NOTA PANDUAN PENGGUNAAN KATALOG IBS JKR VERSI 2: 2016 Oleh: Ir. Zul Amri Bin Abu Bakar Bahagian Pembangunan dan Penyelidikan, Cawangan Kejuruteraan Awam dan Struktur. RASUK PRA TUANG

Upload: doankhanh

Post on 10-Aug-2019

494 views

Category:

Documents


44 download

TRANSCRIPT

Page 1: NOTA PANDUAN PENGGUNAAN KATALOG IBS JKR VERSI 2: …epsmg.jkr.gov.my/images/c/c7/02_ZulAmri_27112016_MODUL_KATALOG_IBS...the specified type of moment and type of shear to get the beam

NOTA PANDUAN PENGGUNAAN KATALOG IBS JKR VERSI 2: 2016

Oleh:

Ir. Zul Amri Bin Abu Bakar

Bahagian Pembangunan dan Penyelidikan,

Cawangan Kejuruteraan Awam dan Struktur.

RASUK PRA TUANG

Page 2: NOTA PANDUAN PENGGUNAAN KATALOG IBS JKR VERSI 2: …epsmg.jkr.gov.my/images/c/c7/02_ZulAmri_27112016_MODUL_KATALOG_IBS...the specified type of moment and type of shear to get the beam

ISI KANDUNGAN Panduan Penggunaan Katalog IBS Versi 2: 2016

RASUK PRATUANG

PAPAK PRATUANG

Page 3: NOTA PANDUAN PENGGUNAAN KATALOG IBS JKR VERSI 2: …epsmg.jkr.gov.my/images/c/c7/02_ZulAmri_27112016_MODUL_KATALOG_IBS...the specified type of moment and type of shear to get the beam

KATALOG IBS JKR

KATALOG IBS JKR

JULAI 2010

KATALOG IBS JKR

VERSI 2: 2016

Page 4: NOTA PANDUAN PENGGUNAAN KATALOG IBS JKR VERSI 2: …epsmg.jkr.gov.my/images/c/c7/02_ZulAmri_27112016_MODUL_KATALOG_IBS...the specified type of moment and type of shear to get the beam

SENARAI LUKISAN DALAM KATALOG IBS JKR VERSI 2: 2016

NOTA AM

RASUK PRATUANG

TIANG PRATUANG

PAPAK PRATUANG

TANGGA PRATUANG

SAMBUNGAN PRATUANG

Page 5: NOTA PANDUAN PENGGUNAAN KATALOG IBS JKR VERSI 2: …epsmg.jkr.gov.my/images/c/c7/02_ZulAmri_27112016_MODUL_KATALOG_IBS...the specified type of moment and type of shear to get the beam

1.0 PRECAST BEAM

PRECAST RECTANGULAR BEAM

PRECAST INVERTED T BEAM

PRECAST L SHAPE BEAM

Page 6: NOTA PANDUAN PENGGUNAAN KATALOG IBS JKR VERSI 2: …epsmg.jkr.gov.my/images/c/c7/02_ZulAmri_27112016_MODUL_KATALOG_IBS...the specified type of moment and type of shear to get the beam

1.1 RASUK PRATUANG (JENIS SEGIEMPAT)

Lekukan 200 mm

Lekukan 100 mm

BIL SAIZ RASUK LEKUKAN

1 300 X 600 200mm

2 300 X 700 200mm

3 350 X 700 200mm

4 350 X 800 200mm

5 300 X 600 100mm

6 300 X 700 100mm

7 350 X 700 100mm

8 350 X 800 100mm

9 300 X 500 -

10 200 X 500 -

11 200 X 600 -

12 200 X 700 -

13 250 X 600 -

14 250 X 700 -

15 250 X 800 -

Lukisan Baru Lukisan Asal

Page 7: NOTA PANDUAN PENGGUNAAN KATALOG IBS JKR VERSI 2: …epsmg.jkr.gov.my/images/c/c7/02_ZulAmri_27112016_MODUL_KATALOG_IBS...the specified type of moment and type of shear to get the beam
Page 8: NOTA PANDUAN PENGGUNAAN KATALOG IBS JKR VERSI 2: …epsmg.jkr.gov.my/images/c/c7/02_ZulAmri_27112016_MODUL_KATALOG_IBS...the specified type of moment and type of shear to get the beam

1.2 RASUK PRATUANG (JENIS INVERTED T & L)

INVERTED T

BIL SAIZ RASUK

1 400 X 500

2 400 X 600

3 400 X 700

4 400 X 800

5 500 X 500

6 500 X 600

7 500 X 650

8 500 X 700

9 500 X 800

10 600 X 600

11 600 X 700

12 600 X 800

Papak Papak

Lukisan Baru

Lukisan Asal

BIL SAIZ RASUK

1 300 X 500

2 300 X 600

3 300 X 700

4 300 X 800

5 400 X 500

6 400 X 600

7 400 X 700

8 400 X 800

JENIS L

Papak

Jenis L

Inverted T

Page 9: NOTA PANDUAN PENGGUNAAN KATALOG IBS JKR VERSI 2: …epsmg.jkr.gov.my/images/c/c7/02_ZulAmri_27112016_MODUL_KATALOG_IBS...the specified type of moment and type of shear to get the beam
Page 10: NOTA PANDUAN PENGGUNAAN KATALOG IBS JKR VERSI 2: …epsmg.jkr.gov.my/images/c/c7/02_ZulAmri_27112016_MODUL_KATALOG_IBS...the specified type of moment and type of shear to get the beam
Page 11: NOTA PANDUAN PENGGUNAAN KATALOG IBS JKR VERSI 2: …epsmg.jkr.gov.my/images/c/c7/02_ZulAmri_27112016_MODUL_KATALOG_IBS...the specified type of moment and type of shear to get the beam

1.3 PANDUAN PENGGUNAAN

Page 12: NOTA PANDUAN PENGGUNAAN KATALOG IBS JKR VERSI 2: …epsmg.jkr.gov.my/images/c/c7/02_ZulAmri_27112016_MODUL_KATALOG_IBS...the specified type of moment and type of shear to get the beam

CARTA ALIR PENGGUNAAN KATALOGMula

Mengira nilai momen lentur dan daya ricih muktamad

dari analisis rekabentuk

Rujuk Panduan 2 Rekabentuk Secara In-House

(One Off/In-situ)

Pilih saiz keratan dan bentuk komponen yang

bersesuaian dengan kapasiti momen, ricih dan beban

paksi pada komponen pratuang yang telah direka

i) Papak Pratuang Jenis Separa (Momen lentur)

ii) Rasuk Pratuang (Momen lentur dan Ricih)

iii) Tiang Pratuang (Momen lentur dan Beban Paksi)

Periksa kestabilan, kekuatan dan integriti pada

keseluruhan rekabentuk struktur

Siap

Rajah 1 : Carta Alir bagi panduan pengguna Katalog IBS JKR

Page 13: NOTA PANDUAN PENGGUNAAN KATALOG IBS JKR VERSI 2: …epsmg.jkr.gov.my/images/c/c7/02_ZulAmri_27112016_MODUL_KATALOG_IBS...the specified type of moment and type of shear to get the beam

LANGKAH UMUM PENGGUNAAN LUKISAN PIAWAI

1. STEPS FOR USING STANDARDIZE DRAWING FOR PRECAST BEAM

1.1 The designer shall prepare layout which contain information for beam, slab column, half joint and nib.

1.2 This guideline specifies how to incorporate precast beam from tables into the layout.

1.3 There are 3 types of precast beam in the JKR IBS CATALOGUE VERSION 2: 2016:

i. Rectangular Beam

ii. Inverted T Beam

iii. L Shape Beam

1.4 The designer shall determine item as follows:

The type of beam and beam size will be used in the project

Design data values as required by the code:

i. Design Moment (Mu)

ii. Design shear (V)

Page 14: NOTA PANDUAN PENGGUNAAN KATALOG IBS JKR VERSI 2: …epsmg.jkr.gov.my/images/c/c7/02_ZulAmri_27112016_MODUL_KATALOG_IBS...the specified type of moment and type of shear to get the beam

LANGKAH UMUM PENGGUNAAN LUKISAN PIAWAI

1.5 The designer shall refer to Precast Beam Catalogue (drawing no JKR.CKAS/P-IBS/PEL 15/……. ) for

the specified type of moment and type of shear to get the beam designation.

1.6 All the information for detailing reinforcement bar, links and related information for the beam can be

found in the specified drawing.

1.7 Explanation of Designation

1.7.1 Designation

Page 15: NOTA PANDUAN PENGGUNAAN KATALOG IBS JKR VERSI 2: …epsmg.jkr.gov.my/images/c/c7/02_ZulAmri_27112016_MODUL_KATALOG_IBS...the specified type of moment and type of shear to get the beam

Uji Minda… 1

BR-3580-6039

Page 16: NOTA PANDUAN PENGGUNAAN KATALOG IBS JKR VERSI 2: …epsmg.jkr.gov.my/images/c/c7/02_ZulAmri_27112016_MODUL_KATALOG_IBS...the specified type of moment and type of shear to get the beam

Uji Minda… 2

BT-4080-5036

Page 17: NOTA PANDUAN PENGGUNAAN KATALOG IBS JKR VERSI 2: …epsmg.jkr.gov.my/images/c/c7/02_ZulAmri_27112016_MODUL_KATALOG_IBS...the specified type of moment and type of shear to get the beam

Uji Minda… 3

BL-4050-0508

Page 18: NOTA PANDUAN PENGGUNAAN KATALOG IBS JKR VERSI 2: …epsmg.jkr.gov.my/images/c/c7/02_ZulAmri_27112016_MODUL_KATALOG_IBS...the specified type of moment and type of shear to get the beam

1.4 CONTOH PENGGUNAAN

Page 19: NOTA PANDUAN PENGGUNAAN KATALOG IBS JKR VERSI 2: …epsmg.jkr.gov.my/images/c/c7/02_ZulAmri_27112016_MODUL_KATALOG_IBS...the specified type of moment and type of shear to get the beam

Lukisan Arkitek digunakan

untuk menentukan kedudukan

rasuk.

Page 20: NOTA PANDUAN PENGGUNAAN KATALOG IBS JKR VERSI 2: …epsmg.jkr.gov.my/images/c/c7/02_ZulAmri_27112016_MODUL_KATALOG_IBS...the specified type of moment and type of shear to get the beam

Struktur dimodelkan di

dalam perisian Orion/

StaadPro bagi tujuan

analisis.

Pada peringkat ini, saiz

rasuk dan jenis rasuk yang

akan digunakan ditentukan

oleh perekabentuk mengikut

keperluan dan kesesuaian.

Page 21: NOTA PANDUAN PENGGUNAAN KATALOG IBS JKR VERSI 2: …epsmg.jkr.gov.my/images/c/c7/02_ZulAmri_27112016_MODUL_KATALOG_IBS...the specified type of moment and type of shear to get the beam

Model struktur dalam

bentuk 3D

Page 22: NOTA PANDUAN PENGGUNAAN KATALOG IBS JKR VERSI 2: …epsmg.jkr.gov.my/images/c/c7/02_ZulAmri_27112016_MODUL_KATALOG_IBS...the specified type of moment and type of shear to get the beam

Hasil analisis struktur seperti

momen lentur dan daya ricih

digunakan untuk penentuan saiz

rasuk di dalam Katalog IBS JKR

Versi 2 .

Page 23: NOTA PANDUAN PENGGUNAAN KATALOG IBS JKR VERSI 2: …epsmg.jkr.gov.my/images/c/c7/02_ZulAmri_27112016_MODUL_KATALOG_IBS...the specified type of moment and type of shear to get the beam
Page 24: NOTA PANDUAN PENGGUNAAN KATALOG IBS JKR VERSI 2: …epsmg.jkr.gov.my/images/c/c7/02_ZulAmri_27112016_MODUL_KATALOG_IBS...the specified type of moment and type of shear to get the beam

Pemilihan komponen rasuk

daripada Katalog IBS JKR V.2

dengan menggunakan nilai

momen lentur dan daya ricih

yang diperolehi.

Page 25: NOTA PANDUAN PENGGUNAAN KATALOG IBS JKR VERSI 2: …epsmg.jkr.gov.my/images/c/c7/02_ZulAmri_27112016_MODUL_KATALOG_IBS...the specified type of moment and type of shear to get the beam

Lukisan struktur dihasilkan dengan

menggunakan pelabelan komponen

daripada Katalog IBS JKR V.2.

BR-2560-1316

Page 26: NOTA PANDUAN PENGGUNAAN KATALOG IBS JKR VERSI 2: …epsmg.jkr.gov.my/images/c/c7/02_ZulAmri_27112016_MODUL_KATALOG_IBS...the specified type of moment and type of shear to get the beam

CONTOH PENGGUNAAN: RECTANGULAR BEAM

Page 27: NOTA PANDUAN PENGGUNAAN KATALOG IBS JKR VERSI 2: …epsmg.jkr.gov.my/images/c/c7/02_ZulAmri_27112016_MODUL_KATALOG_IBS...the specified type of moment and type of shear to get the beam

Precast Rectangular Beam

The designer's data:

Type of beam : Rectangular Beam

Beam size : 300 x 500 (mm)

Maximum moment capacity, Mu: 150 kNm

Maximum shear capacity, Vu: 200 kN

STEP 1: The type of beam and beam size will be used to identify the specific drawing

to be referred.

STEP 2: In this example, for the Rectangular beam size 300 x 500 (mm), the related drawing

from the catalogue :

JKR/CKAS/P-IBS/PEL 15/BR-3050/BR 01

Page 28: NOTA PANDUAN PENGGUNAAN KATALOG IBS JKR VERSI 2: …epsmg.jkr.gov.my/images/c/c7/02_ZulAmri_27112016_MODUL_KATALOG_IBS...the specified type of moment and type of shear to get the beam

Precast Rectangular BeamRectangular beam size 300 x 500(mm) : JKR/CKAS/P-IBS/PEL 15/BR-3050/BR 01

Page 29: NOTA PANDUAN PENGGUNAAN KATALOG IBS JKR VERSI 2: …epsmg.jkr.gov.my/images/c/c7/02_ZulAmri_27112016_MODUL_KATALOG_IBS...the specified type of moment and type of shear to get the beam

Precast Rectangular BeamSTEP 3: From the drawing, the designer has to identify which designation of beam should be used by

referring to the Maximum moment capacity, Mu (For this example Mu:150 kNm) and Maximum shear

capacity, Vu (For this example Vu:200 kN)

Figure 1 & 2 : Rectangular Beam Detail & Rectangular Beam Table Properties

Page 30: NOTA PANDUAN PENGGUNAAN KATALOG IBS JKR VERSI 2: …epsmg.jkr.gov.my/images/c/c7/02_ZulAmri_27112016_MODUL_KATALOG_IBS...the specified type of moment and type of shear to get the beam

STEP 4: The designation that will be used in this case is BR-3050-1520. This designation also will be

used as a marking in beam layout.

STEP 5: As shown in Figure 1, the required reinforcement for main bar of the beam are:

a) Top reinforcement bar: 2T16 for T1, 2T16 for T2

b) Bottom reinforcement bar : 4T20 for B1

c) Link that will be using for this beam are :

i. T10-200 for L1

ii. T10-200 for L2

iii. 2T10@100 c/c for L3

d) Detail for link and lifting hook refer to table in Figure 3 below:

Page 31: NOTA PANDUAN PENGGUNAAN KATALOG IBS JKR VERSI 2: …epsmg.jkr.gov.my/images/c/c7/02_ZulAmri_27112016_MODUL_KATALOG_IBS...the specified type of moment and type of shear to get the beam

INVERTED T BEAM

Page 32: NOTA PANDUAN PENGGUNAAN KATALOG IBS JKR VERSI 2: …epsmg.jkr.gov.my/images/c/c7/02_ZulAmri_27112016_MODUL_KATALOG_IBS...the specified type of moment and type of shear to get the beam

Precast Inverted T BeamThe designer's data:

Type of beam : Inverted T Beam

Beam size : 400 x 600 (mm)

Maximum moment capacity, Mu: 500 kNm

Maximum shear capacity, Vu: 359 kN

STEP 1: The type of beam and beam size will be used to identify the specific drawing

to be referred.

STEP 2: In this example, for the Inverted T beam size 400 x 600 (mm), the related drawing

from the catalogue :

JKR/CKAS/P-IBS/PEL 15/BT-4060/BT 02

Page 33: NOTA PANDUAN PENGGUNAAN KATALOG IBS JKR VERSI 2: …epsmg.jkr.gov.my/images/c/c7/02_ZulAmri_27112016_MODUL_KATALOG_IBS...the specified type of moment and type of shear to get the beam

Precast Inverted T BeamInverted T beam size 400 x 600 (mm): JKR/CKAS/P-IBS/PEL 15/BT-4060/BT 02

Page 34: NOTA PANDUAN PENGGUNAAN KATALOG IBS JKR VERSI 2: …epsmg.jkr.gov.my/images/c/c7/02_ZulAmri_27112016_MODUL_KATALOG_IBS...the specified type of moment and type of shear to get the beam

Precast Inverted T BeamSTEP 3: From the drawing, the designer has to identify which designation of beam should be used by

referring to the Maximum moment capacity, Mu (For this example Mu:500 kNm) and Maximum shear

capacity, Vu (For this example Vu: 359 kN)

Figure 4 & 5 : Inverted T Beam Detail & Table Properties

Page 35: NOTA PANDUAN PENGGUNAAN KATALOG IBS JKR VERSI 2: …epsmg.jkr.gov.my/images/c/c7/02_ZulAmri_27112016_MODUL_KATALOG_IBS...the specified type of moment and type of shear to get the beam

STEP 4: The designation that will be used in this case is BT-4060-5035. This designation also will be

used as a marking in beam layout.

STEP 5: As shown in Figure 4, the required reinforcement for main bar of the beam are:

a) Top reinforcement bar: 2T20 for T1, 2T20 for T2 and 2T20 for T3

b) Bottom reinforcement bar : 4T25 for B1 and 4T25 for B2

c) Link that will be using for this beam are :

i. T10-250 for L1 & L2 for X,

ii. T10-300 for L2 & L2 for Y

iii. 2T10@100 c/c for L3

d) Detail for link and lifting hook refer to table in Figure 6 below:

Page 36: NOTA PANDUAN PENGGUNAAN KATALOG IBS JKR VERSI 2: …epsmg.jkr.gov.my/images/c/c7/02_ZulAmri_27112016_MODUL_KATALOG_IBS...the specified type of moment and type of shear to get the beam

L SHAPE BEAM

Page 37: NOTA PANDUAN PENGGUNAAN KATALOG IBS JKR VERSI 2: …epsmg.jkr.gov.my/images/c/c7/02_ZulAmri_27112016_MODUL_KATALOG_IBS...the specified type of moment and type of shear to get the beam

Precast L Shape Beam

The designer's data:

Type of beam : L Shape Beam

Beam size : 300 x 700 (mm)

Maximum moment capacity, Mu: 600 kNm

Maximum shear capacity, Vu: 364 kN

STEP 1: The type of beam and beam size will be used to identify the specific drawing

to be referred.

STEP 2: In this example, for the L Shape beam size 300 x 700 (mm), the related drawing

from the catalogue :

JKR/CKAS/P-IBS/PEL 15/BL-3070/BL 03

Page 38: NOTA PANDUAN PENGGUNAAN KATALOG IBS JKR VERSI 2: …epsmg.jkr.gov.my/images/c/c7/02_ZulAmri_27112016_MODUL_KATALOG_IBS...the specified type of moment and type of shear to get the beam

Precast L Shape BeamL Shape beam size 300 x 700 (mm): JKR/CKAS/P-IBS/PEL 15/BL-3070/BL 03

Page 39: NOTA PANDUAN PENGGUNAAN KATALOG IBS JKR VERSI 2: …epsmg.jkr.gov.my/images/c/c7/02_ZulAmri_27112016_MODUL_KATALOG_IBS...the specified type of moment and type of shear to get the beam

Precast L Shape BeamSTEP 3: From the drawing, the designer has to identify which designation of beam should be used by

referring to the Maximum moment capacity, Mu (For this example Mu:600 kNm) and Maximum shear

capacity, Vu (For this example Vu: 364 kN)

Figure 7 & 8 : L Shape Beam Detail & Table Properties

Page 40: NOTA PANDUAN PENGGUNAAN KATALOG IBS JKR VERSI 2: …epsmg.jkr.gov.my/images/c/c7/02_ZulAmri_27112016_MODUL_KATALOG_IBS...the specified type of moment and type of shear to get the beam

STEP 4: The designation that will be used in this case is BL-3070-6036. This designation also will be

used as a marking in beam layout.

STEP 5: As shown in Figure 7, the required reinforcement for main bar of the beam are:

a) Top reinforcement bar: 2T16 for T1, 2T16 for T2 and 2T16 for T3

b) Bottom reinforcement bar: 3T25 for B1 and 3T25 for B2

c) Link that will be using for this beam are:

i. T10-200 for L1 & L2 for X

ii. T10-300 for L1 & L2 for Y

iii. 3T16@150 c/c for L3

d) Detail for link and lifting hook refer to table in Figure 9 below:

Page 41: NOTA PANDUAN PENGGUNAAN KATALOG IBS JKR VERSI 2: …epsmg.jkr.gov.my/images/c/c7/02_ZulAmri_27112016_MODUL_KATALOG_IBS...the specified type of moment and type of shear to get the beam

NOTA PANDUAN PENGGUNAAN KATALOG IBS JKR VERSI 2: 2016

Oleh:

Wan Rizana Binti Wan Muhammad

Bahagian Pembangunan dan Penyelidikan,

Cawangan Kejuruteraan Awam dan Struktur.

PAPAK PRA TUANG JENIS SEPARA

Page 42: NOTA PANDUAN PENGGUNAAN KATALOG IBS JKR VERSI 2: …epsmg.jkr.gov.my/images/c/c7/02_ZulAmri_27112016_MODUL_KATALOG_IBS...the specified type of moment and type of shear to get the beam

2.0 PAPAK PRATUANG

Page 43: NOTA PANDUAN PENGGUNAAN KATALOG IBS JKR VERSI 2: …epsmg.jkr.gov.my/images/c/c7/02_ZulAmri_27112016_MODUL_KATALOG_IBS...the specified type of moment and type of shear to get the beam

TERDAPAT 3 JENIS KETEBALAN PAPAK IAITU:

1. 150mm

2. 200mm

3. 250mm

2.1 PAPAK PRATUANG JENIS SEPARA

Page 44: NOTA PANDUAN PENGGUNAAN KATALOG IBS JKR VERSI 2: …epsmg.jkr.gov.my/images/c/c7/02_ZulAmri_27112016_MODUL_KATALOG_IBS...the specified type of moment and type of shear to get the beam
Page 45: NOTA PANDUAN PENGGUNAAN KATALOG IBS JKR VERSI 2: …epsmg.jkr.gov.my/images/c/c7/02_ZulAmri_27112016_MODUL_KATALOG_IBS...the specified type of moment and type of shear to get the beam
Page 46: NOTA PANDUAN PENGGUNAAN KATALOG IBS JKR VERSI 2: …epsmg.jkr.gov.my/images/c/c7/02_ZulAmri_27112016_MODUL_KATALOG_IBS...the specified type of moment and type of shear to get the beam
Page 47: NOTA PANDUAN PENGGUNAAN KATALOG IBS JKR VERSI 2: …epsmg.jkr.gov.my/images/c/c7/02_ZulAmri_27112016_MODUL_KATALOG_IBS...the specified type of moment and type of shear to get the beam

2.2 PANDUAN PENGGUNAAN

Page 48: NOTA PANDUAN PENGGUNAAN KATALOG IBS JKR VERSI 2: …epsmg.jkr.gov.my/images/c/c7/02_ZulAmri_27112016_MODUL_KATALOG_IBS...the specified type of moment and type of shear to get the beam

LANGKAH UMUM PENGGUNAAN LUKISAN PIAWAI

1.0 STEPS FOR USING STANDARDIZE DRAWING FOR PRECAST HALF SLAB

1.1 The designer shall prepare layout which contain information for beam, slab

column, half joint and nib.

1.2 This guideline specifies how to incorporate Precast Half Slab from tables into the layout.

1.3 The designer shall determine item as follows:

Design data values as required by the code:

Design Moment, M kNm

a. Mnon-comp – Installation Stage

b. Mcomp – Final Stage

Type of Precast Half Slab are based on slab thickness (mm)

a. HS-1215 – 1200mm(W) x 150mm (HT)

b. HS-1220 – 1200mm(W) x 200mm (HT)

c. HS-1225 – 1200mm(W) x 250mm (HT)

Page 49: NOTA PANDUAN PENGGUNAAN KATALOG IBS JKR VERSI 2: …epsmg.jkr.gov.my/images/c/c7/02_ZulAmri_27112016_MODUL_KATALOG_IBS...the specified type of moment and type of shear to get the beam

LANGKAH UMUM PENGGUNAAN LUKISAN PIAWAI

1.4 The designer shall refer to Precast Half Slab Table (drawing no: JKR.CKAS/P-IBS/PEL

15/HS…..) for the specified type of slab.

1.5 Explanation of Designation

Designation

Page 50: NOTA PANDUAN PENGGUNAAN KATALOG IBS JKR VERSI 2: …epsmg.jkr.gov.my/images/c/c7/02_ZulAmri_27112016_MODUL_KATALOG_IBS...the specified type of moment and type of shear to get the beam

CONTOH

Page 51: NOTA PANDUAN PENGGUNAAN KATALOG IBS JKR VERSI 2: …epsmg.jkr.gov.my/images/c/c7/02_ZulAmri_27112016_MODUL_KATALOG_IBS...the specified type of moment and type of shear to get the beam

Lukisan Arkitek digunakan

untuk meentukan kedudukan

papak.

Page 52: NOTA PANDUAN PENGGUNAAN KATALOG IBS JKR VERSI 2: …epsmg.jkr.gov.my/images/c/c7/02_ZulAmri_27112016_MODUL_KATALOG_IBS...the specified type of moment and type of shear to get the beam

Struktur dimodelkan di

dalam perisian Orion/

StaadPro bagi tujuan

analisis.

Page 53: NOTA PANDUAN PENGGUNAAN KATALOG IBS JKR VERSI 2: …epsmg.jkr.gov.my/images/c/c7/02_ZulAmri_27112016_MODUL_KATALOG_IBS...the specified type of moment and type of shear to get the beam

Hasil analisis struktur seperti

momen lentur dan daya ricih

digunakan untuk penentuan saiz

papak di dalam Katalog IBS JKR

Versi 2 .

Page 54: NOTA PANDUAN PENGGUNAAN KATALOG IBS JKR VERSI 2: …epsmg.jkr.gov.my/images/c/c7/02_ZulAmri_27112016_MODUL_KATALOG_IBS...the specified type of moment and type of shear to get the beam
Page 55: NOTA PANDUAN PENGGUNAAN KATALOG IBS JKR VERSI 2: …epsmg.jkr.gov.my/images/c/c7/02_ZulAmri_27112016_MODUL_KATALOG_IBS...the specified type of moment and type of shear to get the beam

Pemilihan komponen rasuk

daripada Katalog IBS JKR V.2

dengan menggunakan nilai

momen lentur yang

diperolehi.

Page 56: NOTA PANDUAN PENGGUNAAN KATALOG IBS JKR VERSI 2: …epsmg.jkr.gov.my/images/c/c7/02_ZulAmri_27112016_MODUL_KATALOG_IBS...the specified type of moment and type of shear to get the beam

CONTOH PENGGUNAAN: HALF SLAB

Page 57: NOTA PANDUAN PENGGUNAAN KATALOG IBS JKR VERSI 2: …epsmg.jkr.gov.my/images/c/c7/02_ZulAmri_27112016_MODUL_KATALOG_IBS...the specified type of moment and type of shear to get the beam

Precast Half Slab

The designer's data:

Thickness of Precast Half Slab (HT) : 150 mm

Maximum bending moment (Mnon-comp) : 8.0 kNm

Maximum bending moment (Mcomp) : 20.0 kNm

STEP 1: The type of slab and slab thickness will be used to identify the specific drawing

to be referred.

STEP 2: In this example, for the Half slab with thickness 150 (mm), the related drawing

from the catalogue :

JKR/CKAS/P-IBS/PEL 15/HS-1215/H 01

Page 58: NOTA PANDUAN PENGGUNAAN KATALOG IBS JKR VERSI 2: …epsmg.jkr.gov.my/images/c/c7/02_ZulAmri_27112016_MODUL_KATALOG_IBS...the specified type of moment and type of shear to get the beam

Precast Half SlabHalf slab with thickness 150 (mm): JKR/CKAS/P-IBS/PEL 15/HS-1215/H 01

Page 59: NOTA PANDUAN PENGGUNAAN KATALOG IBS JKR VERSI 2: …epsmg.jkr.gov.my/images/c/c7/02_ZulAmri_27112016_MODUL_KATALOG_IBS...the specified type of moment and type of shear to get the beam

Precast Half SlabSTEP 3: From the drawing, the designer has to identify which designation of half slab should be used

by referring to the Maximum bending moment, Mnon-comp (For this example Mnon-comp: 8.8 kNm) and

Maximum bending moment, Mcomp (For this example Mcomp: 22.1 kNm)

STEP 4: The designation that will be used in this case is HS-1215. This designation also will be used as

a marking in slab layout.

STEP 5: As shown in above, bar reinforcement T1 is T10-150 and T2 is T10-200 for designation half

slab type HS-1215 (drawing no. JKR/CKAS/P-IBS/PEL 15/HS-1215/H 01)

Page 60: NOTA PANDUAN PENGGUNAAN KATALOG IBS JKR VERSI 2: …epsmg.jkr.gov.my/images/c/c7/02_ZulAmri_27112016_MODUL_KATALOG_IBS...the specified type of moment and type of shear to get the beam

TERIMA KASIH