 1.16 73

25 7/2.14 6.42 1.2 1.0 0.3 1.8 32.9 2120 0.734 99

35 7/2.52 7.56 1.2 1.0 0.3 1.9 36.4 2720 0.529 118

50 19/1.78 8.90 1.4 1.2 0.3 2.1 41.8 3570 0.391 143

70 19/2.14 10.70 1.4 1.2 0.3 2.3 47.0 4810 0.270 184

95 19/2.52 12.60 1.6 1.4 0.3 2.5 54.5 6530 0.195 226

Conductor

Size

Maximum

Conductor

Resistance

50Hz at 90℃℃℃℃

Reactance

(50Hz)

mm2 ΩΩΩΩ/km ΩΩΩΩ/km

1.5 15.56 0.114

2.5 9.64 0.106

4 5.99 0.099

6 3.97 0.093

10 2.34 0.087

16 1.48 0.083

25 0.936 0.082

35 0.675 0.079

50 0.499 0.079

70 0.345 0.076

95 0.25 0.075

Page 27: Hi Essence Cable Spec

Doc: HEDoc: HEDoc: HEDoc: HE----SPECSPECSPECSPEC Rev: Rev: Rev: Rev: 4444 ((((02020202/201/201/201/2011111))))

27/67

HI-ESSENCE CABLE SDN. BHD. Factory address: Lot 13662, Kerteh Plastic Park, Kemaman, Terengganu.

Office address: No.2, Jalan Puteri 5/16, Bandar Puteri, 47100 Puchong, Selangor.

Tel:60-3-8061 3793 Fax:60-3-8061 2493 URL:http://www.he-cable.com

HE

TYPE P4A::::TCU/EPR/EVA/SWB/EVA CABLE –MULTI-CORES(1.5 mm2)

0.6/1 (1.2) kV

No.

of core

Conductor Nominal

thickness

of

insulation

Approx.

thickness

of

inner

covering

Nominal

diameter

of

steel

wire

Nominal

thickness

of

outer

sheath

Approx.

overall

diameter

Approx.

cable

weight

Maximum

Conductor

Resistance

ΩΩΩΩ/km

Current

rating

(In air

at 40℃℃℃℃)

Nominal

cross-

sectional

area

No./dia.

of

wire

Approx.

outer

diamete

r

C mm2 No./mm mm mm mm mm mm mm kg/km 20℃℃℃℃ 90℃℃℃℃ A

6 1.5 7/0.53 1.59 1.0 1.0 0.3 1.3 17.8 455

12.2 15.56

17

7 1.5 7/0.53 1.59 1.0 1.0 0.3 1.3 17.8 475 16

8 1.5 7/0.53 1.59 1.0 1.0 0.3 1.4 19.2 540 15

9 1.5 7/0.53 1.59 1.0 1.0 0.3 1.5 20.7 615 15

10 1.5 7/0.53 1.59 1.0 1.0 0.3 1.5 22.2 675 14

11 1.5 7/0.53 1.59 1.0 1.0 0.3 1.5 22.2 705 14

12 1.5 7/0.53 1.59 1.0 1.0 0.3 1.5 22.8 730 13

13 1.5 7/0.53 1.59 1.0 1.0 0.3 1.5 23.8 790 13

14 1.5 7/0.53 1.59 1.0 1.0 0.3 1.5 23.8 810 13

15 1.5 7/0.53 1.59 1.0 1.0 0.3 1.6 25.1 880 12

16 1.5 7/0.53 1.59 1.0 1.0 0.3 1.6 25.1 905 12

17 1.5 7/0.53 1.59 1.0 1.0 0.3 1.6 26.2 965 12

18 1.5 7/0.53 1.59 1.0 1.0 0.3 1.6 26.2 985 12

19 1.5 7/0.53 1.59 1.0 1.0 0.3 1.6 26.2 1010 12

20 1.5 7/0.53 1.59 1.0 1.0 0.3 1.7 27.6 1085 11

21 1.5 7/0.53 1.59 1.0 1.0 0.3 1.7 27.6 1110 11

24 1.5 7/0.53 1.59 1.0 1.0 0.3 1.8 30.4 1270 10

27 1.5 7/0.53 1.59 1.0 1.0 0.3 1.8 31.0 1355 9

30 1.5 7/0.53 1.59 1.0 1.0 0.3 1.8 32.0 1465 8

37 1.5 7/0.53 1.59 1.0 1.0 0.3 1.9 34.4 1725 7

TYPE P4A::::TCU/EPR/EVA/SWB/EVA CABLE –MULTI-CORES(2.5 mm2)

0.6/1 (1.2) kV

No.

of core

Conductor Nominal

thickness

of

insulation

Approx.

thickness

of

inner

covering

Nominal

diameter

of

steel

wire

Nominal

thickness

of

outer

sheath

Approx.

overall

diameter

Approx.

cable

weight

Maximum

Conductor

Resistance

ΩΩΩΩ/km

Current

rating

(In air

at 40℃℃℃℃)

Nominal

cross-

sectional

area

No./dia.

of

wire

Approx.

outer

diameter

C mm2 No./mm mm mm mm mm mm mm kg/km 20℃℃℃℃ 90℃℃℃℃ A

6 2.5 7/0.67 2.01 1.0 1.0 0.3 1.4 19.2 555

7.56 9.64

20

7 2.5 7/0.67 2.01 1.0 1.0 0.3 1.4 19.2 585 19

8 2.5 7/0.67 2.01 1.0 1.0 0.3 1.5 20.9 675 18

9 2.5 7/0.67 2.01 1.0 1.0 0.3 1.5 22.2 745 17

10 2.5 7/0.67 2.01 1.0 1.0 0.3 1.5 23.8 820 16

11 2.5 7/0.67 2.01 1.0 1.0 0.3 1.5 23.8 860 15

12 2.5 7/0.67 2.01 1.0 1.0 0.3 1.6 24.7 910 15

13 2.5 7/0.67 2.01 1.0 1.0 0.3 1.6 25.7 980 15

14 2.5 7/0.67 2.01 1.0 1.0 0.3 1.6 25.7 1010 14

15 2.5 7/0.67 2.01 1.0 1.0 0.3 1.7 27.1 1100 14

16 2.5 7/0.67 2.01 1.0 1.0 0.3 1.7 27.1 1130 14

17 2.5 7/0.67 2.01 1.0 1.0 0.3 1.7 28.4 1210 13

18 2.5 7/0.67 2.01 1.0 1.0 0.3 1.7 28.4 1240 13

19 2.5 7/0.67 2.01 1.0 1.0 0.3 1.7 28.4 1275 13

20 2.5 7/0.67 2.01 1.0 1.0 0.3 1.8 29.9 1365 13

21 2.5 7/0.67 2.01 1.0 1.0 0.3 1.8 29.9 1400 12

24 2.5 7/0.67 2.01 1.0 1.0 0.3 1.9 33.0 1605 11

27 2.5 7/0.67 2.01 1.0 1.0 0.3 1.9 33.7 1725 10

Page 28: Hi Essence Cable Spec

Doc: HEDoc: HEDoc: HEDoc: HE----SPECSPECSPECSPEC Rev: Rev: Rev: Rev: 4444 ((((02020202/201/201/201/2011111))))

28/67

HI-ESSENCE CABLE SDN. BHD. Factory address: Lot 13662, Kerteh Plastic Park, Kemaman, Terengganu.

Office address: No.2, Jalan Puteri 5/16, Bandar Puteri, 47100 Puchong, Selangor.

Tel:60-3-8061 3793 Fax:60-3-8061 2493 URL:http://www.he-cable.com

HE

TYPE P4A::::TCU/EPR/EVA/SWB/EVA CABLE –MULTI-CORES(4 mm2)

0.6/1 (1.2) kV

No.

of core

Conductor Nominal

thickness

of

insulation

Approx.

thickness

of

inner

covering

Nominal

diameter

of

steel

wire

Nominal

thickness

of

outer

sheath

Approx.

overall

diameter

Approx.

cable

weight

Maximum

Conductor

Resistance

ΩΩΩΩ/km

Current

rating

(In air

at 40℃℃℃℃)

Nominal

cross-

sectional

area

No./dia.

of

wire

Approx.

outer

diameter

C mm2 No./mm mm mm mm mm mm mm kg/km 20℃℃℃℃ 90℃℃℃℃ A

6 4 7/0.85 2.55 1.0 1.0 0.3 1.5 21.4 715

4.70 5.99

28

7 4 7/0.85 2.55 1.0 1.0 0.3 1.5 21.4 760 26

8 4 7/0.85 2.55 1.0 1.0 0.3 1.5 22.9 855 25

9 4 7/0.85 2.55 1.0 1.0 0.3 1.6 24.5 960 23

10 4 7/0.85 2.55 1.0 1.0 0.3 1.6 26.4 1060 22

11 4 7/0.85 2.55 1.0 1.0 0.3 1.6 26.4 1115 22

12 4 7/0.85 2.55 1.0 1.0 0.3 1.7 27.3 1180 21

13 4 7/0.85 2.55 1.0 1.0 0.3 1.7 28.6 1275 21

14 4 7/0.85 2.55 1.0 1.0 0.3 1.7 28.6 1325 20

15 4 7/0.85 2.55 1.0 1.0 0.3 1.7 30.0 1425 20

16 4 7/0.85 2.55 1.0 1.0 0.3 1.7 30.0 1470 19

17 4 7/0.85 2.55 1.0 1.0 0.3 1.8 31.6 1585 19

18 4 7/0.85 2.55 1.0 1.0 0.3 1.8 31.6 1630 19

19 4 7/0.85 2.55 1.0 1.0 0.3 1.8 31.6 1680 18

20 4 7/0.85 2.55 1.0 1.0 0.3 1.9 33.3 1800 18

21 4 7/0.85 2.55 1.0 1.0 0.3 1.9 33.3 1845 17

24 4 7/0.85 2.55 1.0 1.2 0.3 2.0 37.2 2155 16

27 4 7/0.85 2.55 1.0 1.2 0.3 2.0 37.9 2325 14

Page 29: Hi Essence Cable Spec

Doc: HEDoc: HEDoc: HEDoc: HE----SPECSPECSPECSPEC Rev: Rev: Rev: Rev: 4444 ((((02020202/201/201/201/2011111))))

29/67

HI-ESSENCE CABLE SDN. BHD. Factory address: Lot 13662, Kerteh Plastic Park, Kemaman, Terengganu.

Office address: No.2, Jalan Puteri 5/16, Bandar Puteri, 47100 Puchong, Selangor.

Tel:60-3-8061 3793 Fax:60-3-8061 2493 URL:http://www.he-cable.com

HE

ETHYLENE PROPYLENE RUBBER INSULATED ARMOURED EVA SHEATHED

FLAME RETARDANT CABLE

TYPE P4B : CU/EPR/EVA/SWA/EVA CABLE

TYPE P4B : CU/EPR/EVA/AWA/EVA CABLE DESCRIPTION

Single core and multi-core cables with copper conductor, EPR insulated, flame retardant low smoke free

halogen compound EVA inner covering, galvanized steel wire armoured and flame retardant low smoke free

halogen compound EVA outer sheath.

Cables are rated at 0.6/1 (1.2) kV

CONSTRUCTION

1 Conductor

Plain annealed circular stranded copper conductor, conform to IEC 60228 class 2.

2 Insulation

EPR (Ethylene propylene rubber)

3 Colour for core identification

Single core - Black

Two core - Red, black

Three core - Red, yellow and blue

Four core - Red, yellow, blue and black

Five core & above - White core with black numbering

4 Cabling

Two, three, four, five or more insulated cores are laid up together, if necessary filled with non-hygroscopic

material compatible with the insulation.

5 Inner covering

Flame retardant low smoke free halogen compound EVA, colour black.

6 Armour

Single core -- Aluminium wires shall be applied over the EVA inner covering.

Multi-core -- Galvanized steel wires shall be applied over the EVA inner covering.

7 Outer sheath

Flame retardant low smoke free halogen compound EVA, colour black. CABLE MARKING

manufacturer’s name, rated voltage, cable type, conductor size, manufacture year. SPECIFICATIONS

IEC 60092, IEC 60502-1

IEC 60332-3 Cat A

IEC 60754 (HCL emission 0.5% maximum by weight)

ASTM D 2863(Oxygen index greater than 30%)

Page 30: Hi Essence Cable Spec

Doc: HEDoc: HEDoc: HEDoc: HE----SPECSPECSPECSPEC Rev: Rev: Rev: Rev: 4444 ((((02020202/201/201/201/2011111))))

30/67

HI-ESSENCE CABLE SDN. BHD. Factory address: Lot 13662, Kerteh Plastic Park, Kemaman, Terengganu.

Office address: No.2, Jalan Puteri 5/16, Bandar Puteri, 47100 Puchong, Selangor.

Tel:60-3-8061 3793 Fax:60-3-8061 2493 URL:http://www.he-cable.com

HE

TYPE P4B::::TCU/EPR/EVA/AWA/EVA CABLE – SINGLE CORE

0.6/1 (1.2) kV

Conductor Nominal

thickness

of

insulation

Approx.

thickness

of

inner

covering

Nominal

diameter

of

aluminium

wire

Nominal

thickness

of

outer

sheath

Approx.

overall

diameter

Approx.

cable

weight

Maximum

Conductor

Resistance

(at 20℃℃℃℃)

Current rating

Nominal

cross-

sectional

area

No./dia.

of

wire

Approx.

outer

diameter

In air

at 40℃℃℃℃

In

ground

at 25℃℃℃℃

mm2 No./mm mm mm mm mm mm mm kg/km ΩΩΩΩ/km A A

16 7/1.70 5.10 1.0 1.0 0.8 1.8 15.3 400 1.16 100 115

25 7/2.14 6.42 1.2 1.0 0.8 1.8 17.1 535 0.734 134 149

35 7/2.52 7.56 1.2 1.0 0.8 1.8 18.3 660 0.529 164 169

50 19/1.78 8.90 1.4 1.0 1.25 1.8 20.9 875 0.391 199 204

70 19/2.14 10.70 1.4 1.0 1.25 1.8 22.7 1120 0.270 254 249

95 19/2.52 12.60 1.6 1.0 1.25 1.8 25.1 1450 0.195 308 298

120 37/2.03 14.21 1.6 1.0 1.6 1.8 27.4 1780 0.154 364 339

150 37/2.25 15.75 1.8 1.0 1.6 1.8 29.4 2115 0.126 412 382

185 37/2.52 17.64 2.0 1.0 1.6 1.8 31.6 2550 0.100 478 433

240 61/2.25 20.25 2.2 1.0 1.6 1.9 34.9 3220 0.0762 567 497

Conductor

Size

Maximum

Conductor

Resistance

50Hz at 90℃℃℃℃

Reactance

(50Hz)

mm2 ΩΩΩΩ/km ΩΩΩΩ/km

16 1.48 0.128

25 0.936 0.121

35 0.674 0.115

50 0.499 0.113

70 0.345 0.107

95 0.25 0.103

120 0.197 0.1

150 0.162 0.098

185 0.129 0.096

240 0.0992 0.093

Page 31: Hi Essence Cable Spec

Doc: HEDoc: HEDoc: HEDoc: HE----SPECSPECSPECSPEC Rev: Rev: Rev: Rev: 4444 ((((02020202/201/201/201/2011111))))

31/67

HI-ESSENCE CABLE SDN. BHD. Factory address: Lot 13662, Kerteh Plastic Park, Kemaman, Terengganu.

Office address: No.2, Jalan Puteri 5/16, Bandar Puteri, 47100 Puchong, Selangor.

Tel:60-3-8061 3793 Fax:60-3-8061 2493 URL:http://www.he-cable.com

HE

TYPE P4B::::TCU/EPR/EVA/SWA/EVA CABLE – TWO CORES

0.6/1 (1.2) kV

Conductor Nominal

thickness

of

insulation

Approx.

thickness

of

inner

covering

Nominal

diameter

of

steel

wire

Nominal

thickness

of

outer

sheath

Approx.

overall

diameter

Approx.

cable

weight

Maximum

Conductor

Resistance

(at 20℃℃℃℃)

Current rating

Nominal

cross-

sectional

area

No./dia.

of

wire

Approx.

outer

diameter

In air

at 40℃℃℃℃

In

ground

at 25℃℃℃℃

mm2 No./mm mm mm mm mm mm mm kg/km ΩΩΩΩ/km A A

1.5 7/0.53 1.59 1.0 1.0 0.8 1.8 15.8 420 12.2 29 33

2.5 7/0.67 2.01 1.0 1.0 0.8 1.8 16.6 470 7.56 38 45

4 7/0.85 2.55 1.0 1.0 0.8 1.8 17.8 545 4.70 45 58

6 7/1.04 3.12 1.0 1.0 1.25 1.8 19.5 735 3.11 58 75

10 7/1.35 4.05 1.0 1.0 1.25 1.8 22.2 940 1.84 79 98

16 7/1.70 5.10 1.0 1.0 1.25 1.8 24.2 1150 1.16 105 124

25 7/2.14 6.42 1.2 1.0 1.6 1.8 28.5 1680 0.734 139 159

35 7/2.52 7.56 1.2 1.0 1.6 1.8 30.9 2020 0.529 169 194

50 19/1.78 8.90 1.4 1.0 1.6 1.9 34.5 2480 0.391 209 229

70 19/2.14 10.70 1.4 1.0 2.0 2.0 39.1 3405 0.270 259 279

95 19/2.52 12.60 1.6 1.2 2.0 2.2 44.7 4365 0.195 318 333

120 37/2.03 14.21 1.6 1.2 2.0 2.3 48.1 5105 0.154 369 379

150 37/2.25 15.75 1.8 1.2 2.5 2.4 53.8 6465 0.126 422 422

185 37/2.52 17.64 2.0 1.4 2.5 2.6 59.0 7750 0.100 483 478

240 61/2.25 20.25 2.2 1.4 2.5 2.8 65.7 9550 0.0762 572 552

Conductor

Size

Maximum

Conductor

Resistance

50Hz at 90℃℃℃℃

Reactance

(50Hz)

mm2 ΩΩΩΩ/km ΩΩΩΩ/km

1.5 15.56 0.114

2.5 9.64 0.106

4 5.99 0.099

6 3.97 0.093

10 2.34 0.087

16 1.48 0.083

25 0.936 0.082

35 0.675 0.079

50 0.499 0.079

70 0.345 0.076

95 0.25 0.075

120 0.197 0.0738

150 0.16 0.0738

185 0.129 0.0736

240 0.0997 0.073

Page 32: Hi Essence Cable Spec

Doc: HEDoc: HEDoc: HEDoc: HE----SPECSPECSPECSPEC Rev: Rev: Rev: Rev: 4444 ((((02020202/201/201/201/2011111))))

32/67

HI-ESSENCE CABLE SDN. BHD. Factory address: Lot 13662, Kerteh Plastic Park, Kemaman, Terengganu.

Office address: No.2, Jalan Puteri 5/16, Bandar Puteri, 47100 Puchong, Selangor.

Tel:60-3-8061 3793 Fax:60-3-8061 2493 URL:http://www.he-cable.com

HE

TYPE P4B::::TCU/EPR/EVA/SWA/EVA CABLE – THREE CORES

0.6/1 (1.2) kV

Conductor Nominal

thickness

of

insulation

Approx.

thickness

of

inner

covering

Nominal

diameter

of

steel

wire

Nominal

thickness

of

outer

sheath

Approx.

overall

diameter

Approx.

cable

weight

Maximum

Conductor

Resistance

(at 20℃℃℃℃)

Current rating

Nominal

cross-

sectional

area

No./dia.

of

wire

Approx.

outer

diameter

In air

at 40℃℃℃℃

In

ground

at 25℃℃℃℃

mm2 No./mm mm mm mm mm mm mm kg/km ΩΩΩΩ/km A A

1.5 7/0.53 1.59 1.0 1.0 0.8 1.8 16.4 465 12.2 21 28

2.5 7/0.67 2.01 1.0 1.0 0.8 1.8 17.3 525 7.56 27 37

4 7/0.85 2.55 1.0 1.0 1.25 1.8 19.2 725 4.70 38 48

6 7/1.04 3.12 1.0 1.0 1.25 1.8 20.3 830 3.11 49 60

10 7/1.35 4.05 1.0 1.0 1.25 1.8 23.2 1090 1.84 65 81

16 7/1.70 5.10 1.0 1.0 1.25 1.8 25.3 1365 1.16 89 105

25 7/2.14 6.42 1.2 1.0 1.6 1.8 29.9 2030 0.734 119 134

35 7/2.52 7.56 1.2 1.0 1.6 1.8 32.5 2470 0.529 144 159

50 19/1.78 8.90 1.4 1.0 1.6 2.0 36.6 3090 0.391 174 189

70 19/2.14 10.70 1.4 1.2 2.0 2.1 41.9 4275 0.270 224 234

95 19/2.52 12.60 1.6 1.2 2.0 2.2 47.2 5485 0.195 274 279

120 37/2.03 14.21 1.6 1.2 2.0 2.3 51.4 6485 0.154 314 319

150 37/2.25 15.75 1.8 1.4 2.5 2.5 57.5 8245 0.126 362 352

185 37/2.52 17.64 2.0 1.4 2.5 2.7 62.6 9865 0.100 418 403

240 61/2.25 20.25 2.2 1.6 2.5 2.9 70.2 12350 0.0762 487 463

Conductor

Size

Maximum

Conductor

Resistance

50Hz at 90℃℃℃℃

Reactance

(50Hz)

mm2 ΩΩΩΩ/km ΩΩΩΩ/km

1.5 15.56 0.114

2.5 9.64 0.106

4 5.99 0.099

6 3.97 0.093

10 2.34 0.087

16 1.48 0.083

25 0.936 0.082

35 0.675 0.079

50 0.499 0.079

70 0.345 0.076

95 0.25 0.075

120 0.197 0.0738

150 0.16 0.0738

185 0.129 0.0736

240 0.0997 0.073

Page 33: Hi Essence Cable Spec

Doc: HEDoc: HEDoc: HEDoc: HE----SPECSPECSPECSPEC Rev: Rev: Rev: Rev: 4444 ((((02020202/201/201/201/2011111))))

33/67

HI-ESSENCE CABLE SDN. BHD. Factory address: Lot 13662, Kerteh Plastic Park, Kemaman, Terengganu.

Office address: No.2, Jalan Puteri 5/16, Bandar Puteri, 47100 Puchong, Selangor.

Tel:60-3-8061 3793 Fax:60-3-8061 2493 URL:http://www.he-cable.com

HE

TYPE P4B::::TCU/EPR/EVA/SWA/EVA CABLE –FOUR CORES

0.6/1 (1.2) kV

Conductor Nominal

thickness

of

insulation

Approx.

thickness

of

inner

covering

Nominal

diameter

of

steel

wire

Nominal

thickness

of

outer

sheath

Approx.

overall

diameter

Approx.

cable

weight

Maximum

Conductor

Resistance

(at 20℃℃℃℃)

Current rating

Nominal

cross-

sectional

area

No./dia.

of

wire

Approx.

outer

diameter

In air

at 40℃℃℃℃

In

ground

at 25℃℃℃℃

mm2 No./mm mm mm mm mm mm mm kg/km ΩΩΩΩ/km A A

1.5 7/0.53 1.59 1.0 1.0 0.8 1.8 17.4 530 12.2 21 28

2.5 7/0.67 2.01 1.0 1.0 0.8 1.8 18.3 605 7.56 27 37

4 7/0.85 2.55 1.0 1.0 1.25 1.8 20.5 830 4.70 38 48

6 7/1.04 3.12 1.0 1.0 1.25 1.8 21.7 970 3.11 49 60

10 7/1.35 4.05 1.0 1.0 1.25 1.8 24.8 1280 1.84 65 81

16 7/1.70 5.10 1.0 1.0 1.6 1.8 28 1790 1.16 89 105

25 7/2.14 6.42 1.2 1.0 1.6 1.8 32.3 2430 0.734 119 134

35 7/2.52 7.56 1.2 1.0 1.6 1.9 35.4 3010 0.529 144 159

50 19/1.78 8.90 1.4 1.2 2.0 2.1 41.1 4110 0.391 174 189

70 19/2.14 10.70 1.4 1.2 2.0 2.2 45.7 5270 0.270 224 234

95 19/2.52 12.60 1.6 1.2 2.5 2.4 53.3 7300 0.195 274 279

120 37/2.03 14.21 1.6 1.4 2.5 2.5 57.8 8670 0.154 314 319

150 37/2.25 15.75 1.8 1.4 2.5 2.7 63.0 10240 0.126 362 352

185 37/2.52 17.64 2.0 1.6 2.5 2.9 69.2 12405 0.100 418 403

240 61/2.25 20.25 2.2 1.6 2.5 3.1 77.1 15470 0.0762 487 463

Conductor

Size

Maximum

Conductor

Resistance

50Hz at 90℃℃℃℃

Reactance

(50Hz)

mm2 ΩΩΩΩ/km ΩΩΩΩ/km

1.5 15.56 0.114

2.5 9.64 0.106

4 5.99 0.099

6 3.97 0.093

10 2.34 0.087

16 1.48 0.083

25 0.936 0.082

35 0.675 0.079

50 0.499 0.079

70 0.345 0.076

95 0.25 0.075

120 0.197 0.0738

150 0.16 0.0738

185 0.129 0.0736

240 0.0997 0.073

Page 34: Hi Essence Cable Spec

Doc: HEDoc: HEDoc: HEDoc: HE----SPECSPECSPECSPEC Rev: Rev: Rev: Rev: 4444 ((((02020202/201/201/201/2011111))))

34/67

HI-ESSENCE CABLE SDN. BHD. Factory address: Lot 13662, Kerteh Plastic Park, Kemaman, Terengganu.

Office address: No.2, Jalan Puteri 5/16, Bandar Puteri, 47100 Puchong, Selangor.

Tel:60-3-8061 3793 Fax:60-3-8061 2493 URL:http://www.he-cable.com

HE

TYPE P4B::::TCU/EPR/EVA/SWA/EVA CABLE –FIVE CORES

0.6/1 (1.2) kV

Conductor Nominal

thickness

of

insulation

Approx.

thickness

of

inner

covering

Nominal

diameter

of

steel

wire

Nominal

thickness

of

outer

sheath

Approx.

overall

diameter

Approx.

cable

weight

Maximum

Conductor

Resistance

(at 20℃℃℃℃)

Current rating

Nominal

cross-

sectional

area

No./dia.

of

wire

Approx.

outer

diameter

In air

at 40℃℃℃℃

In

ground

at 25℃℃℃℃

mm2 No./mm mm mm mm mm mm mm kg/km ΩΩΩΩ/km A A

1.5 7/0.53 1.59 1.0 1.0 0.8 1.8 18.5 580 12.2 19 23

2.5 7/0.67 2.01 1.0 1.0 1.25 1.8 20.2 775 7.56 22 30

4 7/0.85 2.55 1.0 1.0 1.25 1.8 21.9 930 4.70 31 40

6 7/1.04 3.12 1.0 1.0 1.25 1.8 23.2 1085 3.11 40 49

10 7/1.35 4.05 1.0 1.0 1.6 1.8 27.4 1610 1.84 53 67

16 7/1.70 5.10 1.0 1.0 1.6 1.8 30.1 2045 1.16 73 86

25 7/2.14 6.42 1.2 1.0 1.6 1.9 35.1 2820 0.734 99 110

35 7/2.52 7.56 1.2 1.0 2.0 2.0 39.4 3775 0.529 118 131

50 19/1.78 8.90 1.4 1.2 2.0 2.2 44.8 4770 0.391 143 155

70 19/2.14 10.70 1.4 1.2 2.0 2.3 49.8 6135 0.270 184 194

95 19/2.52 12.60 1.6 1.4 2.5 2.5 58.6 8600 0.195 226 230

Conductor

Size

Maximum

Conductor

Resistance

50Hz at 90℃℃℃℃

Reactance

(50Hz)

mm2 ΩΩΩΩ/km ΩΩΩΩ/km

1.5 15.56 0.114

2.5 9.64 0.106

4 5.99 0.099

6 3.97 0.093

10 2.34 0.087

16 1.48 0.083

25 0.936 0.082

35 0.675 0.079

50 0.499 0.079

70 0.345 0.076

95 0.25 0.075

Page 35: Hi Essence Cable Spec

Doc: HEDoc: HEDoc: HEDoc: HE----SPECSPECSPECSPEC Rev: Rev: Rev: Rev: 4444 ((((02020202/201/201/201/2011111))))

35/67

HI-ESSENCE CABLE SDN. BHD. Factory address: Lot 13662, Kerteh Plastic Park, Kemaman, Terengganu.

Office address: No.2, Jalan Puteri 5/16, Bandar Puteri, 47100 Puchong, Selangor.

Tel:60-3-8061 3793 Fax:60-3-8061 2493 URL:http://www.he-cable.com

HE

TYPE P4B::::TCU/EPR/EVA/SWA/EVA CABLE –MULTI-CORES(1.5 mm2)

0.6/1 (1.2) kV

No.

of core

Conductor Nominal

thickness

of

insulation

Approx.

thickness

of

inner

covering

Nominal

diameter

of

steel

wire

Nominal

thickness

of

outer

sheath

Approx.

overall

diameter

Approx.

cable

weight

Maximum

Conductor

Resistance

ΩΩΩΩ/km

Current rating

Nominal

cross-

sectional

area

No./dia.

of

wire

Approx.

outer

diameter

In air

at 40℃℃℃℃

In

ground

at 25℃℃℃℃

C mm2 No./mm mm mm mm mm mm mm kg/km 20℃℃℃℃ 90℃℃℃℃ A A

6 1.5 7/0.53 1.59 1.0 1.0 1.25 1.8 20.3 755

12.2 15.56

17 21

7 1.5 7/0.53 1.59 1.0 1.0 1.25 1.8 20.3 775 16 19

8 1.5 7/0.53 1.59 1.0 1.0 1.25 1.8 21.5 855 15 18

9 1.5 7/0.53 1.59 1.0 1.0 1.25 1.8 22.6 935 15 17

10 1.5 7/0.53 1.59 1.0 1.0 1.25 1.8 24.1 1015 14 16

11 1.5 7/0.53 1.59 1.0 1.0 1.25 1.8 24.1 1045 14 16

12 1.5 7/0.53 1.59 1.0 1.0 1.25 1.8 24.7 1090 13 16

13 1.5 7/0.53 1.59 1.0 1.0 1.6 1.8 26.4 1305 13 15

14 1.5 7/0.53 1.59 1.0 1.0 1.6 1.8 26.4 1330 13 15

15 1.5 7/0.53 1.59 1.0 1.0 1.6 1.8 27.5 1430 12 14

16 1.5 7/0.53 1.59 1.0 1.0 1.6 1.8 27.5 1450 12 14

17 1.5 7/0.53 1.59 1.0 1.0 1.6 1.8 28.6 1535 12 14

18 1.5 7/0.53 1.59 1.0 1.0 1.6 1.8 28.6 1560 12 14

19 1.5 7/0.53 1.59 1.0 1.0 1.6 1.8 28.6 1580 12 13

20 1.5 7/0.53 1.59 1.0 1.0 1.6 1.8 29.8 1670 11 13

21 1.5 7/0.53 1.59 1.0 1.0 1.6 1.8 29.8 1695 11 13

24 1.5 7/0.53 1.59 1.0 1.0 1.6 1.9 32.6 1920 10 11

27 1.5 7/0.53 1.59 1.0 1.0 1.6 1.9 33.2 2020 9 10

30 1.5 7/0.53 1.59 1.0 1.0 1.6 1.9 34.2 2155 8 9

37 1.5 7/0.53 1.59 1.0 1.0 1.6 2.0 36.6 2465 7 8

TYPE P4B::::TCU/EPR/EVA/SWA/EVA CABLE –MULTI-CORES(2.5 mm2)

0.6/1 (1.2) kV

No.

of core

Conductor Nominal

thickness

of

insulation

Approx.

thickness

of

inner

covering

Nominal

diameter

of

steel

wire

Nominal

thickness

of

outer

sheath

Approx.

overall

diameter

Approx.

cable

weight

Maximum

Conductor

Resistance

ΩΩΩΩ/km

Current rating

Nominal

cross-

sectional

area

No./dia.

of

wire

Approx.

outer

diameter

In air

at 40℃℃℃℃

In

ground

at 25℃℃℃℃

C mm2 No./mm mm mm mm mm mm mm kg/km 20℃℃℃℃ 90℃℃℃℃ A A

6 2.5 7/0.67 2.01 1.0 1.0 1.25 1.8 21.5 870

7.56 9.64

20 27

7 2.5 7/0.67 2.01 1.0 1.0 1.25 1.8 21.5 900 19 25

8 2.5 7/0.67 2.01 1.0 1.0 1.25 1.8 22.8 990 18 24

9 2.5 7/0.67 2.01 1.0 1.0 1.6 1.8 24.8 1240 17 23

10 2.5 7/0.67 2.01 1.0 1.0 1.6 1.8 26.4 1335 16 22

11 2.5 7/0.67 2.01 1.0 1.0 1.6 1.8 26.4 1375 15 21

12 2.5 7/0.67 2.01 1.0 1.0 1.6 1.8 27.1 1445 15 21

13 2.5 7/0.67 2.01 1.0 1.0 1.6 1.8 28.1 1540 15 20

14 2.5 7/0.67 2.01 1.0 1.0 1.6 1.8 28.1 1575 14 20

15 2.5 7/0.67 2.01 1.0 1.0 1.6 1.8 29.3 1670 14 19

16 2.5 7/0.67 2.01 1.0 1.0 1.6 1.8 29.3 1705 14 19

17 2.5 7/0.67 2.01 1.0 1.0 1.6 1.8 30.6 1805 13 18

18 2.5 7/0.67 2.01 1.0 1.0 1.6 1.8 30.6 1835 13 18

19 2.5 7/0.67 2.01 1.0 1.0 1.6 1.8 30.6 1870 13 18

20 2.5 7/0.67 2.01 1.0 1.0 1.6 1.9 32.1 2005 13 17

21 2.5 7/0.67 2.01 1.0 1.0 1.6 1.9 32.1 2035 12 17

24 2.5 7/0.67 2.01 1.0 1.0 1.6 1.9 35.0 2290 11 15

27 2.5 7/0.67 2.01 1.0 1.0 1.6 2.0 35.9 2435 10 14

Page 36: Hi Essence Cable Spec

Doc: HEDoc: HEDoc: HEDoc: HE----SPECSPECSPECSPEC Rev: Rev: Rev: Rev: 4444 ((((02020202/201/201/201/2011111))))

36/67

HI-ESSENCE CABLE SDN. BHD. Factory address: Lot 13662, Kerteh Plastic Park, Kemaman, Terengganu.

Office address: No.2, Jalan Puteri 5/16, Bandar Puteri, 47100 Puchong, Selangor.

Tel:60-3-8061 3793 Fax:60-3-8061 2493 URL:http://www.he-cable.com

HE

TYPE P4B::::TCU/EPR/EVA/SWA/EVA CABLE –MULTI-CORES(4 mm2)

0.6/1 (1.2) kV

No.

of core

Conductor Nominal

thickness

of

insulation

Approx.

thickness

of

inner

covering

Nominal

diameter

of

steel

wire

Nominal

thickness

of

outer

sheath

Approx.

overall

diameter

Approx.

cable

weight

Maximum

Conductor

Resistance

ΩΩΩΩ/km

Current rating

Nominal

cross-

sectional

area

No./dia.

of

wire

Approx.

outer

diameter

In air

at 40℃℃℃℃

In

ground

at 25℃℃℃℃

C mm2 No./mm mm mm mm mm mm mm kg/km 20℃℃℃℃ 90℃℃℃℃ A

6 4 7/0.85 2.55 1.0 1.0 1.25 1.8 23.3 1050

4.70 5.99

28 36

7 4 7/0.85 2.55 1.0 1.0 1.25 1.8 23.3 1095 26 33

8 4 7/0.85 2.55 1.0 1.0 1.6 1.8 25.5 1360 25 31

9 4 7/0.85 2.55 1.0 1.0 1.6 1.8 26.9 1475 23 29

10 4 7/0.85 2.55 1.0 1.0 1.6 1.8 28.8 1630 22 28

11 4 7/0.85 2.55 1.0 1.0 1.6 1.8 28.8 1685 22 28

12 4 7/0.85 2.55 1.0 1.0 1.6 1.8 29.5 1750 21 27

13 4 7/0.85 2.55 1.0 1.0 1.6 1.8 30.8 1890 21 26

14 4 7/0.85 2.55 1.0 1.0 1.6 1.8 30.8 1935 20 26

15 4 7/0.85 2.55 1.0 1.0 1.6 1.8 32.2 2060 20 25

16 4 7/0.85 2.55 1.0 1.0 1.6 1.8 32.2 2105 19 24

17 4 7/0.85 2.55 1.0 1.0 1.6 1.9 33.8 2260 19 24

18 4 7/0.85 2.55 1.0 1.0 1.6 1.9 33.8 2305 19 24

19 4 7/0.85 2.55 1.0 1.0 1.6 1.9 33.8 2355 18 23

20 4 7/0.85 2.55 1.0 1.0 1.6 1.9 35.3 2500 18 22

21 4 7/0.85 2.55 1.0 1.0 1.6 1.9 35.3 2545 17 22

24 4 7/0.85 2.55 1.0 1.2 2.0 2.1 40.2 3230 16 20

27 4 7/0.85 2.55 1.0 1.2 2.0 2.1 40.9 3420 14 18

Page 37: Hi Essence Cable Spec

Doc: HEDoc: HEDoc: HEDoc: HE----SPECSPECSPECSPEC Rev: Rev: Rev: Rev: 4444 ((((02020202/201/201/201/2011111))))

37/67

HI-ESSENCE CABLE SDN. BHD. Factory address: Lot 13662, Kerteh Plastic Park, Kemaman, Terengganu.

Office address: No.2, Jalan Puteri 5/16, Bandar Puteri, 47100 Puchong, Selangor.

Tel:60-3-8061 3793 Fax:60-3-8061 2493 URL:http://www.he-cable.com

HE

ETHYLENE PROPYLENE RUBBER INSULATED BRAIDED EVA SHEATHED FIRE

RESISTANT AND FLAME RETARDANT CABLE

TYPE P5 : CU/MICA/EPR/EVA/SWB/EVA CABLE

TYPE P5 : CU/MICA/EPR/EVA/TCWB/EVA CABLE DESCRIPTION

Single core and multi-core cables with copper conductor, mica tape, EPR insulated, flame retardant low smoke

free halogen compound EVA inner covering, galvanized steel wire braided and flame retardant low smoke free

halogen compound EVA outer sheath.

Cables are rated at 0.6/1 (1.2) kV

CONSTRUCTION

1 Conductor

Plain annealed circular stranded copper conductor, conform to IEC 60228 class 2.

2 Fire proof layer

Mica tape.

3 Insulation

EPR (Ethylene propylene rubber)

4 Colour for core identification

Single core - Black

Two core - Red, black

Three core - Red, yellow and blue

Four core - Red, yellow, blue and black

Five core & above - White core with black numbering

5 Cabling

Two, three, four, five or more insulated cores are laid up together, if necessary filled with non-hygroscopic

material compatible with the insulation.

6 Inner covering

Flame retardant low smoke free halogen compound EVA, colour black.

7 Armour

Single core – Tinned copper wires shall be braided over the EVA inner covering.

Multi-core -- Galvanized steel wires shall be braided over the EVA inner covering.

8 Outer sheath

Flame retardant low smoke free halogen compound EVA, colour black. CABLE MARKING

manufacturer’s name, rated voltage, cable type, conductor size, manufacture year.

SPECIFICATIONS

IEC 60092, IEC 60092-353

IEC 60331

IEC 60332-3 Cat A

IEC 60754 (HCL emission 0.5% maximum by weight)

ASTM D 2863(Oxygen index greater than 30%)

Page 38: Hi Essence Cable Spec

Doc: HEDoc: HEDoc: HEDoc: HE----SPECSPECSPECSPEC Rev: Rev: Rev: Rev: 4444 ((((02020202/201/201/201/2011111))))

38/67

HI-ESSENCE CABLE SDN. BHD. Factory address: Lot 13662, Kerteh Plastic Park, Kemaman, Terengganu.

Office address: No.2, Jalan Puteri 5/16, Bandar Puteri, 47100 Puchong, Selangor.

Tel:60-3-8061 3793 Fax:60-3-8061 2493 URL:http://www.he-cable.com

HE

TYPE P5::::TCU/MICA/EPR/EVA/TCWB/EVA CABLE – SINGLE CORE

0.6/1 (1.2) kV

Conductor Nominal

thickness

of

insulation

Approx.

thickness

of

inner

covering

Nominal

diameter

of

tinned

copper

wire

Nominal

thickness

of

outer

sheath

Approx.

overall

diameter

Approx.

cable

weight

Maximum

Conductor

Resistance

(at 20℃℃℃℃)

Current

rating(In

air at 40℃℃℃℃)

Nominal

cross-

sectional

area

No./dia.

of

wire

Approx.

outer

diameter

mm2 No./mm mm mm mm mm mm mm kg/km ΩΩΩΩ/km A

16 7/1.70 5.10 1.0 1.0 0.3 1.2 14.5 415 1.16 100

25 7/2.14 6.42 1.2 1.0 0.3 1.3 16.5 565 0.734 134

35 7/2.52 7.56 1.2 1.0 0.3 1.3 17.7 690 0.529 164

50 19/1.78 8.90 1.4 1.0 0.3 1.4 19.6 865 0.391 199

70 19/2.14 10.70 1.4 1.0 0.3 1.4 21.4 1110 0.270 254

95 19/2.52 12.60 1.6 1.0 0.3 1.5 24.2 1460 0.195 308

120 37/2.03 14.21 1.6 1.0 0.3 1.6 26.0 1750 0.154 364

150 37/2.25 15.75 1.8 1.0 0.3 1.6 28.0 2080 0.126 412

185 37/2.52 17.64 2.0 1.0 0.3 1.7 30.4 2520 0.100 478

240 61/2.25 20.25 2.2 1.0 0.3 1.8 33.7 3190 0.0762 567

Conductor

Size

Maximum

Conductor

Resistance

50Hz at 90℃℃℃℃

Reactance

(50Hz)

mm2 ΩΩΩΩ/km ΩΩΩΩ/km

16 1.48 0.125

25 0.936 0.119

35 0.674 0.113

50 0.499 0.109

70 0.345 0.103

95 0.25 0.1

120 0.197 0.097

150 0.162 0.095

185 0.129 0.093

240 0.0992 0.091

Page 39: Hi Essence Cable Spec

Doc: HEDoc: HEDoc: HEDoc: HE----SPECSPECSPECSPEC Rev: Rev: Rev: Rev: 4444 ((((02020202/201/201/201/2011111))))

39/67

HI-ESSENCE CABLE SDN. BHD. Factory address: Lot 13662, Kerteh Plastic Park, Kemaman, Terengganu.

Office address: No.2, Jalan Puteri 5/16, Bandar Puteri, 47100 Puchong, Selangor.

Tel:60-3-8061 3793 Fax:60-3-8061 2493 URL:http://www.he-cable.com

HE

TYPE P5::::TCU/MICA/EPR/EVA/SWB/EVA CABLE – TWO CORES

0.6/1 (1.2) kV

Conductor Nominal

thickness

of

insulation

Approx.

thickness

of

inner

covering

Nominal

diameter

of

steel

wire

Nominal

thickness

of

outer

sheath

Approx.

overall

diameter

Approx.

cable

weight

Maximum

Conductor

Resistance

(at 20℃℃℃℃)

Current

rating(In

air at 40℃℃℃℃)

Nominal

cross-

sectional

area

No./dia.

of

wire

Approx.

outer

diameter

mm2 No./mm mm mm mm mm mm mm A ΩΩΩΩ/km A

1.5 7/0.53 1.59 1.0 1.0 0.3 1.3 16.2 345 12.2 29

2.5 7/0.67 2.01 1.0 1.0 0.3 1.3 17.0 385 7.56 38

4 7/0.85 2.55 1.0 1.0 0.3 1.3 18.0 445 4.70 45

6 7/1.04 3.12 1.0 1.0 0.3 1.4 19.4 530 3.11 58

10 7/1.35 4.05 1.0 1.0 0.3 1.5 22.3 705 1.84 79

16 7/1.70 5.10 1.0 1.0 0.3 1.5 24.3 880 1.16 105

25 7/2.14 6.42 1.2 1.0 0.3 1.6 28.1 1210 0.734 139

35 7/2.52 7.56 1.2 1.0 0.3 1.7 30.7 1500 0.529 169

50 19/1.78 8.90 1.4 1.0 0.3 1.9 34.5 1915 0.391 209

70 19/2.14 10.70 1.4 1.2 0.3 2.0 38.7 2520 0.270 259

95 19/2.52 12.60 1.6 1.2 0.3 2.2 43.9 3305 0.195 318

120 37/2.03 14.21 1.6 1.2 0.3 2.3 47.3 3955 0.154 369

150 37/2.25 15.75 1.8 1.4 0.3 2.4 51.9 4775 0.126 422

185 37/2.52 17.64 2.0 1.4 0.3 2.6 56.9 5830 0.100 483

240 61/2.25 20.25 2.2 1.6 0.3 2.8 64.0 7470 0.0762 572

Conductor

Size

Maximum

Conductor

Resistance

50Hz at 90℃℃℃℃

Reactance

(50Hz)

mm2 ΩΩΩΩ/km ΩΩΩΩ/km

1.5 15.56 0.13

2.5 9.64 0.12

4 5.99 0.111

6 3.97 0.104

10 2.34 0.096

16 1.48 0.091

25 0.936 0.089

35 0.675 0.084

50 0.499 0.084

70 0.345 0.08

95 0.25 0.079

120 0.197 0.0772

150 0.16 0.0765

185 0.129 0.0763

240 0.0997 0.0752

Page 40: Hi Essence Cable Spec

Doc: HEDoc: HEDoc: HEDoc: HE----SPECSPECSPECSPEC Rev: Rev: Rev: Rev: 4444 ((((02020202/201/201/201/2011111))))

40/67

HI-ESSENCE CABLE SDN. BHD. Factory address: Lot 13662, Kerteh Plastic Park, Kemaman, Terengganu.

Office address: No.2, Jalan Puteri 5/16, Bandar Puteri, 47100 Puchong, Selangor.

Tel:60-3-8061 3793 Fax:60-3-8061 2493 URL:http://www.he-cable.com

HE

TYPE P5::::TCU/MICA/EPR/EVA/SWB/EVA CABLE – THREE CORES

0.6/1 (1.2) kV

Conductor Nominal

thickness

of

insulation

Approx.

thickness

of

inner

covering

Nominal

diameter

of

steel

wire

Nominal

thickness

of

outer

sheath

Approx.

overall

diameter

Approx.

cable

weight

Maximum

Conductor

Resistance

(at 20℃℃℃℃)

Current

rating(In

air at 40℃℃℃℃)

Nominal

cross-

sectional

area

No./dia.

of

wire

Approx.

outer

diameter

mm2 No./mm mm mm mm mm mm mm kg/km ΩΩΩΩ/km A

1.5 7/0.53 1.59 1.0 1.0 0.3 1.3 17.0 395 12.2 21

2.5 7/0.67 2.01 1.0 1.0 0.3 1.3 17.8 445 7.56 27

4 7/0.85 2.55 1.0 1.0 0.3 1.4 19.1 535 4.70 38

6 7/1.04 3.12 1.0 1.0 0.3 1.4 20.4 635 3.11 49

10 7/1.35 4.05 1.0 1.0 0.3 1.5 23.4 855 1.84 65

16 7/1.70 5.10 1.0 1.0 0.3 1.6 25.8 1105 1.16 89

25 7/2.14 6.42 1.2 1.0 0.3 1.7 29.9 1545 0.734 119

35 7/2.52 7.56 1.2 1.0 0.3 1.8 32.7 1935 0.529 144

50 19/1.78 8.90 1.4 1.2 0.3 2.0 37.1 2530 0.391 174

70 19/2.14 10.70 1.4 1.2 0.3 2.1 41.2 3315 0.270 224

95 19/2.52 12.60 1.6 1.2 0.3 2.3 46.8 4380 0.195 274

120 37/2.03 14.21 1.6 1.4 0.3 2.4 50.8 5330 0.154 314

150 37/2.25 15.75 1.8 1.4 0.3 2.5 55.5 6420 0.126 362

185 37/2.52 17.64 2.0 1.4 0.3 2.7 60.7 7840 0.100 418

240 61/2.25 20.25 2.2 1.6 0.3 2.9 68.3 10080 0.0762 487

Conductor

Size

Maximum

Conductor

Resistance

50Hz at 90℃℃℃℃

Reactance

(50Hz)

mm2 ΩΩΩΩ/km ΩΩΩΩ/km

1.5 15.56 0.13

2.5 9.64 0.12

4 5.99 0.111

6 3.97 0.104

10 2.34 0.096

16 1.48 0.091

25 0.936 0.089

35 0.675 0.084

50 0.499 0.084

70 0.345 0.08

95 0.25 0.079

120 0.197 0.0772

150 0.16 0.0765

185 0.129 0.0763

240 0.0997 0.0752

Page 41: Hi Essence Cable Spec

Doc: HEDoc: HEDoc: HEDoc: HE----SPECSPECSPECSPEC Rev: Rev: Rev: Rev: 4444 ((((02020202/201/201/201/2011111))))

41/67

HI-ESSENCE CABLE SDN. BHD. Factory address: Lot 13662, Kerteh Plastic Park, Kemaman, Terengganu.

Office address: No.2, Jalan Puteri 5/16, Bandar Puteri, 47100 Puchong, Selangor.

Tel:60-3-8061 3793 Fax:60-3-8061 2493 URL:http://www.he-cable.com

HE

TYPE P5::::TCU/MICA/EPR/EVA/SWB/EVA CABLE –FOUR CORES

0.6/1 (1.2) kV

Conductor Nominal

thickness

of

insulation

Approx.

thickness

of

inner

covering

Nominal

diameter

of

steel

wire

Nominal

thickness

of

outer

sheath

Approx.

overall

diameter

Approx.

cable

weight

Maximum

Conductor

Resistance

(at 20℃℃℃℃)

Current

rating(In

air at 40℃℃℃℃)

Nominal

cross-

sectional

area

No./dia.

of

wire

Approx.

outer

diameter

mm2 No./mm mm mm mm mm mm mm kg/km ΩΩΩΩ/km A

1.5 7/0.53 1.59 1.0 1.0 0.3 1.3 18.2 460 12.2 21

2.5 7/0.67 2.01 1.0 1.0 0.3 1.4 19.4 535 7.56 27

4 7/0.85 2.55 1.0 1.0 0.3 1.4 20.6 635 4.70 38

6 7/1.04 3.12 1.0 1.0 0.3 1.5 22.4 780 3.11 49

10 7/1.35 4.05 1.0 1.0 0.3 1.6 25.6 1050 1.84 65

16 7/1.70 5.10 1.0 1.0 0.3 1.6 28.0 1360 1.16 89

25 7/2.14 6.42 1.2 1.0 0.3 1.8 32.7 1935 0.734 119

35 7/2.52 7.56 1.2 1.0 0.3 1.9 35.8 2435 0.529 144

50 19/1.78 8.90 1.4 1.2 0.3 2.1 40.7 3190 0.391 174

70 19/2.14 10.70 1.4 1.2 0.3 2.2 45.3 4210 0.270 224

95 19/2.52 12.60 1.6 1.4 0.3 2.4 51.9 5640 0.195 274

120 37/2.03 14.21 1.6 1.4 0.3 2.6 56.3 6865 0.154 314

150 37/2.25 15.75 1.8 1.4 0.3 2.7 61.5 8275 0.126 362

185 37/2.52 17.64 2.0 1.6 0.3 2.9 67.6 10185 0.100 418

Conductor

Size

Maximum

Conductor

Resistance

50Hz at 90℃℃℃℃

Reactance

(50Hz)

mm2 ΩΩΩΩ/km ΩΩΩΩ/km

1.5 15.56 0.13

2.5 9.64 0.12

4 5.99 0.111

6 3.97 0.104

10 2.34 0.096

16 1.48 0.091

25 0.936 0.089

35 0.675 0.084

50 0.499 0.084

70 0.345 0.08

95 0.25 0.079

120 0.197 0.0772

150 0.16 0.0765

185 0.129 0.0763

Page 42: Hi Essence Cable Spec

Doc: HEDoc: HEDoc: HEDoc: HE----SPECSPECSPECSPEC Rev: Rev: Rev: Rev: 4444 ((((02020202/201/201/201/2011111))))

42/67

HI-ESSENCE CABLE SDN. BHD. Factory address: Lot 13662, Kerteh Plastic Park, Kemaman, Terengganu.

Office address: No.2, Jalan Puteri 5/16, Bandar Puteri, 47100 Puchong, Selangor.

Tel:60-3-8061 3793 Fax:60-3-8061 2493 URL:http://www.he-cable.com

HE

TYPE P5::::TCU/MICA/EPR/EVA/SWB/EVA CABLE –FIVE CORES

0.6/1 (1.2) kV

Conductor Nominal

thickness

of

insulation

Approx.

thickness

of

inner

covering

Nominal

diameter

of

steel

wire

Nominal

thickness

of

outer

sheath

Approx.

overall

diameter

Approx.

cable

weight

Maximum

Conductor

Resistance

(at 20℃℃℃℃)

Current

rating(In

air at 40℃℃℃℃)

Nominal

cross-

sectional

area

No./dia.

of

wire

Approx.

outer

diameter

mm2 No./mm mm mm mm mm mm mm kg/km ΩΩΩΩ/km A

1.5 7/0.53 1.59 1.0 1.0 0.3 1.4 19.8 520 12.2 19

2.5 7/0.67 2.01 1.0 1.0 0.3 1.4 20.9 600 7.56 22

4 7/0.85 2.55 1.0 1.0 0.3 1.5 22.7 740 4.70 31

6 7/1.04 3.12 1.0 1.0 0.3 1.5 24.3 890 3.11 40

10 7/1.35 4.05 1.0 1.0 0.3 1.6 27.7 1205 1.84 53

16 7/1.70 5.10 1.0 1.0 0.3 1.7 30.6 1590 1.16 73

25 7/2.14 6.42 1.2 1.0 0.3 1.9 35.9 2275 0.734 99

35 7/2.52 7.56 1.2 1.2 0.3 2.0 39.7 2915 0.529 118

50 19/1.78 8.90 1.4 1.2 0.3 2.2 44.7 3770 0.391 143

70 19/2.14 10.70 1.4 1.4 0.3 2.4 50.3 5060 0.270 184

95 19/2.52 12.60 1.6 1.4 0.3 2.6 57.4 6750 0.195 226

Conductor

Size

Maximum

Conductor

Resistance

50Hz at 90℃℃℃℃

Reactance

(50Hz)

mm2 ΩΩΩΩ/km ΩΩΩΩ/km

1.5 15.56 0.13

2.5 9.64 0.12

4 5.99 0.111

6 3.97 0.104

10 2.34 0.096

16 1.48 0.091

25 0.936 0.089

35 0.675 0.084

50 0.499 0.084

70 0.345 0.08

95 0.25 0.079

Page 43: Hi Essence Cable Spec

Doc: HEDoc: HEDoc: HEDoc: HE----SPECSPECSPECSPEC Rev: Rev: Rev: Rev: 4444 ((((02020202/201/201/201/2011111))))

43/67

HI-ESSENCE CABLE SDN. BHD. Factory address: Lot 13662, Kerteh Plastic Park, Kemaman, Terengganu.

Office address: No.2, Jalan Puteri 5/16, Bandar Puteri, 47100 Puchong, Selangor.

Tel:60-3-8061 3793 Fax:60-3-8061 2493 URL:http://www.he-cable.com

HE

TYPE P5::::TCU/MICA/EPR/EVA/SWB/EVA CABLE –MULTI-CORES(1.5 mm2)

0.6/1 (1.2) kV

No.

of core

Conductor Nominal

thickness

of

insulation

Approx.

thickness

of

inner

covering

Nominal

diameter

of

steel

wire

Nominal

thickness

of

outer

sheath

Approx.

overall

diameter

Approx.

cable

weight

Maximum

Conductor

Resistance

ΩΩΩΩ/km

Current

rating(In

air at 40℃℃℃℃)

Nominal

cross-

sectional

area

No./dia.

of

wire

Approx.

outer

diameter

C mm2 No./mm mm mm mm mm mm mm kg/km 20℃℃℃℃ 90℃℃℃℃ A

6 1.5 7/0.53 1.59 1.0 1.0 0.3 1.4 21.3 595 12.2 15.56

17

7 1.5 7/0.53 1.59 1.0 1.0 0.3 1.4 21.3 620 16

8 1.5 7/0.53 1.59 1.0 1.0 0.3 1.5 23.2 720 15

9 1.5 7/0.53 1.59 1.0 1.0 0.3 1.6 24.9 810 15

10 1.5 7/0.53 1.59 1.0 1.0 0.3 1.6 26.8 890 14

11 1.5 7/0.53 1.59 1.0 1.0 0.3 1.6 26.8 930 14

12 1.5 7/0.53 1.59 1.0 1.0 0.3 1.6 27.6 965 13

13 1.5 7/0.53 1.59 1.0 1.0 0.3 1.7 29.0 1055 13

14 1.5 7/0.53 1.59 1.0 1.0 0.3 1.7 29.0 1085 13

15 1.5 7/0.53 1.59 1.0 1.0 0.3 1.7 30.4 1170 12

16 1.5 7/0.53 1.59 1.0 1.0 0.3 1.7 30.4 1195 12

17 1.5 7/0.53 1.59 1.0 1.0 0.3 1.8 32.1 1295 12

18 1.5 7/0.53 1.59 1.0 1.0 0.3 1.8 32.1 1325 12

19 1.5 7/0.53 1.59 1.0 1.0 0.3 1.8 32.1 1355 12

20 1.5 7/0.53 1.59 1.0 1.0 0.3 1.8 33.6 1445 11

21 1.5 7/0.53 1.59 1.0 1.0 0.3 1.8 33.6 1470 11

24 1.5 7/0.53 1.59 1.0 1.2 0.3 2.0 37.8 1750 10

27 1.5 7/0.53 1.59 1.0 1.2 0.3 2.0 38.6 1865 9

30 1.5 7/0.53 1.59 1.0 1.2 0.3 2.0 39.8 2010 8

37 1.5 7/0.53 1.59 1.0 1.2 0.3 2.1 42.9 2370 7

TYPE P5::::TCU/MICA/EPR/EVA/SWB/EVA CABLE –MULTI-CORES(2.5 mm2)

0.6/1 (1.2) kV

No.

of core

Conductor Nominal

thickness

of

insulation

Approx.

thickness

of

inner

covering

Nominal

diameter

of

steel

wire

Nominal

thickness

of

outer

sheath

Approx.

overall

diameter

Approx.

cable

weight

Maximum

Conductor

Resistance

ΩΩΩΩ/km

Current

rating(In

air at 40℃℃℃℃)

Nominal

cross-

sectional

area

No./dia.

of

wire

Approx.

outer

diameter

C mm2 No./mm mm mm mm mm mm mm kg/km 20℃℃℃℃ 90℃℃℃℃ A

6 2.5 7/0.67 2.01 1.0 1.0 0.3 1.5 22.9 715 7.56 9.64

20

7 2.5 7/0.67 2.01 1.0 1.0 0.3 1.5 22.9 750 19

8 2.5 7/0.67 2.01 1.0 1.0 0.3 1.6 24.7 850 18

9 2.5 7/0.67 2.01 1.0 1.0 0.3 1.6 26.3 945 17

10 2.5 7/0.67 2.01 1.0 1.0 0.3 1.7 28.6 1060 16

11 2.5 7/0.67 2.01 1.0 1.0 0.3 1.7 28.6 1110 15

12 2.5 7/0.67 2.01 1.0 1.0 0.3 1.7 29.4 1155 15

13 2.5 7/0.67 2.01 1.0 1.0 0.3 1.8 31.0 1265 15

14 2.5 7/0.67 2.01 1.0 1.0 0.3 1.8 31.0 1305 14

15 2.5 7/0.67 2.01 1.0 1.0 0.3 1.8 32.5 1400 14

16 2.5 7/0.67 2.01 1.0 1.0 0.3 1.8 32.5 1440 14

17 2.5 7/0.67 2.01 1.0 1.0 0.3 1.9 34.3 1560 13

18 2.5 7/0.67 2.01 1.0 1.0 0.3 1.9 34.3 1600 13

19 2.5 7/0.67 2.01 1.0 1.0 0.3 1.9 34.3 1635 13

20 2.5 7/0.67 2.01 1.0 1.0 0.3 1.9 35.9 1740 13

21 2.5 7/0.67 2.01 1.0 1.0 0.3 1.9 35.9 1780 12

24 2.5 7/0.67 2.01 1.0 1.2 0.3 2.1 40.4 2110 11

27 2.5 7/0.67 2.01 1.0 1.2 0.3 2.1 41.2 2255 10

Page 44: Hi Essence Cable Spec

Doc: HEDoc: HEDoc: HEDoc: HE----SPECSPECSPECSPEC Rev: Rev: Rev: Rev: 4444 ((((02020202/201/201/201/2011111))))

44/67

HI-ESSENCE CABLE SDN. BHD. Factory address: Lot 13662, Kerteh Plastic Park, Kemaman, Terengganu.

Office address: No.2, Jalan Puteri 5/16, Bandar Puteri, 47100 Puchong, Selangor.

Tel:60-3-8061 3793 Fax:60-3-8061 2493 URL:http://www.he-cable.com

HE

TYPE P5::::TCU/MICA/EPR/EVA/SWB/EVA CABLE –MULTI-CORES(4 mm2)

0.6/1 (1.2) kV

No.

of core

Conductor Nominal

thickness

of

insulation

Approx.

thickness

of

inner

covering

Nominal

diameter

of

steel

wire

Nominal

thickness

of

outer

sheath

Approx.

overall

diameter

Approx.

cable

weight

Maximum

Conductor

Resistance

ΩΩΩΩ/km

Current

rating(In

air at 40℃℃℃℃)

Nominal

cross-

sectional

area

No./dia.

of

wire

Approx.

outer

diameter

C mm2 No./mm mm mm mm mm mm mm kg/km 20℃℃℃℃ 90℃℃℃℃ A

6 4 7/0.85 2.55 1.0 1.0 0.3 1.6 24.6 865 4.70 5.99

28

7 4 7/0.85 2.55 1.0 1.0 0.3 1.6 24.6 915 26

8 4 7/0.85 2.55 1.0 1.0 0.3 1.6 26.2 1025 25

9 4 7/0.85 2.55 1.0 1.0 0.3 1.7 28.4 1165 23

10 4 7/0.85 2.55 1.0 1.0 0.3 1.8 30.8 1300 22

11 4 7/0.85 2.55 1.0 1.0 0.3 1.8 30.8 1370 22

12 4 7/0.85 2.55 1.0 1.0 0.3 1.8 31.7 1430 21

13 4 7/0.85 2.55 1.0 1.0 0.3 1.8 33.2 1545 21

14 4 7/0.85 2.55 1.0 1.0 0.3 1.8 33.2 1600 20

15 4 7/0.85 2.55 1.0 1.0 0.3 1.9 35.1 1745 20

16 4 7/0.85 2.55 1.0 1.0 0.3 1.9 35.1 1800 19

17 4 7/0.85 2.55 1.0 1.2 0.3 2.0 37.4 1980 19

18 4 7/0.85 2.55 1.0 1.2 0.3 2.0 37.4 2030 19

19 4 7/0.85 2.55 1.0 1.2 0.3 2.0 37.4 2085 18

20 4 7/0.85 2.55 1.0 1.2 0.3 2.0 39.2 2220 18

21 4 7/0.85 2.55 1.0 1.2 0.3 2.0 39.2 2275 17

24 4 7/0.85 2.55 1.0 1.2 0.3 2.2 43.6 2635 16

27 4 7/0.85 2.55 1.0 1.2 0.3 2.2 44.5 2835 14

Page 45: Hi Essence Cable Spec

Doc: HEDoc: HEDoc: HEDoc: HE----SPECSPECSPECSPEC Rev: Rev: Rev: Rev: 4444 ((((02020202/201/201/201/2011111))))

45/67

HI-ESSENCE CABLE SDN. BHD. Factory address: Lot 13662, Kerteh Plastic Park, Kemaman, Terengganu.

Office address: No.2, Jalan Puteri 5/16, Bandar Puteri, 47100 Puchong, Selangor.

Tel:60-3-8061 3793 Fax:60-3-8061 2493 URL:http://www.he-cable.com

HE

POLYETHYLENE INSULATED BRAIDED LSFH SHEATHED INDIVIDUAL AND

OVERALL SCREENED FLAME RETARDANT INSTRUMENT CABLE

TYPE I1 : CU/PE/IOSCR/PE/SWB/LSFH INSTRUMENT CABLE DESCRIPTION

Single pair and multi-pair cables with copper conductor, PE insulated, individual and overall screened, PE

bedding, galvanized steel wire braided and flame retardant low smoke free halogen compound outer sheath.

Cables are rated at 300/500 V

CONSTRUCTION

1 Conductor

Plain annealed circular solid copper conductor, conform to IEC 60228 or BS 6360 class 1.

2 Insulation

PE (polyethylene)

3 Pairing

Two insulated cores shall be uniformly twisted together to form a pair.

Each pair is screened with aluminium/mylar tape, helically applied with the metallic side down, in electrical

contact with a tinned annealed copper drain wire of 0.5 mm2.

4 Pair identification

Single pair - Black, white

Multi-pair - Printed numbers on black-white pair

5 Cabling

Twisted pairs are laid up together, if necessary filled with non-hygroscopic material compatible with the

insulation.

6 Screening

Accumulated pairs screened with aluminium/mylar tape, helically applied with the metallic side down, in

electrical contact with a tinned annealed copper drain wire of 0.5 mm2.

7 Bedding

PE compound, colour black.

8 Armour

Galvanized steel wires shall be braided over the PE bedding.

9 Outer sheath

Flame retardant low smoke free halogen compound, colour black. (Blue – IS) CABLE MARKING

manufacturer’s name, rated voltage, cable type, conductor size, manufacture year. SPECIFICATIONS

BS 5308

IEC 60332-3 Cat A

IEC 60754 (HCL emission 0.5% maximum by weight)

ASTM D 2863(Oxygen index greater than 30%)

Page 46: Hi Essence Cable Spec

Doc: HEDoc: HEDoc: HEDoc: HE----SPECSPECSPECSPEC Rev: Rev: Rev: Rev: 4444 ((((02020202/201/201/201/2011111))))

46/67

HI-ESSENCE CABLE SDN. BHD. Factory address: Lot 13662, Kerteh Plastic Park, Kemaman, Terengganu.

Office address: No.2, Jalan Puteri 5/16, Bandar Puteri, 47100 Puchong, Selangor.

Tel:60-3-8061 3793 Fax:60-3-8061 2493 URL:http://www.he-cable.com

HE

TYPE I1 : CU/PE/IOSCR/PE/SWB/LSFH INSTRUMENT CABLE

300/500 V

Number

of

pairs

Conductor Nominal

thickness

of

insulation

Nominal

thickness

of

bedding

Nominal

diameter

of

steel

wire

Nominal

thickness

of

outer

sheath

Approx.

overall

diameter

Approx.

cable

weight

Maximum

Conductor

Resistance

(at 20ºC)

Nominal

cross-

sectional

area

No./dia.

of

wire

Approx.

outer

diameter

P mm2 No./mm mm mm mm mm mm mm kg/km ΩΩΩΩ/km

2 1.0 1/1.13 1.13 0.6 1.1 0.3 1.5 15.8 315 18.4

3 1.0 1/1.13 1.13 0.6 1.1 0.3 1.5 16.5 355 18.4

4 1.0 1/1.13 1.13 0.6 1.2 0.3 1.5 17.9 415 18.4

5 1.0 1/1.13 1.13 0.6 1.2 0.3 1.6 19.4 470 18.4

6 1.0 1/1.13 1.13 0.6 1.2 0.3 1.6 20.7 535 18.4

7 1.0 1/1.13 1.13 0.6 1.2 0.3 1.6 20.7 555 18.4

8 1.0 1/1.13 1.13 0.6 1.3 0.3 1.7 22.5 635 18.4

9 1.0 1/1.13 1.13 0.6 1.3 0.3 1.7 23.8 700 18.4

10 1.0 1/1.13 1.13 0.6 1.3 0.3 1.8 25.8 785 18.4

11 1.0 1/1.13 1.13 0.6 1.3 0.3 1.8 25.8 815 18.4

12 1.0 1/1.13 1.13 0.6 1.3 0.3 1.8 26.4 840 18.4

13 1.0 1/1.13 1.13 0.6 1.3 0.3 1.8 27.6 910 18.4

14 1.0 1/1.13 1.13 0.6 1.3 0.3 1.8 27.6 930 18.4

15 1.0 1/1.13 1.13 0.6 1.5 0.3 1.9 29.5 1035 18.4

16 1.0 1/1.13 1.13 0.6 1.5 0.3 1.9 29.5 1060 18.4

17 1.0 1/1.13 1.13 0.6 1.5 0.3 1.9 30.8 1130 18.4

18 1.0 1/1.13 1.13 0.6 1.5 0.3 1.9 30.8 1150 18.4

19 1.0 1/1.13 1.13 0.6 1.5 0.3 1.9 30.8 1175 18.4

20 1.0 1/1.13 1.13 0.6 1.7 0.3 2.0 32.8 1290 18.4

21 1.0 1/1.13 1.13 0.6 1.7 0.3 2.0 32.8 1310 18.4

22 1.0 1/1.13 1.13 0.6 1.7 0.3 2.0 34.2 1390 18.4

23 1.0 1/1.13 1.13 0.6 1.7 0.3 2.0 34.2 1415 18.4

24 1.0 1/1.13 1.13 0.6 1.7 0.3 2.0 35.9 1485 18.4

Page 47: Hi Essence Cable Spec

Doc: HEDoc: HEDoc: HEDoc: HE----SPECSPECSPECSPEC Rev: Rev: Rev: Rev: 4444 ((((02020202/201/201/201/2011111))))

47/67

HI-ESSENCE CABLE SDN. BHD. Factory address: Lot 13662, Kerteh Plastic Park, Kemaman, Terengganu.

Office address: No.2, Jalan Puteri 5/16, Bandar Puteri, 47100 Puchong, Selangor.

Tel:60-3-8061 3793 Fax:60-3-8061 2493 URL:http://www.he-cable.com

HE

POLYETHYLENE INSULATED BRAIDED LSFH SHEATHED OVERALL SCREENED

FLAME RETARDANT INSTRUMENT CABLE

TYPE I2 : CU/PE/OSCR/PE/SWB/LSFH INSTRUMENT CABLE DESCRIPTION

Single pair and multi-pair cables with copper conductor, PE insulated, overall screened, PE bedding,

galvanized steel wire braided and flame retardant low smoke free halogen compound outer sheath.

Cables are rated at 300/500 V

CONSTRUCTION

1 Conductor

Plain annealed circular solid copper conductor, conform to IEC 60228 or BS 6360 class 1.

2 Insulation

PE (polyethylene)

3 Pairing

Two insulated cores shall be uniformly twisted together to form a pair.

Note: Two pair cables with overall screen shall have four cores laid in quad formation.

4 Pair identification

Single pair - Black, white

Multi-pair - Printed numbers on black-white pair

Note:Two Pairs - 1st pair:Black 1,White 1,2

nd pair:Black 2, White 2

5 Cabling

Twisted pairs are laid up together, if necessary filled with non-hygroscopic material compatible with the

insulation.

6 Screening

Accumulated pairs screened with aluminium/mylar tape, helically applied with the metallic side down, in

electrical contact with a tinned annealed copper drain wire of 0.5 mm2.

7 Bedding

PE compound, colour black.

8 Armour

Galvanized steel wires shall be braided over the PE bedding.

9 Outer sheath

Flame retardant low smoke free halogen compound, colour black. (Blue – IS) CABLE MARKING

Manufacturer’s name, rated voltage, cable type, conductor size, manufacture year. SPECIFICATIONS

BS 5308

IEC 60332-3 Cat A

IEC 60754 (HCL emission 0.5% maximum by weight)

ASTM D 2863(Oxygen index greater than 30%)

Page 48: Hi Essence Cable Spec

Doc: HEDoc: HEDoc: HEDoc: HE----SPECSPECSPECSPEC Rev: Rev: Rev: Rev: 4444 ((((02020202/201/201/201/2011111))))

48/67

HI-ESSENCE CABLE SDN. BHD. Factory address: Lot 13662, Kerteh Plastic Park, Kemaman, Terengganu.

Office address: No.2, Jalan Puteri 5/16, Bandar Puteri, 47100 Puchong, Selangor.

Tel:60-3-8061 3793 Fax:60-3-8061 2493 URL:http://www.he-cable.com

HE

TYPE I2 : CU/PE/OSCR/PE/SWB/LSFH INSTRUMENT CABLE

300/500 V

Number

of

pairs

Conductor Nominal

thickness

of

insulation

Nominal

thickness

of

bedding

Nominal

diameter

of

steel

wire

Nominal

thickness

of

outer

sheath

Approx.

overall

diameter

Approx.

cable

weight

Maximum

Conductor

Resistance

(at 20ºC)

Nominal

cross-

sectional

area

No./dia.

of

wire

Approx.

outer

diameter

P mm2 No./mm mm mm mm mm mm mm kg/km ΩΩΩΩ/km

1 1.0 1/1.13 1.13 0.6 0.8 0.3 1.3 10.5 160 18.4

2 1.0 1/1.13 1.13 0.6 0.8 0.3 1.4 13.9 250 18.4

3 1.0 1/1.13 1.13 0.6 1.1 0.3 1.4 15.1 300 18.4

4 1.0 1/1.13 1.13 0.6 1.1 0.3 1.5 16.3 355 18.4

5 1.0 1/1.13 1.13 0.6 1.2 0.3 1.5 17.7 400 18.4

6 1.0 1/1.13 1.13 0.6 1.2 0.3 1.6 19.0 455 18.4

7 1.0 1/1.13 1.13 0.6 1.2 0.3 1.6 19.0 475 18.4

8 1.0 1/1.13 1.13 0.6 1.2 0.3 1.6 20.0 520 18.4

9 1.0 1/1.13 1.13 0.6 1.2 0.3 1.7 21.3 580 18.4

10 1.0 1/1.13 1.13 0.6 1.2 0.3 1.7 22.2 625 18.4

11 1.0 1/1.13 1.13 0.6 1.2 0.3 1.7 22.2 650 18.4

12 1.0 1/1.13 1.13 0.6 1.3 0.3 1.7 23.2 685 18.4

13 1.0 1/1.13 1.13 0.6 1.3 0.3 1.7 23.9 730 18.4

14 1.0 1/1.13 1.13 0.6 1.3 0.3 1.7 24.5 765 18.4

15 1.0 1/1.13 1.13 0.6 1.3 0.3 1.8 25.3 820 18.4

16 1.0 1/1.13 1.13 0.6 1.3 0.3 1.8 25.8 850 18.4

17 1.0 1/1.13 1.13 0.6 1.3 0.3 1.8 26.4 890 18.4

18 1.0 1/1.13 1.13 0.6 1.3 0.3 1.8 26.9 920 18.4

19 1.0 1/1.13 1.13 0.6 1.3 0.3 1.8 27.4 950 18.4

20 1.0 1/1.13 1.13 0.6 1.5 0.3 1.8 28.4 1005 18.4

21 1.0 1/1.13 1.13 0.6 1.5 0.3 1.8 28.9 1045 18.4

22 1.0 1/1.13 1.13 0.6 1.5 0.3 1.8 29.3 1090 18.4

23 1.0 1/1.13 1.13 0.6 1.5 0.3 1.8 29.8 1120 18.4

24 1.0 1/1.13 1.13 0.6 1.5 0.3 1.8 30.3 1155 18.4

Page 49: Hi Essence Cable Spec

Doc: HEDoc: HEDoc: HEDoc: HE----SPECSPECSPECSPEC Rev: Rev: Rev: Rev: 4444 ((((02020202/201/201/201/2011111))))

49/67

HI-ESSENCE CABLE SDN. BHD. Factory address: Lot 13662, Kerteh Plastic Park, Kemaman, Terengganu.

Office address: No.2, Jalan Puteri 5/16, Bandar Puteri, 47100 Puchong, Selangor.

Tel:60-3-8061 3793 Fax:60-3-8061 2493 URL:http://www.he-cable.com

HE

POLYETHYLENE INSULATED BRAIDED LSFH SHEATHED INDIVIDUAL AND

OVERALL SCREENED FLAME RETARDANT INSTRUMENT CABLE

TYPE I3 : CU/PE/IOSCR/PE/SWB/LSFH INSTRUMENT CABLE DESCRIPTION

Single triad and multi-triad cables with copper conductor, PE insulated, individual and overall screened, PE

bedding, galvanized steel wire braided and flame retardant low smoke free halogen compound outer sheath.

Cables are rated at 300/500 V

CONSTRUCTION

1 Conductor

Plain annealed circular solid copper conductor, conform to IEC 60228 or BS 6360 class 1.

2 Insulation

PE (polyethylene)

3 Tripling

Three insulated cores shall be uniformly twisted together to form a triad.

Each triad is screened with aluminium/mylar tape, helically applied with the metallic side down, in electrical

contact with a tinned annealed copper drain wire of 0.5 mm2.

4 Triad identification

Single triad - Black, white, red

Multi-triad - Printed numbers on black-white-red triad

5 Cabling

Twisted triads are laid up together, if necessary filled with non-hygroscopic material compatible with the

insulation.

6 Screening

Accumulated triads screened with aluminium/mylar tape, helically applied with the metallic side down, in

electrical contact with a tinned annealed copper drain wire of 0.5 mm2.

7 Bedding

PE compound, colour black.

8 Armour

Galvanized steel wires shall be braided over the PE bedding.

9 Outer sheath

Flame retardant low smoke free halogen compound, colour black. (Blue – IS) CABLE MARKING

Manufacturer’s name, rated voltage, cable type, conductor size, manufacture year.

SPECIFICATIONS

BS 5308

IEC 60332-3 Cat A

IEC 60754 (HCL emission 0.5% maximum by weight)

ASTM D 2863(Oxygen index greater than 30%)

Page 50: Hi Essence Cable Spec

Doc: HEDoc: HEDoc: HEDoc: HE----SPECSPECSPECSPEC Rev: Rev: Rev: Rev: 4444 ((((02020202/201/201/201/2011111))))

50/67

HI-ESSENCE CABLE SDN. BHD. Factory address: Lot 13662, Kerteh Plastic Park, Kemaman, Terengganu.

Office address: No.2, Jalan Puteri 5/16, Bandar Puteri, 47100 Puchong, Selangor.

Tel:60-3-8061 3793 Fax:60-3-8061 2493 URL:http://www.he-cable.com

HE

TYPE I3 : CU/PE/IOSCR/PE/SWB/LSFH INSTRUMENT CABLE

300/500 V

Number

of

triads

Conductor Nominal

thickness

of

insulation

Nominal

thickness

of

bedding

Nominal

diameter

of

steel

wire

Nominal

thickness

of

outer

sheath

Approx.

overall

diameter

Approx.

cable

weight

Maximum

Conductor

Resistance

(at 20ºC)

Nominal

cross-

sectional

area

No./dia.

of

wire

Approx.

outer

diameter

T mm2 No./mm mm mm mm mm mm mm kg/km ΩΩΩΩ/km

2 1.0 1/1.13 1.13 0.6 1.2 0.3 1.5 16.8 365 18.4

3 1.0 1/1.13 1.13 0.6 1.2 0.3 1.5 17.5 415 18.4

4 1.0 1/1.13 1.13 0.6 1.2 0.3 1.6 19.0 495 18.4

5 1.0 1/1.13 1.13 0.6 1.2 0.3 1.6 20.4 555 18.4

6 1.0 1/1.13 1.13 0.6 1.3 0.3 1.7 22.2 650 18.4

7 1.0 1/1.13 1.13 0.6 1.3 0.3 1.7 22.2 680 18.4

8 1.0 1/1.13 1.13 0.6 1.3 0.3 1.7 23.7 760 18.4

9 1.0 1/1.13 1.13 0.6 1.4 0.3 1.8 25.6 865 18.4

10 1.0 1/1.13 1.13 0.6 1.4 0.3 1.8 27.4 945 18.4

11 1.0 1/1.13 1.13 0.6 1.4 0.3 1.8 27.4 990 18. 4

12 1.0 1/1.13 1.13 0.6 1.5 0.3 1.9 28.6 1055 18.4

Page 51: Hi Essence Cable Spec

Doc: HEDoc: HEDoc: HEDoc: HE----SPECSPECSPECSPEC Rev: Rev: Rev: Rev: 4444 ((((02020202/201/201/201/2011111))))

51/67

HI-ESSENCE CABLE SDN. BHD. Factory address: Lot 13662, Kerteh Plastic Park, Kemaman, Terengganu.

Office address: No.2, Jalan Puteri 5/16, Bandar Puteri, 47100 Puchong, Selangor.

Tel:60-3-8061 3793 Fax:60-3-8061 2493 URL:http://www.he-cable.com

HE

POLYETHYLENE INSULATED BRAIDED LSFH SHEATHED OVERALL SCREENED

FLAME RETARDANT INSTRUMENT CABLE

TYPE I4 : CU/PE/OSCR/PE/SWB/LSFH INSTRUMENT CABLE DESCRIPTION

Single triad and multi-triad cables with copper conductor, PE insulated, overall screened, PE bedding,

galvanized steel wire braided and flame retardant low smoke free halogen compound outer sheath.

Cables are rated at 300/500 V

CONSTRUCTION

1 Conductor

Plain annealed circular solid copper conductor, conform to IEC 60228 or BS 6360 class 1.

2 Insulation

PE (polyethylene)

3 Tripling

Three insulated cores shall be uniformly twisted together to form a triad.

4 Triad identification

Single triad - Black, white, red

Multi-triad - Printed numbers on black-white-red triad

5 Cabling

Twisted triads are laid up together, if necessary filled with non-hygroscopic material compatible with the

insulation.

6 Screening

Accumulated triads screened with aluminium/mylar tape, helically applied with the metallic side down, in

electrical contact with a tinned annealed copper drain wire of 0.5 mm2.

7 Bedding

PE compound, colour black.

8 Armour

Galvanized steel wires shall be braided over the PE bedding.

9 Outer sheath

Flame retardant low smoke free halogen compound, colour black. (Blue – IS) CABLE MARKING

manufacturer’s name, rated voltage, cable type, conductor size, manufacture year. SPECIFICATIONS

BS 5308

IEC 60332-3 Cat A

IEC 60754 (HCL emission 0.5% maximum by weight)

ASTM D 2863(Oxygen index greater than 30%)

Page 52: Hi Essence Cable Spec

Doc: HEDoc: HEDoc: HEDoc: HE----SPECSPECSPECSPEC Rev: Rev: Rev: Rev: 4444 ((((02020202/201/201/201/2011111))))

52/67

HI-ESSENCE CABLE SDN. BHD. Factory address: Lot 13662, Kerteh Plastic Park, Kemaman, Terengganu.

Office address: No.2, Jalan Puteri 5/16, Bandar Puteri, 47100 Puchong, Selangor.

Tel:60-3-8061 3793 Fax:60-3-8061 2493 URL:http://www.he-cable.com

HE

TYPE I4 : CU/PE/OSCR/PE/SWB/LSFH INSTRUMENT CABLE

300/500 V

Number

of

triads

Conductor Nominal

thickness

of

insulation

Nominal

thickness

of

bedding

Nominal

diameter

of

steel

wire

Nominal

thickness

of

outer

sheath

Approx.

overall

diameter

Approx.

cable

weight

Maximum

Conductor

Resistance

(at 20ºC)

Nominal

cross-

sectional

area

No./dia.

of

wire

Approx.

outer

diameter

T mm2 No./mm mm mm mm mm mm mm kg/km ΩΩΩΩ/km

1 1.0 1/1.13 1.13 0.6 0.8 0.3 1.4 11.1 185 18.4

2 1.0 1/1.13 1.13 0.6 1.1 0.3 1.5 15.5 320 18.4

3 1.0 1/1.13 1.13 0.6 1.2 0.3 1.5 16.5 375 18.4

4 1.0 1/1.13 1.13 0.6 1.2 0.3 1.5 17.7 435 18.4

5 1.0 1/1.13 1.13 0.6 1.2 0.3 1.6 19.3 495 18.4

6 1.0 1/1.13 1.13 0.6 1.2 0.3 1.6 21.1 575 18.4

7 1.0 1/1.13 1.13 0.6 1.2 0.3 1.6 21.1 600 18.4

8 1.0 1/1.13 1.13 0.6 1.3 0.3 1.7 22.7 685 18.4

9 1.0 1/1.13 1.13 0.6 1.3 0.3 1.8 24.0 760 18.4

10 1.0 1/1.13 1.13 0.6 1.4 0.3 1.8 25.4 830 18.4

11 1.0 1/1.13 1.13 0.6 1.4 0.3 1.8 25.4 870 18.4

12 1.0 1/1.13 1.13 0.6 1.4 0.3 1.8 26.0 900 18.4

13 1.0 1/1.13 1.13 0.6 1.4 0.3 1.9 27.0 980 18.4

14 1.0 1/1.13 1.13 0.6 1.4 0.3 1.9 27.7 1020 18.4

15 1.0 1/1.13 1.13 0.6 1.5 0.3 1.9 28.5 1090 18.4

Page 53: Hi Essence Cable Spec

Doc: HEDoc: HEDoc: HEDoc: HE----SPECSPECSPECSPEC Rev: Rev: Rev: Rev: 4444 ((((02020202/201/201/201/2011111))))

53/67

HI-ESSENCE CABLE SDN. BHD. Factory address: Lot 13662, Kerteh Plastic Park, Kemaman, Terengganu.

Office address: No.2, Jalan Puteri 5/16, Bandar Puteri, 47100 Puchong, Selangor.

Tel:60-3-8061 3793 Fax:60-3-8061 2493 URL:http://www.he-cable.com

HE

ETHYLENE PROPYLENE RUBBER INSULATED BRAIDED EVA SHEATHED

INDIVIDUAL AND OVERALL SCREENED FIRE RESISTANT AND FLAME

RETARDANT INSTRUMENT CABLE

TYPE F1 : CU/MICA/EPR/IOSCR/EVA/SWB/EVA INSTRUMENT CABLE DESCRIPTION

Single pair and multi-pair cables with copper conductor, mica tape, EPR insulated, individual and overall

screened, flame retardant low smoke free halogen compound EVA inner covering, galvanized steel wire

braided and flame retardant low smoke free halogen compound EVA outer sheath.

Cables are rated at 150/250 V (300 V).

CONSTRUCTION

1 Conductor

Plain annealed circular stranded copper conductor, conform to IEC 60228 class 2.

2 Fire proof layer

Mica tape.

3 Insulation

EPR (Ethylene propylene rubber)

4 Pairing

Two insulated cores shall be uniformly twisted together to form a pair.

Each pair is screened with aluminium/mylar tape, helically applied with the metallic side down, in electrical

contact with a tinned annealed copper drain wire of 0.75 mm2.

5 Pair identification

Single pair - Red, white

Multi-pair - Printed numbers on red-white pair

6 Cabling

Twisted pairs are laid up together, if necessary filled with non-hygroscopic material compatible with the

insulation.

7 Screening

Accumulated pairs screened with aluminium/mylar tape, helically applied with the metallic side down, in

electrical contact with a tinned annealed copper drain wire of 0.75 mm2.

8 Inner covering

Flame retardant low smoke free halogen compound EVA, colour black.

9 Armour

Galvanized steel wires shall be braided over the EVA inner covering.

10 Outer sheath

Flame retardant low smoke free halogen compound EVA, colour black. (Blue – IS) CABLE MARKING

manufacturer’s name, rated voltage, cable type, conductor size, manufacture year. SPECIFICATIONS

IEC 60092, IEC 60092-376

IEC 60331, IEC 60332-3 Cat A

IEC 60754 (HCL emission 0.5% maximum by weight)

ASTM D 2863(Oxygen index greater than 30%)

Page 54: Hi Essence Cable Spec

Doc: HEDoc: HEDoc: HEDoc: HE----SPECSPECSPECSPEC Rev: Rev: Rev: Rev: 4444 ((((02020202/201/201/201/2011111))))

54/67

HI-ESSENCE CABLE SDN. BHD. Factory address: Lot 13662, Kerteh Plastic Park, Kemaman, Terengganu.

Office address: No.2, Jalan Puteri 5/16, Bandar Puteri, 47100 Puchong, Selangor.

Tel:60-3-8061 3793 Fax:60-3-8061 2493 URL:http://www.he-cable.com

HE

TYPE F1 : CU/MICA/EPR/IOSCR/EVA/SWB/EVA INSTRUMENT CABLE

150/250 V (300 V)

Number

of

pairs

Conductor Nominal

thickness

of

insulation

Approx.

thickness

of

inner

covering

Nominal

diameter

of

steel

wire

Nominal

thickness

of

outer

sheath

Approx.

overall

diameter

Approx.

cable

weight

Maximum

Conductor

Resistance

(at 20ºC)

Nominal

cross-

sectional

area

No./dia.

of

wire

Approx.

outer

diameter

P mm2 No./mm mm mm mm mm mm mm kg/km ΩΩΩΩ/km

2 1.5 7/0.53 1.59 0.7 1.0 0.3 1.4 23.1 605 12.9

3 1.5 7/0.53 1.59 0.7 1.0 0.3 1.4 24.3 690 12.9

4 1.5 7/0.53 1.59 0.7 1.0 0.3 1.5 26.9 845 12.9

5 1.5 7/0.53 1.59 0.7 1.0 0.3 1.6 29.4 950 12.9

6 1.5 7/0.53 1.59 0.7 1.0 0.3 1.6 31.9 1095 12.9

7 1.5 7/0.53 1.59 0.7 1.0 0.3 1.6 31.9 1135 12.9

8 1.5 7/0.53 1.59 0.7 1.0 0.3 1.7 34.5 1300 12.9

9 1.5 7/0.53 1.59 0.7 1.0 0.3 1.8 37.3 1475 12.9

10 1.5 7/0.53 1.59 0.7 1.0 0.3 1.9 40.6 1650 12.9

11 1.5 7/0.53 1.59 0.7 1.0 0.3 1.9 40.6 1725 12.9

12 1.5 7/0.53 1.59 0.7 1.0 0.3 1.9 41.9 1775 12.9

13 1.5 7/0.53 1.59 0.7 1.2 0.3 2.0 44.6 2000 12.9

14 1.5 7/0.53 1.59 0.7 1.2 0.3 2.0 44.6 2050 12.9

15 1.5 7/0.53 1.59 0.7 1.2 0.3 2.0 47.0 2220 12.9

16 1.5 7/0.53 1.59 0.7 1.2 0.3 2.0 47.0 2270 12.9

17 1.5 7/0.53 1.59 0.7 1.2 0.3 2.1 49.6 2465 12.9

18 1.5 7/0.53 1.59 0.7 1.2 0.3 2.1 49.6 2515 12.9

19 1.5 7/0.53 1.59 0.7 1.2 0.3 2.1 49.6 2560 12.9

20 1.5 7/0.53 1.59 0.7 1.2 0.3 2.2 52.3 2770 12.9

Page 55: Hi Essence Cable Spec

Doc: HEDoc: HEDoc: HEDoc: HE----SPECSPECSPECSPEC Rev: Rev: Rev: Rev: 4444 ((((02020202/201/201/201/2011111))))

55/67

HI-ESSENCE CABLE SDN. BHD. Factory address: Lot 13662, Kerteh Plastic Park, Kemaman, Terengganu.

Office address: No.2, Jalan Puteri 5/16, Bandar Puteri, 47100 Puchong, Selangor.

Tel:60-3-8061 3793 Fax:60-3-8061 2493 URL:http://www.he-cable.com

HE

ETHYLENE PROPYLENE RUBBER INSULATED BRAIDED EVA SHEATHED

OVERALL SCREENED FIRE RESISTANT AND FLAME RETARDANT INSTRUMENT

CABLE

TYPE F2 : CU/MICA/EPR/OSCR/EVA/SWB/EVA INSTRUMENT CABLE DESCRIPTION

Single pair and multi-pair cables with copper conductor, mica tape, EPR insulated, overall screened, flame

retardant low smoke free halogen compound EVA inner covering, galvanized steel wire braided and flame

retardant low smoke free halogen compound EVA outer sheath.

Cables are rated at 150/250 V (300 V).

CONSTRUCTION

1 Conductor

Plain annealed circular stranded copper conductor, conform to IEC 60228 class 2.

2 Fire proof layer

Mica tape.

3 Insulation

EPR (Ethylene propylene rubber)

4 Pairing

Two insulated cores shall be uniformly twisted together to form a pair.

Note: Two pair cables with overall screen shall have four cores laid in quad formation.

5 Pair identification

Single pair - Red, white

Multi-pair - Printed numbers on red-white pair

Note:Two Pairs - 1st pair: Red 1,White 1; 2

nd pair: Red 2, White 2

6 Cabling

Twisted pairs are laid up together, if necessary filled with non-hygroscopic material compatible with the

insulation.

7 Screening

Accumulated pairs screened with aluminium/mylar tape, helically applied with the metallic side down, in

electrical contact with a tinned annealed copper drain wire of 0.75 mm2.

8 Inner covering

Flame retardant low smoke free halogen compound EVA, colour black.

9 Armour

Galvanized steel wires shall be braided over the EVA inner covering.

10 Outer sheath

Flame retardant low smoke free halogen compound EVA, colour black. (Blue – IS) CABLE MARKING

Manufacturer’s name, rated voltage, cable type, conductor size, manufacture year. SPECIFICATIONS

IEC 60092, IEC 60092-376

IEC 60331, IEC 60332-3 Cat A

IEC 60754 (HCL emission 0.5% maximum by weight)

ASTM D 2863(Oxygen index greater than 30%)

Page 56: Hi Essence Cable Spec

Doc: HEDoc: HEDoc: HEDoc: HE----SPECSPECSPECSPEC Rev: Rev: Rev: Rev: 4444 ((((02020202/201/201/201/2011111))))

56/67

HI-ESSENCE CABLE SDN. BHD. Factory address: Lot 13662, Kerteh Plastic Park, Kemaman, Terengganu.

Office address: No.2, Jalan Puteri 5/16, Bandar Puteri, 47100 Puchong, Selangor.

Tel:60-3-8061 3793 Fax:60-3-8061 2493 URL:http://www.he-cable.com

HE

TYPE F2 : CU/MICA/EPR/OSCR/EVA/SWB/EVA INSTRUMENT CABLE

150/250 V (300 V)

Number

of

pairs

Conductor Nominal

thickness

of

insulation

Approx.

thickness

of

inner

covering

Nominal

diameter

of

steel

wire

Nominal

thickness

of

outer

sheath

Approx.

overall

diameter

Approx.

cable

weight

Maximum

Conductor

Resistance

(at 20ºC)

Nominal

cross-

sectional

area

No./dia.

of

wire

Approx.

outer

diameter

P mm2 No./mm mm mm mm mm mm mm kg/km ΩΩΩΩ/km

1 1.5 7/0.53 1.59 0.7 1.0 0.3 1.2 14.9 310 12.9

2 1.5 7/0.53 1.59 0.7 1.0 0.3 1.4 17.1 425 12.9

3 1.5 7/0.53 1.59 0.7 1.0 0.3 1.4 22.4 615 12.9

4 1.5 7/0.53 1.59 0.7 1.0 0.3 1.4 24.3 720 12.9

5 1.5 7/0.53 1.59 0.7 1.0 0.3 1.5 26.9 830 12.9

6 1.5 7/0.53 1.59 0.7 1.0 0.3 1.6 29.2 965 12.9

7 1.5 7/0.53 1.59 0.7 1.0 0.3 1.6 29.2 1005 12.9

8 1.5 7/0.53 1.59 0.7 1.0 0.3 1.7 31.2 1135 12.9

9 1.5 7/0.53 1.59 0.7 1.0 0.3 1.7 33.3 1265 12.9

10 1.5 7/0.53 1.59 0.7 1.0 0.3 1.8 35.2 1390 12.9

11 1.5 7/0.53 1.59 0.7 1.0 0.3 1.8 35.2 1455 12.9

12 1.5 7/0.53 1.59 0.7 1.0 0.3 1.8 36.7 1515 12.9

13 1.5 7/0.53 1.59 0.7 1.0 0.3 1.9 38.1 1650 12.9

14 1.5 7/0.53 1.59 0.7 1.0 0.3 1.9 39.3 1725 12.9

15 1.5 7/0.53 1.59 0.7 1.0 0.3 1.9 40.4 1840 12.9

16 1.5 7/0.53 1.59 0.7 1.0 0.3 1.9 41.4 1910 12.9

17 1.5 7/0.53 1.59 0.7 1.2 0.3 2.0 43.1 2090 12.9

18 1.5 7/0.53 1.59 0.7 1.2 0.3 2.0 44.1 2160 12.9

19 1.5 7/0.53 1.59 0.7 1.2 0.3 2.0 45.0 2225 12.9

20 1.5 7/0.53 1.59 0.7 1.2 0.3 2.1 46.2 2335 12.9

Page 57: Hi Essence Cable Spec

Doc: HEDoc: HEDoc: HEDoc: HE----SPECSPECSPECSPEC Rev: Rev: Rev: Rev: 4444 ((((02020202/201/201/201/2011111))))

57/67

HI-ESSENCE CABLE SDN. BHD. Factory address: Lot 13662, Kerteh Plastic Park, Kemaman, Terengganu.

Office address: No.2, Jalan Puteri 5/16, Bandar Puteri, 47100 Puchong, Selangor.

Tel:60-3-8061 3793 Fax:60-3-8061 2493 URL:http://www.he-cable.com

HE

ETHYLENE PROPYLENE RUBBER INSULATED BRAIDED EVA SHEATHED

INDIVIDUAL AND OVERALL SCREENED FIRE RESISTANT AND FLAME

RETARDANT INSTRUMENT CABLE

TYPE F3 : CU/MICA/EPR/IOSCR/EVA/SWB/EVA INSTRUMENT CABLE DESCRIPTION

Single triad and multi-triad cables with copper conductor, mica tape, EPR insulated, individual and overall

screened, flame retardant low smoke free halogen compound EVA inner covering, galvanized steel wire

braided and flame retardant low smoke free halogen compound EVA outer sheath.

Cables are rated at 150/250 V (300 V).

CONSTRUCTION

1 Conductor

Plain annealed circular stranded copper conductor, conform to IEC 60228 class 2.

2 Fire proof layer

Mica tape.

3 Insulation

EPR (Ethylene propylene rubber)

4 Tripling

Three insulated cores shall be uniformly twisted together to form a triad.

Each triad is screened with aluminium/mylar tape, helically applied with the metallic side down, in electrical

contact with a tinned annealed copper drain wire of 0.75 mm2.

5 Triad identification

Single triad - Red, white, black

Multi-triad - Printed numbers on red-white-black triad

6 Cabling

Twisted triads are laid up together, if necessary filled with non-hygroscopic material compatible with the

insulation.

7 Screening

Accumulated triads screened with aluminium/mylar tape, helically applied with the metallic side down, in

electrical contact with a tinned annealed copper drain wire of 0.75 mm2.

8 Inner covering

Flame retardant low smoke free halogen compound EVA, colour black.

9 Armour

Galvanized steel wires shall be braided over the EVA inner covering.

10 Outer sheath

Flame retardant low smoke free halogen compound EVA, colour black. (Blue – IS) CABLE MARKING

manufacturer’s name, rated voltage, cable type, conductor size, manufacture year. SPECIFICATIONS

IEC 60092, IEC 60092-376

IEC 60331, IEC 60332-3 Cat A

IEC 60754 (HCL emission 0.5%maximum by weight)

ASTM D 2863(Oxygen index greater than 30%)

Page 58: Hi Essence Cable Spec

Doc: HEDoc: HEDoc: HEDoc: HE----SPECSPECSPECSPEC Rev: Rev: Rev: Rev: 4444 ((((02020202/201/201/201/2011111))))

58/67

HI-ESSENCE CABLE SDN. BHD. Factory address: Lot 13662, Kerteh Plastic Park, Kemaman, Terengganu.

Office address: No.2, Jalan Puteri 5/16, Bandar Puteri, 47100 Puchong, Selangor.

Tel:60-3-8061 3793 Fax:60-3-8061 2493 URL:http://www.he-cable.com

HE

TYPE F3 : CU/MICA/EPR/IOSCR/EVA/SWB/EVA INSTRUMENT CABLE

150/250 V (300 V)

Number

of

triads

Conductor Nominal

thickness

of

insulation

Approx.

thickness

of

inner

covering

Nominal

diameter

of

steel

wire

Nominal

thickness

of

outer

sheath

Approx.

overall

diameter

Approx.

cable

weight

Maximum

Conductor

Resistance

(at 20ºC)

Nominal

cross-

sectional

area

No./dia.

of

wire

Approx.

outer

diameter

T mm2 No./mm mm mm mm mm mm mm kg/km ΩΩΩΩ/km

2 1.5 7/0.53 1.59 0.7 1.0 0.3 1.5 24.8 730 12.9

3 1.5 7/0.53 1.59 0.7 1.0 0.3 1.5 26.1 850 12.9

4 1.5 7/0.53 1.59 0.7 1.0 0.3 1.6 28.6 1030 12.9

5 1.5 7/0.53 1.59 0.7 1.0 0.3 1.6 31.2 1160 12.9

6 1.5 7/0.53 1.59 0.7 1.0 0.3 1.7 34.0 1360 12.9

7 1.5 7/0.53 1.59 0.7 1.0 0.3 1.7 34.0 1425 12.9

8 1.5 7/0.53 1.59 0.7 1.0 0.3 1.8 36.9 1635 12.9

9 1.5 7/0.53 1.59 0.7 1.0 0.3 1.9 39.8 1850 12.9

10 1.5 7/0.53 1.59 0.7 1.2 0.3 2.0 43.8 2115 12.9

11 1.5 7/0.53 1.59 0.7 1.2 0.3 2.0 43.8 2225 12.9

12 1.5 7/0.53 1.59 0.7 1.2 0.3 2.0 45.2 2300 12.9

Page 59: Hi Essence Cable Spec

Doc: HEDoc: HEDoc: HEDoc: HE----SPECSPECSPECSPEC Rev: Rev: Rev: Rev: 4444 ((((02020202/201/201/201/2011111))))

59/67

HI-ESSENCE CABLE SDN. BHD. Factory address: Lot 13662, Kerteh Plastic Park, Kemaman, Terengganu.

Office address: No.2, Jalan Puteri 5/16, Bandar Puteri, 47100 Puchong, Selangor.

Tel:60-3-8061 3793 Fax:60-3-8061 2493 URL:http://www.he-cable.com

HE

ETHYLENE PROPYLENE RUBBER INSULATED BRAIDED EVA SHEATHED

OVERALL SCREENED FIRE RESISTANT AND FLAME RETARDANT INSTRUMENT

CABLE

TYPE F4 : CU/MICA/EPR/OSCR/EVA/SWB/EVA INSTRUMENT CABLE DESCRIPTION

Single triad and multi-triad cables with copper conductor, mica tape, EPR insulated, overall screened, flame

retardant low smoke free halogen compound EVA inner covering, galvanized steel wire braided and flame

retardant low smoke free halogen compound EVA outer sheath.

Cables are rated at 150/250 V (300 V).

CONSTRUCTION

1 Conductor

Plain annealed circular stranded copper conductor, conform to IEC 60228 class 2.

2 Fire proof layer

Mica tape.

3 Insulation

EPR (Ethylene propylene rubber)

4 Tripling

Three insulated cores shall be uniformly twisted together to form a triad.

5 Triad identification

Single triad - Red, white, black

Multi-triad - Printed numbers on red-white-black triad

6 Cabling

Twisted triads are laid up together, if necessary filled with non-hygroscopic material compatible with the

insulation.

7 Screening

Accumulated triads screened with aluminium/mylar tape, helically applied with the metallic side down, in

electrical contact with a tinned annealed copper drain wire of 0.75 mm2.

8 Inner covering

Flame retardant low smoke free halogen compound EVA, colour black.

9 Armour

Galvanized steel wires shall be braided over the EVA inner covering.

10 Outer sheath

Flame retardant low smoke free halogen compound EVA, colour black. (Blue – IS) CABLE MARKING

manufacturer’s name, rated voltage, cable type, conductor size, manufacture year. SPECIFICATIONS

IEC 60092, IEC 60092-376

IEC 60331, IEC 60332-3 Cat A

IEC 60754 (HCL emission 0.5% maximum by weight)

ASTM D 2863(Oxygen index greater than 30%)

Page 60: Hi Essence Cable Spec

Doc: HEDoc: HEDoc: HEDoc: HE----SPECSPECSPECSPEC Rev: Rev: Rev: Rev: 4444 ((((02020202/201/201/201/2011111))))

60/67

HI-ESSENCE CABLE SDN. BHD. Factory address: Lot 13662, Kerteh Plastic Park, Kemaman, Terengganu.

Office address: No.2, Jalan Puteri 5/16, Bandar Puteri, 47100 Puchong, Selangor.

Tel:60-3-8061 3793 Fax:60-3-8061 2493 URL:http://www.he-cable.com

HE

TYPE F4 : CU/MICA/EPR/OSCR/EVA/SWB/EVA INSTRUMENT CABLE

150/250 V (300 V)

Number

of

triads

Conductor Nominal

thickness

of

insulation

Approx.

thickness

of

inner

covering

Nominal

diameter

of

steel

wire

Nominal

thickness

of

outer

sheath

Approx.

overall

diameter

Approx.

cable

weight

Maximum

Conductor

Resistance

(at 20ºC)

Nominal

cross-

sectional

area

No./dia.

of

wire

Approx.

outer

diameter

T mm2 No./mm mm mm Mm mm mm mm kg/km ΩΩΩΩ/km

1 1.5 7/0.53 1.59 0.7 1.0 0.3 1.2 15.6 355 12.9

2 1.5 7/0.53 1.59 0.7 1.0 0.3 1.4 22.9 645 12.9

3 1.5 7/0.53 1.59 0.7 1.0 0.3 1.5 24.7 780 12.9

4 1.5 7/0.53 1.59 0.7 1.0 0.3 1.5 26.9 930 12.9

5 1.5 7/0.53 1.59 0.7 1.0 0.3 1.6 29.7 1065 12.9

6 1.5 7/0.53 1.59 0.7 1.0 0.3 1.7 33.3 1275 12.9

7 1.5 7/0.53 1.59 0.7 1.0 0.3 1.7 33.3 1330 12.9

8 1.5 7/0.53 1.59 0.7 1.0 0.3 1.8 35.7 1515 12.9

9 1.5 7/0.53 1.59 0.7 1.0 0.3 1.9 38.0 1705 12.9

10 1.5 7/0.53 1.59 0.7 1.0 0.3 1.9 40.2 1860 12.9

11 1.5 7/0.53 1.59 0.7 1.0 0.3 1.9 40.2 1955 12.9

12 1.5 7/0.53 1.59 0.7 1.0 0.3 1.9 41.4 2025 12.9

13 1.5 7/0.53 1.59 0.7 1.2 0.3 2.0 43.4 2255 12.9

14 1.5 7/0.53 1.59 0.7 1.2 0.3 2.0 44.7 2355 12.9

15 1.5 7/0.53 1.59 0.7 1.2 0.3 2.1 46.2 2545 12.9

Page 61: Hi Essence Cable Spec

Doc: HEDoc: HEDoc: HEDoc: HE----SPECSPECSPECSPEC Rev: Rev: Rev: Rev: 4444 ((((02020202/201/201/201/2011111))))

61/67

HI-ESSENCE CABLE SDN. BHD. Factory address: Lot 13662, Kerteh Plastic Park, Kemaman, Terengganu.

Office address: No.2, Jalan Puteri 5/16, Bandar Puteri, 47100 Puchong, Selangor.

Tel:60-3-8061 3793 Fax:60-3-8061 2493 URL:http://www.he-cable.com

HE

SILICON RUBBER INSULATED BRAIDED LSFH SHEATHED OVERALL SCREENED

FIRE RESISTANT AND FLAME RETARDANT INSTRUMENTCABLE

TYPE TEL1 : CU/MICA/SiR/OSCR/LSFH/SWB/LSFH INSTRUMENT CABLE DESCRIPTION

Single pair and multi-pair cables with copper conductor, mica tape, SiR insulated, overall screened, flame

retardant low smoke free halogen compound inner covering, galvanized steel wire braided and flame retardant

low smoke free halogen compound outer sheath.

Cables are rated at 100 V

CONSTRUCTION

1 Conductor

Plain annealed circular stranded copper conductor, conform to IEC 60228 or BS 6360 class 1.

2 Fire proof layer

Mica tape.

3 Insulation

SiR (Silicon rubber)

4 Pairing

Two insulated cores shall be uniformly twisted together to form a pair.

Note : Two pair cables with overall screen shall have four cores laid in quad formation.

5 Pair identification

Colour code.

6 Cabling

Twisted pairs are laid up together, if necessary filled with non-hygroscopic material compatible with the

insulation.

7 Screening

Accumulated pairs screened with aluminium/mylar tape, helically applied with the metallic side down, in

electrical contact with a tinned annealed copper drain wire of 0.75 mm2.

8 Inner covering

Flame retardant low smoke free halogen compound, colour black.

9 Armour

Galvanized steel wires shall be braided over the LSFH inner covering.

10 Outer sheath

Flame retardant low smoke free halogen compound , colour grey. CABLE MARKING

manufacturer’s name, rated voltage, cable type, conductor size, manufacture year.

SPECIFICATIONS

IEC 60092,

IEC 60331, IEC 60332-3 Cat A

IEC 60754 (HCL emission 0.5%maximum by weight)

ASTM D 2863(Oxygen index greater than 30%)

Page 62: Hi Essence Cable Spec

Doc: HEDoc: HEDoc: HEDoc: HE----SPECSPECSPECSPEC Rev: Rev: Rev: Rev: 4444 ((((02020202/201/201/201/2011111))))

62/67

HI-ESSENCE CABLE SDN. BHD. Factory address: Lot 13662, Kerteh Plastic Park, Kemaman, Terengganu.

Office address: No.2, Jalan Puteri 5/16, Bandar Puteri, 47100 Puchong, Selangor.

Tel:60-3-8061 3793 Fax:60-3-8061 2493 URL:http://www.he-cable.com

HE

TYPE TEL1 : CU/MICA/SiR/OSCR/LSFH/SWB/LSFH INSTRUMENT CABLE

100 V

Number

of

pairs

Conductor Nominal

thickness

of

insulation

Approx.

thickness

of

inner

covering

Nominal

diameter

of

steel

wire

Nominal

thickness

of

outer

sheath

Approx.

overall

diameter

Approx.

cable

weight

Maximum

Conductor

Resistance

(at 20ºC)

Nominal

cross-

sectional

area

No./dia.

of

wire

Approx.

outer

diameter

P mm2 No./mm mm mm mm mm mm mm kg/km ΩΩΩΩ/km

1 1.0 1/1.13 1.13 1.0 1.0 0.3 1.2 14.7 290 18.6

2 1.0 1/1.13 1.13 1.0 1.0 0.3 1.2 16.4 370 18.6

3 1.0 1/1.13 1.13 1.0 1.0 0.3 1.4 22 560 18.6

4 1.0 1/1.13 1.13 1.0 1.0 0.3 1.4 23.9 655 18.6

5 1.0 1/1.13 1.13 1.0 1.0 0.3 1.5 26.4 750 18.6

6 1.0 1/1.13 1.13 1.0 1.0 0.3 1.6 28.7 870 18.6

7 1.0 1/1.13 1.13 1.0 1.0 0.3 1.6 28.7 895 18.6

8 1.0 1/1.13 1.13 1.0 1.0 0.3 1.6 30.4 995 18.6

9 1.0 1/1.13 1.13 1.0 1.0 0.3 1.7 32.7 1125 18.6

10 1.0 1/1.13 1.13 1.0 1.0 0.3 1.8 34.6 1235 18.6

11 1.0 1/1.13 1.13 1.0 1.0 0.3 1.8 34.6 1285 18.6

12 1.0 1/1.13 1.13 1.0 1.0 0.3 1.8 36.1 1330 18.6

13 1.0 1/1.13 1.13 1.0 1.0 0.3 1.8 37.2 1430 18.6

14 1.0 1/1.13 1.13 1.0 1.0 0.3 1.8 38.3 1485 18.6

15 1.0 1/1.13 1.13 1.0 1.0 0.3 1.9 39.6 1610 18.6

16 1.0 1/1.13 1.13 1.0 1.0 0.3 1.9 40.7 1665 18.6

17 1.0 1/1.13 1.13 1.0 1.2 0.3 2.0 42.3 1825 18.6

18 1.0 1/1.13 1.13 1.0 1.2 0.3 2.0 43.2 1880 18.6

19 1.0 1/1.13 1.13 1.0 1.2 0.3 2.0 44.2 1935 18.6

20 1.0 1/1.13 1.13 1.0 1.2 0.3 2.1 45.3 2030 18.6

PAIR IDENTIFICATION:

Pair No. a-wire b-wire Pair No. a-wire b-wire

1 Black Blue 11 Black Red

2 Black Green 12 Blue Red

3 Blue Green 13 Green Red

4 Black Brown 14 Brown Red

5 Blue Brown 15 White Red

6 Green Brown 16 Black Orange

7 Black White 17 Blue Orange

8 Blue White 18 Green Orange

9 Green White 19 Brown Orange

10 Brown White 20 White Orange

Note:Two pair cables with overall screen shall have four cores laid in quad formation and colour coded

in clockwise order of rotation: Black, Blue, Green, Brown.

Page 63: Hi Essence Cable Spec

Doc: HEDoc: HEDoc: HEDoc: HE----SPECSPECSPECSPEC Rev: Rev: Rev: Rev: 4444 ((((02020202/201/201/201/2011111))))

63/67

HI-ESSENCE CABLE SDN. BHD. Factory address: Lot 13662, Kerteh Plastic Park, Kemaman, Terengganu.

Office address: No.2, Jalan Puteri 5/16, Bandar Puteri, 47100 Puchong, Selangor.

Tel:60-3-8061 3793 Fax:60-3-8061 2493 URL:http://www.he-cable.com

HE

Minimum Bending Radius: Cable Type Radius

PVC wire 8D

No shield Single-core 8D

Multi-core 6D

Shield Single-core 10D

Multi-core 8D

SWA-Cable 10D

SWB-Cable 8D

where D: cable outer diameter

Voltage Drop: For single-phase circuits,

Voltage drop, 222 XRLIVd +×××= (V)

For three-phase circuits,

Voltage drop, 223 XRLIVd +×××= (V)

where I = current (A)

R = a.c. resistance at operating temperature(Ω/km)

X = reactance(Ω/km)

L = cable length (km)

Page 64: Hi Essence Cable Spec

Doc: HEDoc: HEDoc: HEDoc: HE----SPECSPECSPECSPEC Rev: Rev: Rev: Rev: 4444 ((((02020202/201/201/201/2011111))))

64/67

HI-ESSENCE CABLE SDN. BHD. Factory address: Lot 13662, Kerteh Plastic Park, Kemaman, Terengganu.

Office address: No.2, Jalan Puteri 5/16, Bandar Puteri, 47100 Puchong, Selangor.

Tel:60-3-8061 3793 Fax:60-3-8061 2493 URL:http://www.he-cable.com

HE

Short Circuit Current(based on IEC 60949)

t

SK

Ii

f

+

+××

=βθ

βθln22

where I : permissible short-circuit current.

t : duration of short-circuit(sec)

K: constant depending on .the material of the current carrying component(As1/2

/mm2):

( )

20

121020

ρ

βσ −×+= cK [Copper : 226

; Tinned Copper : 221]

S: geometrical cross-sectional area of the current carrying component(mm2):for

conductors spevified in IEC 228 it is sufficient to take the nominal cross-sectional

area

θf : final temperature(ºC) [XLPE : 250 ; PE : 140

; EPR : 250]

θi : initial temperature(ºC) [XLPE : 90 ; PE : 70

; EPR : 90]

β : reciprocal of temperature coefficient of resistance of the current carrying component

at 0º(K)[Copper : 234.5]

σc : volumetric specific heat of the current carrying component at 20 ºC(J/K.m3)

[Copper : 3.45x106]

ρ20 : electrical resistivity of the current carrying component at 20 ºC(Ω.m)

[Copper : 1.7241x10-8

; Tinned Copper : 1.796x10-8

]

(A). XLPE Insulation cable, Copper Conductor:

Nominal cross sectional area(mm²) 1.5 2.5 4 6 10 16 25 35 50 70

Short circuit current for 1 sec.(kA) 0.215 0.36 0.57 0.86 1.43 2.29 3.58 5.01 7.15 10.02

Nominal cross sectional area(mm²) 95 120 150 185 240 300 400 500 630

Short circuit current for 1 sec.(kA) 13.59 17.17 21.46 26.47 34.34 42.93 57.23 71.54 90.14

(B). EPR Insulation cable, Tinned Copper Conductor:

Nominal cross sectional area(mm²) 1.0 1.5 2.5 4 6 10 16 25 35 50

Short circuit current for 1 sec.(kA) 0.14 0.21 0.35 0.56 0.84 1.4 2.24 3.5 4.9 7.0

Nominal cross sectional area(mm²) 70 95 120 150 185 240 300 400 500 630

Short circuit current for 1 sec.(kA) 9.79 13.3 16.8 20.99 25.89 33.58 41.98 55.97 69.96 88.15

(C). PE Insulation cable, Copper Conductor:

Nominal cross sectional area(mm²) 1.0

Short circuit current for 1 sec.(kA) 0.103

Page 65: Hi Essence Cable Spec

Doc: HEDoc: HEDoc: HEDoc: HE----SPECSPECSPECSPEC Rev: Rev: Rev: Rev: 4444 ((((02020202/201/201/201/2011111))))

65/67

HI-ESSENCE CABLE SDN. BHD. Factory address: Lot 13662, Kerteh Plastic Park, Kemaman, Terengganu.

Office address: No.2, Jalan Puteri 5/16, Bandar Puteri, 47100 Puchong, Selangor.

Tel:60-3-8061 3793 Fax:60-3-8061 2493 URL:http://www.he-cable.com

HE

Page 66: Hi Essence Cable Spec

Doc: HEDoc: HEDoc: HEDoc: HE----SPECSPECSPECSPEC Rev: Rev: Rev: Rev: 4444 ((((02020202/201/201/201/2011111))))

66/67

HI-ESSENCE CABLE SDN. BHD. Factory address: Lot 13662, Kerteh Plastic Park, Kemaman, Terengganu.

Office address: No.2, Jalan Puteri 5/16, Bandar Puteri, 47100 Puchong, Selangor.

Tel:60-3-8061 3793 Fax:60-3-8061 2493 URL:http://www.he-cable.com

HE

Correction factors for ambient air temperatures

Maximum conductor

temperature ºC

ambient air temperature

ºC

20 25 30 35 40 45 50 55 60

90 1.08 1.04 1 0.96 0.91 0.87 0.82 0.76 0.71

Correction factors for ambient ground temperatures

Maximum conductor

temperature

ºC

ambient air temperature

ºC

10 15 20 25 30 35 40 45 50

90 1.07 1.04 1 0.96 0.93 0.89 0.85 0.8 0.76

Correction factors for depths of laying other than 0.8m for direct buried

cables

Depth of laying

m

Single-core cables

Three-core cables Nominal conductor size (mm2)

≤185mm2 >185mm

2

0.5 1.04 1.06 1.04

0.6 1.02 1.04 1.03

1 0.98 0.97 0.98

1.25 0.96 0.95 0.96

1.5 0.95 0.93 0.95

1.75 0.94 0.91 0.94

2 0.93 0.90 0.93

2.5 0.91 0.88 0.91

3 0.90 0.86 0.90

Correction factors for depths of laying other than 0.8m for cables in ducts

Depth of laying

m

Single-core cables

Three-core cables Nominal conductor size (mm2)

≤185mm2 >185mm

2

0.5 1.04 1.05 1.03

0.6 1.02 1.03 1.02

1 0.98 0.97 0.99

1.25 0.96 0.95 0.97

1.5 0.95 0.93 0.96

1.75 0.94 0.92 0.95

2 0.93 0.91 0.94

2.5 0.91 0.89 0.93

3 0.90 0.88 0.92

Page 67: Hi Essence Cable Spec

Doc: HEDoc: HEDoc: HEDoc: HE----SPECSPECSPECSPEC Rev: Rev: Rev: Rev: 4444 ((((02020202/201/201/201/2011111))))

67/67

HI-ESSENCE CABLE SDN. BHD. Factory address: Lot 13662, Kerteh Plastic Park, Kemaman, Terengganu.

Office address: No.2, Jalan Puteri 5/16, Bandar Puteri, 47100 Puchong, Selangor.

Tel:60-3-8061 3793 Fax:60-3-8061 2493 URL:http://www.he-cable.com

HE

Derating factor of current carrying capacity for group installation in air (1) 1~ 12 cable

No. of cables 1 2 3 6 4

Arrangement

of installation

S = d

1

0.85 0.8 0.7 0.7

S = 2d 0.95 0.95 0.9 0.9

S = 3d 1.00 1.00 0.95 0.95

No. of cables 6 8 9 12

Arrangement

of installation

S = d 0.6 --- --- ---

S = 2d 0.9 0.85 0.8 0.8

S = 3d 0.95 0.9 0.85 0.85

(2) Other arrangement of installation

No. of cables in column 1 2 3

No. of cables in row 7~20 4 5 6 7 8~20 3 4

S = d 0.7 0.6 0.56 0.53 0.51 0.5 0.48 0.41

S = 2d 0.8 --- 0.73 0.72 0.71 0.7 --- ---

No. of cables in column 3

No. of cables in row 5 6 7 8 9~10 11~12 13~15 16~19 20

S = d 0.37 0.34 0.32 0.31 0.3 0.3 0.3 0.3 0.3

S = 2d 0.68 0.66 0.65 0.65 0.64 0.63 0.62 0.61 0.6