XDM®-100 Product Line
Version 8.3
Reference Manual
417006-2709-0H3-B02
-
8/9/2019 Xdm-100 Product Line Rm Etsi b02 8.3 En
2/325
XDM-100 Product Line (ETSI) Reference Manual
V8.3
Catalog No: X39175December 2011
10th Edition
© Copyright by ECI Telecom, 2007-2011. All rights reserved worldwide.
This is a legal agreement between you, the end user, and ECI Telecom Ltd. (“ECI Telecom”). BY OPENING THEDOCUMENTATION AND/OR DISK PACKAGE, YOU ARE AGREEING TO BE BOUND BY THE TERMS OF THIS
AGREEMENT. IF YOU DO NOT AGREE TO THE TERMS OF THIS AGREEMENT, PROMPTLY RETURN THE
UNOPENED DOCUMENTATION AND/OR DISK PACKAGE AND THE ACCOMPANYING ITEMS (INCLUDINGWRITTEN MATERIALS AND BINDERS OR OTHER CONTAINERS), TO THE PLACE FROM WHICH YOUOBTAINED THEM.
The information contained in the documentation and/or disk is proprietary and is subject to al l relevant copyright,patent, and other laws protecting intellectual property, as well as any specific agreement protecting ECI Telecom'srights in the aforesaid information. Neither this document nor the information contained in the documentation and/ordisk may be published, reproduced, or disclosed to third parties, in whole or in part, without the express priorwritten permission of ECI Telecom. In addition, any use of this document, the documentation and/or the disk, or theinformation contained therein for any purposes other than those for which it was disclosed, is strictly forbidden.
ECI Telecom reserves the right, without prior notice or liability, to make changes in equipment design orspecifications. Information supplied by ECI Telecom is believed to be accurate and reliable. However, noresponsibility whatsoever is assumed by ECI Telecom for the use thereof, nor for the rights of third parties, whichmay be affected in any way by the use and/or dissemination thereof.
Any representation(s) in the documentation and/or disk concerning performance of ECI Telecom product(s) are forinformational purposes only and are not warranties of product performance or otherwise, either express or implied.
ECI Telecom's standard limited warranty, stated in its sales contract or order confirmation form, is the only warrantyoffered by ECI Telecom.
The documentation and/or disk is provided “AS IS” and may contain flaws, omissions, or typesetting errors. Nowarranty is granted nor liability assumed in relation thereto, unless specifically undertaken in ECI Telecom's salescontract or order confirmation. Information contained in the documentation and in the disk is periodically updated,and changes will be incorporated in subsequent editions. If you have encountered an error, please notify ECITelecom. All specifications are subject to change without prior notice.
The documentation and/or disk and all information contained therein is owned by ECI Telecom and is protected byall relevant copyright, patent, and other applicable laws and international treaty provisions. Therefore, you musttreat the information contained in the documentation and disk as any other copyrighted material (for example, abook or musical recording).
Other Restrictions. You may not rent, lease, sell, or otherwise dispose of the documentation and disk, asapplicable. YOU MAY NOT USE, COPY, MODIFY, OR TRANSFER THE DOCUMENTATION AND/OR DISK OR
ANY COPY IN WHOLE OR PART, EXCEPT AS EXPRESSLY PROVIDED IN THIS LICENSE. ALL RIGHTS NOTEXPRESSLY GRANTED ARE RESERVED BY ECI Telecom.
All trademarks mentioned herein are the property of their respective holders.ECI Telecom shall not be liable to you or to any other party for any loss or damage whatsoever or howsoevercaused, arising directly or indirectly in connection with this documentation and/or disk, the information containedtherein, its use, or otherwise. Notwithstanding the generality of the aforementioned, you expressly waive any claimand/or demand regarding liability for indirect, special, incidental, or consequential loss or damage which may arisein respect of the documentation and/or disk and/or the information contained therein, howsoever caused, even ifadvised of the possibility of such damages.
The end user hereby undertakes and acknowledges that they read the "Before You Start/Safety Guidelines"instructions and that such instructions were understood by them.
It is hereby clarified that ECI Telecom shall not be liable to you or to any other party for any loss or damagewhatsoever or howsoever caused, arising directly or indirectly in connection with you fulfilling and/or failed to fulfillin whole or in part the "Before You Start/Safety Guidelines" instructions.
-
8/9/2019 Xdm-100 Product Line Rm Etsi b02 8.3 En
3/325
417006-2709-0H3-B02 ECI Telecom Ltd. Proprietary i
Contents About This Manual ................................................................... xv
Overview ............................................................................................................ xvIntended Audience ............................................................................................. xvDocument Organization ..................................................................................... xviDocument Conventions ..................................................................................... xviRelated Documentation ....................................................................................xviiiObtaining Technical Documentation ................................................................xviiiTechnical Assistance ......................................................................................... xix
Introduct ion .............................................................................. 1-1XDM-50 Platform Overview .............................................................................. 1-2XDM-50 Shelf Options ...................................................................................... 1-3XDM-100 Platform Overview ............................................................................ 1-5XDM-100 Shelf Configurations ......................................................................... 1-6XDM-100 I/O Protection Options ...................................................................... 1-8XDM-100H Overview ...................................................................................... 1-10XDM-300 Platform Overview .......................................................................... 1-16XDM-300 I/O Protection Options .................................................................... 1-17XDM-900 Platform Overview .......................................................................... 1-23XDM-900 I/O Protection Options .................................................................... 1-25DCC Functionality .......................................................................................... 1-30Management Architecture .............................................................................. 1-33
XDM-50 Common Cards .......................................................... 2-1Overview .......................................................................................................... 2-1Main Cross-Connect and Control (MXC50) Card ............................................. 2-2External Connection Unit (ECU50/ECU50-R) .................................................. 2-5Fan Control Unit (FCU50) .............................................................................. 2-11INF50 .............................................................................................................. 2-13CCP50-2 ......................................................................................................... 2-14
XDM-100 Common Cards ........................................................ 3-1Shelf Overview ................................................................................................. 3-2Fan Control Unit (FCU) .................................................................................... 3-3External Connection Unit (ECU) ....................................................................... 3-6Main Cross-Connect and Control (MXC) Card ............................................... 3-11
-
8/9/2019 Xdm-100 Product Line Rm Etsi b02 8.3 En
4/325
Contents XDM-100 Product Line Reference
Manual
ii ECI Telecom Ltd. Proprietary 417006-2709-0H3-B02
XDM-300 Common Cards ........................................................ 4-1XDM-300 Shelf Overview ................................................................................. 4-1
Fan Control Unit (FCU300) .............................................................................. 4-2External Connection Unit (ECU300) ................................................................. 4-6Main Cross-Connect and Control Card (MXC300) ......................................... 4-12XDM-300 Platform with 100 Gbps Capacity ................................................... 4-15
XDM-900 Common Cards ........................................................ 5-1XDM-900 Shelf Overview ................................................................................. 5-1Fan Control Unit (FCU900) .............................................................................. 5-2External Connection Unit (ECU900) ................................................................. 5-6Main Cross-Connect and Control Card (MXC900) ......................................... 5-11XDM-900 Platform with 60 Gbps Capacity ..................................................... 5-14
I/O Cards and Modules ............................................................ 6-1Overview .......................................................................................................... 6-1PDH Modules ................................................................................................... 6-4SDH Cards and Modules ................................................................................ 6-15CWDM I/O Modules ....................................................................................... 6-39Pluggable Interfaces (SFP/XFP) .................................................................... 6-42Overhead Access Module (OHU) ................................................................... 6-45
MPLS and Ethernet Data Modules ......................................... 7-1Overview .......................................................................................................... 7-1
Ethernet Switching Modules ............................................................................. 7-3EISMB Functionality ......................................................................................... 7-4EISMB Module Types ..................................................................................... 7-11DIOM Modules ............................................................................................... 7-17DIOM Module Types ...................................................................................... 7-17MCSM ............................................................................................................ 7-25
ASON (Automat ically Switched Opt ical Network) ................ 8-1Overview .......................................................................................................... 8-1Optical Control Plane Architecture ................................................................... 8-2 ASON Traffic Management .............................................................................. 8-6
ACP100 Module ............................................................................................... 8-9 ACP900 Module ............................................................................................. 8-11
-
8/9/2019 Xdm-100 Product Line Rm Etsi b02 8.3 En
5/325
XDM-100 Product Line Reference
Manual
Contents
417006-2709-0H3-B02 ECI Telecom Ltd. Proprietary iii
Tributary Protection Unit (TPU) .............................................. 9-1Overview .......................................................................................................... 9-1
TC Modules ...................................................................................................... 9-5TPMs ................................................................................................................ 9-8TPU and I/O Slots Allocation for Protection ................................................... 9-15Optical Amplifiers ........................................................................................... 9-19TPU/OCU Shelf .............................................................................................. 9-24CWDM Networking Modules .......................................................................... 9-24
Accessories ......................................................................... 10-35Overview ...................................................................................................... 10-35xRAP-100 ..................................................................................................... 10-36xRAP-D ........................................................................................................ 10-40
RAP-BG ........................................................................................................ 10-46RAP-4B ........................................................................................................ 10-47xDDF-21 Patch Panel for Unbalanced Electrical Connections ..................... 10-50Fiber Storage Tray (FST) ............................................................................. 10-51Optical Distribution Frame ............................................................................ 10-52Optical Patch Panel ...................................................................................... 10-54Cable Guiding Accessories .......................................................................... 10-55
XDM Protection and Restoration Mechanisms ................... 11-1Overview ........................................................................................................ 11-1 ASON Protection and Restoration Capabilities .............................................. 11-2
MPLS Protection Schemes ............................................................................ 11-6Ethernet PB Features ................................................................................... 11-11Fast IOP: 1:1 Card Protection ...................................................................... 11-13SDH Protection Schemes ............................................................................. 11-14SDH Line Protection ..................................................................................... 11-19Equipment Protection ................................................................................... 11-22Integrated Protection for I/O Cards with Electrical Interfaces ....................... 11-23
Maintenance ........................................................................... 12-1Overview ........................................................................................................ 12-1Short MTTR .................................................................................................... 12-2Built-In Test .................................................................................................... 12-3 Alarms System ............................................................................................... 12-4Troubleshooting .............................................................................................. 12-5
-
8/9/2019 Xdm-100 Product Line Rm Etsi b02 8.3 En
6/325
Contents XDM-100 Product Line Reference
Manual
iv ECI Telecom Ltd. Proprietary 417006-2709-0H3-B02
Standards and References .................................................... A-1Overview .......................................................................................................... A-1
Broadband Forum ............................................................................................ A-2Environmental Standards ................................................................................. A-2ETSI: European Telecommunications Standards Institute ............................... A-3IEC: International Electrotechnical Commission .............................................. A-4IEEE: Institute of Electrical and Electronic Engineers ...................................... A-5IETF: Internet Engineering Task Force ............................................................ A-6ISO: International Organization for Standardization ......................................... A-8ITU-T: International Telecommunication Union ................................................ A-9MEF: Metro Ethernet Forum ........................................................................... A-14NIST: National Institute of Standards and Technology .................................. A-14North American Standards ............................................................................. A-15OMG: Object Management Group ................................................................. A-16TMF: TeleManagement Forum ....................................................................... A-16Web Protocol Standards ................................................................................ A-16
Index .......................................................................................... I-1
-
8/9/2019 Xdm-100 Product Line Rm Etsi b02 8.3 En
7/325
417006-2709-0H3-B02 ECI Telecom Ltd. Proprietary v
List of FiguresFigure 1-1: XDM-50 shelf ............................................................................................... 1-2
Figure 1-2: Basic XDM-50 shelf layout .......................................................................... 1-4
Figure 1-3: XDM-100 shelf ............................................................................................. 1-5
Figure 1-4: Basic XDM-100 shelf ................................................................................... 1-8
Figure 1-5: Expanded XDM-100 shelf ............................................................................ 1-9
Figure 1-6: Double-expanded XDM-100 shelf ............................................................... 1-9
Figure 1-7: XDM-100 with a TPU/OCU shelf ............................................................... 1-11
Figure 1-8: TPU and OCU slots designation ................................................................ 1-12
Figure 1-9: Basic XDM-100 .......................................................................................... 1-13
Figure 1-10: Expanded XDM-100 ................................................................................ 1-14
Figure 1-11: Double-expanded XDM-100 .................................................................... 1-15
Figure 1-12: XDM-300 shelf ......................................................................................... 1-16
Figure 1-13: Basic XDM-300 shelf, horizontal installation ........................................... 1-18
Figure 1-14: Basic XDM-300 shelf, vertical Installation ............................................... 1-19
Figure 1-15: XDM-300 with TPU on top ....................................................................... 1-20
Figure 1-16: XDM-300 with TPUs on top and at the bottom ........................................ 1-21
Figure 1-17: XDM-300 with two TPUs and an OCU .................................................... 1-22
Figure 1-18: XDM-900 shelf ......................................................................................... 1-23
Figure 1-19: Basic XDM-900 shelf, horizontal installation ........................................... 1-26
Figure 1-20: Basic XDM-900 shelf, vertical Installation ............................................... 1-26
Figure 1-21: XDM-900 with TPU on top ....................................................................... 1-27
Figure 1-22: XDM-900 with TPUs on top and at the bottom ........................................ 1-28
Figure 1-23: XDM-900 with two TPUs and an OCU .................................................... 1-29
Figure 1-24: XDM-100 DCC capacity before modification ........................................... 1-30
Figure 1-25: XDM-100 DCC capacity after modification .............................................. 1-31
Figure 1-26: XDM-300/XDM-900 DCC capacity before modification........................... 1-31
Figure 1-27: XDM-300/XDM-900 DCC capacity after modification .............................. 1-32
Figure 1-28: Typical XDM-100 Shelf View ................................................................... 1-33
Figure 1-29: Typical XDM-100 Shelf window ............................................................... 1-34
Figure 2-1: Basic XDM-50 shelf layout .......................................................................... 2-2
Figure 2-2: MXC50 front panel ....................................................................................... 2-3
Figure 2-3: ECU50 front panel ....................................................................................... 2-6
Figure 2-4: ECU50_R front panel .................................................................................. 2-9
Figure 2-5: FCU50 front panel ..................................................................................... 2-11
Figure 2-6: Installed air filter ......................................................................................... 2-12
Figure 2-7: INF50 front panel ....................................................................................... 2-13
-
8/9/2019 Xdm-100 Product Line Rm Etsi b02 8.3 En
8/325
List of Figures XDM-100 Product Line Reference
Manual
vi ECI Telecom Ltd. Proprietary 417006-2709-0H3-B02
Figure 2-8: CCP50-2 module front panel ..................................................................... 2-14
Figure 3-1: Basic XDM-100 shelf ................................................................................... 3-2
Figure 3-2: FCU general view ........................................................................................ 3-3
Figure 3-3: Installed air filter ........................................................................................... 3-5
Figure 3-4: ECU-F front panel ........................................................................................ 3-7
Figure 3-5: ECU front panel ........................................................................................... 3-9
Figure 3-6: XDM-100 with two MXC-100 slots capacity .............................................. 3-12
Figure 3-7: MXC-100 front panel ................................................................................. 3-12
Figure 3-8: XDM-100 with two MXC-100B slots capacity ............................................ 3-15
Figure 3-9: MXC-100B front panel ............................................................................... 3-15
Figure 3-10: XDM-100 with one MXC-100 and one MXC-BR slots capacity ............... 3-16
Figure 3-11: MXC-BR front panel ................................................................................ 3-16
Figure 3-12: Shelf with MXC-100 redundancy ............................................................. 3-17
Figure 3-13: Shelf without MXC redundancy ............................................................... 3-19
Figure 3-14: SAM1_4/E ................................................................................................ 3-21
Figure 3-15: SAM1_4O/SAM1_4OB aggregate module .............................................. 3-22
Figure 3-16: SAM4_2 aggregate module ..................................................................... 3-23
Figure 3-17: SAM16_1/SAM16_1B .............................................................................. 3-24
Figure 4-1: FCU300 general view .................................................................................. 4-3
Figure 4-2: XDM-300 with air filter ................................................................................. 4-5
Figure 4-3: ECU300-F front panel .................................................................................. 4-6
Figure 4-4: ECU300 front panel ..................................................................................... 4-9
Figure 4-5: MXC300 front panel ................................................................................... 4-13
Figure 4-6: Warning labels on extractor handles ......................................................... 4-13
Figure 4-7: XDM-300_100G slot capacity .................................................................... 4-15
Figure 5-1: FCU900 general view .................................................................................. 5-3
Figure 5-2: XDM-900 with air filter ................................................................................. 5-5
Figure 5-3: ECU900-F front panel .................................................................................. 5-6
Figure 5-4: ECU900 front panel ..................................................................................... 5-9
Figure 5-5: MXC900 front panel ................................................................................... 5-12
Figure 5-6: Warning labels on extractor handles ......................................................... 5-12
Figure 6-1: PIM2_21 I/O module .................................................................................... 6-5
Figure 6-2: PIM2_42 front panel .................................................................................... 6-7
Figure 6-3: PIM2_63/B I/O module ................................................................................ 6-9
Figure 6-4: PIM2_63 front panel .................................................................................. 6-11
Figure 6-5: PIM2_63S traffic cable .............................................................................. 6-12
Figure 6-6: PIM345_3 I/O module ................................................................................ 6-13
Figure 6-7: SIM1_4/E I/O module ................................................................................ 6-16
Figure 6-8: SIM 1_4/O and SIM1_4OB I/O module ..................................................... 6-18
-
8/9/2019 Xdm-100 Product Line Rm Etsi b02 8.3 En
9/325
XDM-100 Product Line Reference
Manual
List of Figures
417006-2709-0H3-B02 ECI Telecom Ltd. Proprietary vii
Figure 6-9: SIM1_8 front panel .................................................................................... 6-20
Figure 6-10: SIM4_2 I/O module .................................................................................. 6-21
Figure 6-11: SIM4_4 front panel .................................................................................. 6-23
Figure 6-12: SIM4_8 front panel .................................................................................. 6-25
Figure 6-13: SIM16_1 front panel ................................................................................ 6-27
Figure 6-14: SIM16_2 front panel ................................................................................ 6-28
Figure 6-15: SIM16_4 front panel ................................................................................ 6-30
Figure 6-16: Warning labels on extractor handles ....................................................... 6-30
Figure 6-17: SIM16_8 ports and bandwidth assignment ............................................. 6-31
Figure 6-18: SIM16_8 front panel ................................................................................ 6-32
Figure 6-19: Warning labels on extractor handles ....................................................... 6-33
Figure 6-20: SIM64_1 front panel ................................................................................ 6-34
Figure 6-21: SIM64_XFP front panel ........................................................................... 6-36
Figure 6-22: Warning labels on extractor handles ....................................................... 6-36
Figure 6-23: SIM64_2 front panel ................................................................................ 6-38
Figure 6-24: Warning labels on extractor handles ....................................................... 6-38
Figure 6-25: CRPT25_2C module ............................................................................... 6-39
Figure 6-26: CTRP25_2C module ............................................................................... 6-40
Figure 6-27: CCMB25_2D module ............................................................................... 6-41
Figure 6-28: SFP transceiver ....................................................................................... 6-42
Figure 6-29: OHU front panel ....................................................................................... 6-45
Figure 7-1: EISMB_804 front panel ............................................................................. 7-13
Figure 7-2: EISMB_840 front panel ............................................................................. 7-16
Figure 7-3: DIOM_04 front panel ................................................................................. 7-19
Figure 7-4: DIOM_08 front panel ................................................................................. 7-21
Figure 7-5: DIOM_40 front panel ................................................................................. 7-23
Figure 7-6: MCSM functional block diagram ................................................................ 7-25
Figure 7-7: MCSM front panel ...................................................................................... 7-30
Figure 8-1: XDM control plane architecture ................................................................... 8-2
Figure 8-2: ASON family software structure .................................................................. 8-7
Figure 8-3: ASON software structure ............................................................................. 8-8
Figure 8-4: ACP100 front panel ..................................................................................... 8-9
Figure 8-5: ACP900 front panel ................................................................................... 8-11
Figure 9-1: XDM-50 with TPU ........................................................................................ 9-2
Figure 9-2: XDM-100 with TPU ...................................................................................... 9-3
Figure 9-3: XDM-300 with two TPUs ............................................................................. 9-3
Figure 9-4: XDM-900 with two TPUs ............................................................................. 9-4
Figure 9-5: TC module ................................................................................................... 9-5
Figure 9-6: TCF module ................................................................................................. 9-7
-
8/9/2019 Xdm-100 Product Line Rm Etsi b02 8.3 En
10/325
List of Figures XDM-100 Product Line Reference
Manual
viii ECI Telecom Ltd. Proprietary 417006-2709-0H3-B02
Figure 9-7: TPM2_1 protection module ......................................................................... 9-9
Figure 9-8: TPM2_3 front panel ................................................................................... 9-10
Figure 9-9: TPM2_42_2 front panel ............................................................................. 9-11
Figure 9-10: TPM2_63_2 front panel ........................................................................... 9-12
Figure 9-11: TPM2_63_3 Front Panel ......................................................................... 9-13
Figure 9-12: TPMH_1 ................................................................................................... 9-14
Figure 9-13: MO_DC0_BAS front panel ...................................................................... 9-20
Figure 9-14: MO_PAS_DCM80 front panel ................................................................. 9-21
Figure 9-15: MO_OFA21 front panel ........................................................................... 9-23
Figure 9-16: MO_CMD4C module ............................................................................... 9-25
Figure 9-17: MO_CMD8 module .................................................................................. 9-26
Figure 9-18: MO_CMD4C_E module ........................................................................... 9-27
Figure 9-19: MO_CMD4SL module ............................................................................. 9-28
Figure 9-20: Typical MO_COADM1AB_xx module ...................................................... 9-29
Figure 9-21: Typical MO_COADM2AB_Gxx module ................................................... 9-30
Figure 9-22: MO_4CP4SPMM50 module .................................................................... 9-31
Figure 9-23: MO_4CP4SPMM62 module .................................................................... 9-32
Figure 9-24: MO_4CP4SPSM module ......................................................................... 9-33
Figure 10-1: xRAP-100 front panel ............................................................................ 10-37
Figure 10-2: xRAP-100 connectors ............................................................................ 10-39
Figure 10-3: xRAP-D power supply flow .................................................................... 10-40
Figure 10-4: xRAP-D front panel ................................................................................ 10-43
Figure 10-5: xRAP-D connectors ............................................................................... 10-44
Figure 10-6: Y-cable connection ................................................................................ 10-45
Figure 10-7: Double-Y cable connection .................................................................... 10-45
Figure 10-8: RAP-BG front panel ............................................................................... 10-46
Figure 10-9: RAP-4B front panel ................................................................................ 10-48
Figure 10-10: RAP-4B alarm connectors ................................................................... 10-49
Figure 10-11: xDDF-21 patch panel for unbalanced E1 interfaces............................ 10-50
Figure 10-12: Label inside xDDF-21 patch panel door .............................................. 10-50
Figure 10-13: FST top view ........................................................................................ 10-51
Figure 10-14: ODF internal view ................................................................................ 10-52
Figure 10-15: ODF front panel ................................................................................... 10-53
Figure 10-16: OPP top view ....................................................................................... 10-54
Figure 10-17: Cable guide .......................................................................................... 10-55
Figure 10-18: Fiber guide for ETSI A racks ............................................................... 10-55
Figure 10-19: PIM2_63S traffic cable box tray for above shelf installations .............. 10-56
Figure 10-20: PIM2_63S traffic cable box tray for under shelf installations .............. 10-57
Figure 10-21: Cable slack tray ................................................................................... 10-57
-
8/9/2019 Xdm-100 Product Line Rm Etsi b02 8.3 En
11/325
XDM-100 Product Line Reference
Manual
List of Figures
417006-2709-0H3-B02 ECI Telecom Ltd. Proprietary ix
Figure 11-1: 1++ protection .......................................................................................... 11-3
Figure 11-2: 1+R protection ......................................................................................... 11-4
Figure 11-3: Comprehensive protection ....................................................................... 11-6
Figure 11-4: P2MP link protection example ................................................................. 11-7
Figure 11-5: P2MP node protection example .............................................................. 11-8
Figure 11-6: H-VPLS with dual homing for access rings ............................................. 11-9
Figure 11-7: LAG scenario ......................................................................................... 11-10
Figure 11-8: Ethernet ring protection ......................................................................... 11-12
Figure 11-9: Fast IOP protection ................................................................................ 11-13
Figure 11-10: Typical SNCP-protected network sites ................................................ 11-15
Figure 11-11: SNCP-protected XDM sites ................................................................. 11-16
Figure 11-12: MSP protection modes ........................................................................ 11-19
Figure 11-13: Two-fiber protection ............................................................................. 11-21
-
8/9/2019 Xdm-100 Product Line Rm Etsi b02 8.3 En
12/325
List of Figures XDM-100 Product Line Reference
Manual
x ECI Telecom Ltd. Proprietary 417006-2709-0H3-B02
-
8/9/2019 Xdm-100 Product Line Rm Etsi b02 8.3 En
13/325
417006-2709-0H3-B02 ECI Telecom Ltd. Proprietary xi
List of TablesTable 1-1: Supported modules in basic and hybrid XDM-100 .............................. 1-13
Table 1-2: Supported modules in expanded XDM-100 ........................................ 1-14
Table 1-3: Supported modules in double-expanded XDM-100 ............................ 1-15
Table 2-1: MXC50 indicators and functions ............................................................ 2-4
Table 2-2: ECU50 indicators and functions ............................................................ 2-6
Table 2-3: ECU50-R indicators and functions ........................................................ 2-9
Table 2-4: FCU front panel LED indicators ........................................................... 2-11
Table 2-5: INF50 front panel LED indicators ........................................................ 2-13
Table 2-6:
CCP50-2 indicators and functions ....................................................... 2-14
Table 3-1:
FCU front panel LED indicators ............................................................. 3-4
Table 3-2: ECU300-F indicators and functions ....................................................... 3-7
Table 3-3: ECU100 indicators and functions .......................................................... 3-9
Table 3-4: MXC-100 indicators and functions ...................................................... 3-13
Table 3-5:
MXC-100B indicators and functions .................................................... 3-15
Table 3-6: Available aggregate module types ...................................................... 3-20
Table 3-7: SAM1_4/E front panel LED indicators ................................................. 3-21
Table 3-8: SAM1_4O/SAM1_4OB front panel LED indicators ............................. 3-22
Table 3-9: SAM4_2 front panel LED indicators .................................................... 3-23
Table 3-10: SAM16_1/SAM16_1B front panel LED indicators ............................... 3-24
Table 4-1: FCU300 front panel indicators ............................................................... 4-3
Table 4-2: ECU300-F indicators and functions ....................................................... 4-7
Table 4-3: ECU300 indicators and functions ........................................................ 4-10
Table 4-4: MXC300 indicators and functions ........................................................ 4-14
Table 5-1: FCU900 front panel indicators ............................................................... 5-3
Table 5-2: ECU900-F indicators and functions ....................................................... 5-7
Table 5-3: ECU900 indicators and functions .......................................................... 5-9
Table 5-4: MXC900 indicators and functions ........................................................ 5-13
Table 6-1:
PDH and SDH I/O modules and cards .................................................. 6-2
Table 6-2: PDH I/O module types ........................................................................... 6-4
Table 6-3: PIM2_21 modules and E1 interfaces per shelf ..................................... 6-5
Table 6-4: PIM2_21 front panel LED indicators ...................................................... 6-6
Table 6-5: PIM2_42 modules and E1 interfaces per shelf ..................................... 6-7
Table 6-6: PIM2_42 front panel LED indicators ...................................................... 6-7
Table 6-7: PIM2_63/B modules and E1 interfaces per shelf .................................. 6-8
Table 6-8: PIM2_63/B front panel LED indicators .................................................. 6-9
Table 6-9: PIM2_63S modules and E1 interfaces per shelf ................................. 6-10
-
8/9/2019 Xdm-100 Product Line Rm Etsi b02 8.3 En
14/325
List of Tables XDM-100 Product Line Reference
Manual
xii ECI Telecom Ltd. Proprietary 417006-2709-0H3-B02
Table 6-10: PIM2_63S front panel LED indicator ................................................... 6-11
Table 6-11: PIM345_3 modules and E3/DS-3/STS-1 interfaces per shelf ............. 6-13
Table 6-12:
PIM345_3 front panel LED indicators .................................................. 6-14
Table 6-13: SDH I/O module and card types .......................................................... 6-15
Table 6-14: SIM1_4/E modules and OC-3 interfaces per shelf .............................. 6-16
Table 6-15: SIM1_4/E front panel LED indicators .................................................. 6-17
Table 6-16: SIM1_4/O or SIM1_4OB modules and OC-3 interfaces per shelf ...... 6-17
Table 6-17: SIM1_4/O and SIM1_4OB front panel LED indicators ........................ 6-18
Table 6-18: SIM1_8 modules and OC-3 interfaces per shelf ................................. 6-19
Table 6-19: SIM1_8 front panel LED indicators ...................................................... 6-20
Table 6-20: SIM4_2 modules and OC-12 interfaces per shelf ............................... 6-21
Table 6-21:
SIM4_2 front panel LED indicators ...................................................... 6-22
Table 6-22: SIM4_4 modules and STM-1/4 interfaces per shelf ............................ 6-22
Table 6-23: SIM4_4 front panel LED indicators ...................................................... 6-24
Table 6-24: SIM4_8 modules and STM-1/4 interfaces per shelf ............................ 6-24
Table 6-25: SIM4_8 front panel LED indicators ...................................................... 6-25
Table 6-26: SIM16_1 modules and STM-16 interfaces per shelf ........................... 6-26
Table 6-27: SIM16_1 front panel LED indicators .................................................... 6-27
Table 6-28: SIM16_2 modules and STM-16 interfaces per shelf ........................... 6-28
Table 6-29: SIM16_2 front panel LED indicators .................................................... 6-29
Table 6-30: SIM16_4 cards and STM-16 interfaces per shelf ................................ 6-29
Table 6-31:
SIM16_4 front panel LED indicators .................................................... 6-30
Table 6-32: SIM16_8 cards and STM-16 and STM-1/4 interfaces per shelf .......... 6-32
Table 6-33: SIM16_8 front panel LED indicators .................................................... 6-33
Table 6-34: SIM64_1 cards and STM-64 interfaces per shelf ................................ 6-34
Table 6-35: SIM64_1 front panel LED indicators .................................................... 6-34
Table 6-36: SIM64_XFP cards and STM-64 interfaces per shelf ........................... 6-35
Table 6-37: SIM64_XFP front panel LED indicators ............................................... 6-36
Table 6-38:
SIM64_2 cards and STM-64 interfaces per shelf ................................ 6-37
Table 6-39: SIM64_2 front panel LED indicators .................................................... 6-38
Table 6-40:
CRPT25_2C front panel LED indicators .............................................. 6-40
Table 6-41: CTRP25_2C front panel LED indicators .............................................. 6-40
Table 6-42:
CCMB25_2D front panel LED indicators ............................................. 6-41
Table 6-43: OHU indicators and functions .............................................................. 6-46
Table 7-1: Data module types ................................................................................. 7-2
Table 7-2: EISMB_804 modules and Ethernet interfaces per shelf ..................... 7-12
Table 7-3: EISMB_804 main and protection module slots per shelf .................... 7-13
Table 7-4: EISMB_804 front panel LED indicators ............................................... 7-14
Table 7-5: EISMB_840 modules and Ethernet interfaces per shelf ..................... 7-15
-
8/9/2019 Xdm-100 Product Line Rm Etsi b02 8.3 En
15/325
XDM-100 Product Line Reference
Manual
List of Tables
417006-2709-0H3-B02 ECI Telecom Ltd. Proprietary xiii
Table 7-6: EISMB_840 main and protection module slots per shelf .................... 7-15
Table 7-7: Port cable options ................................................................................ 7-16
Table 7-8:
EISMB_840 main and protection module slots per shelf .................... 7-16
Table 7-9: DIOM_04 modules and Ethernet interfaces per shelf ......................... 7-18
Table 7-10: DIOM_04 main and protection module slots per shelf ........................ 7-18
Table 7-11: DIOM_04 front panel LED indicators ................................................... 7-19
Table 7-12: DIOM_08 modules and Ethernet interfaces per shelf ......................... 7-20
Table 7-13: DIOM_08 main and protection module slots per shelf ........................ 7-21
Table 7-14: DIOM_08 front panel LED indicators ................................................... 7-21
Table 7-15: DIOM_40 modules and Ethernet interfaces per shelf ......................... 7-22
Table 7-16: DIOM_40 main and protection module slots per shelf ........................ 7-23
Table 7-17:
Port cable options ................................................................................ 7-23
Table 7-18: DIOM_40 front panel LED indicators ................................................... 7-24
Table 7-19: MCSM port numbering and assignment .............................................. 7-26
Table 7-20: MCSM WAN port specifications .......................................................... 7-27
Table 7-21: MCSM modules and Ethernet interfaces per shelf .............................. 7-28
Table 7-22: MCSM main and protection module slots per shelf ............................. 7-28
Table 7-23: MCSM front panel LED indicators ....................................................... 7-30
Table 8-1: ACP100 front panel LED indicators and connectors ........................... 8-10
Table 8-2: ACP900 front panel LED indicators and connectors ........................... 8-12
Table 9-1: TC front panel LED indicators ............................................................... 9-6
Table 9-2:
TCF front panel LED indicators ............................................................. 9-7
Table 9-3: TPM2_1 front panel LED indicators ...................................................... 9-9
Table 9-4: TPM2_3 front panel LED indicators .................................................... 9-10
Table 9-5: TPM2_42_2 front panel LED indicators .............................................. 9-11
Table 9-6: TPM2_63_2 front panel LED indicators .............................................. 9-12
Table 9-7: TPM2_63_3 front panel LED indicators .............................................. 9-13
Table 9-8: TPMH_1 front panel LED indicators .................................................... 9-14
Table 9-9:
XDM-50 slots allocation for protection schemes ................................. 9-15
Table 9-10: XDM-100 slots allocation for protection schemes ............................... 9-16
Table 9-11:
XDM-300 slots allocation for protection schemes ............................... 9-17
Table 9-12: XDM-900 slots allocation for protection schemes ............................... 9-18
Table 9-13:
MO_DC0_BAS indicators .................................................................... 9-20
Table 9-14: MO_PAS_DCM80 indicators ............................................................... 9-22
Table 9-15: MO_OFA21 indicators ......................................................................... 9-23
Table 9-16: MO_CMD4C front panel LED indicators ............................................. 9-25
Table 9-17: MO_CMD8 front panel LED indicators ................................................ 9-26
Table 9-18: MO_CMD4C_E front panel LED indicators ......................................... 9-27
Table 9-19: MO_CMD4SL front panel LED indicators............................................ 9-28
-
8/9/2019 Xdm-100 Product Line Rm Etsi b02 8.3 En
16/325
List of Tables XDM-100 Product Line Reference
Manual
xiv ECI Telecom Ltd. Proprietary 417006-2709-0H3-B02
Table 9-20: MO_COADM1AB_xx front panel LED indicators ................................ 9-29
Table 9-21: MO_COADM2AB_Gxx front panel LED indicators ............................. 9-30
Table 9-22:
MO_4CP4SPMM50 front panel LED indicators .................................. 9-31
Table 9-23: MO_4CP4SPMM62 front panel LED indicators .................................. 9-32
Table 9-24: MO_4CP4SPSM front panel LED indicators ....................................... 9-33
Table 10-1: xRAP-100 front panel component functions ...................................... 10-38
Table 10-2: xRAP-100 connectors........................................................................ 10-39
Table 10-3: xRAP-D front panel component functions ......................................... 10-43
Table 10-4: xRAP-D connector functions ............................................................. 10-44
Table 10-5: RAP-BG front panel component functions ........................................ 10-46
Table 10-6: RAP-4B front panel component functions ......................................... 10-48
Table 10-7:
RAP-4B connector functions ............................................................. 10-49
Table 10-8: XDM-100 cables ................................................................................ 10-58
-
8/9/2019 Xdm-100 Product Line Rm Etsi b02 8.3 En
17/325
417006-2709-0H3-B02 ECI Telecom Ltd. Proprietary xv
In this chapter:
Overview .......................................................................................................... xv
Intended Audience ............................................................................................ xv
Document Organization ................................................................................... xvi
Document Conventions ................................................................................... xvi
Related Documentation ................................................................................. xviii
Obtaining Technical Documentation ............................................................. xviii
Technical Assistance ....................................................................................... xix
OverviewThe XDM®-100 Product Line Reference Manual describes the key
components of the XDM-50, XDM-100, XDM-300, and XDM-900 including
cards, modules, accessories, and related capabilities.
It also provides detailed descriptions for interpreting indicator functions,
enabling field personnel to troubleshoot hardware-related problems.
Intended AudienceThe XDM®-100 Product Line Reference Manual is intended for field and other
qualified service personnel responsible for installing the XDM-50, XDM-100,
XDM-300, and XDM-900 and their accessories.
About This Manual
-
8/9/2019 Xdm-100 Product Line Rm Etsi b02 8.3 En
18/325
About This Manual XDM-100 Product Line Reference
Manual
xvi ECI Telecom Ltd. Proprietary 417006-2709-0H3-B02
Document OrganizationThis Reference Manual contains the following information:
XDM-50, XDM-100, XDM-300, and XDM-900 shelves overview
XDM-50, XDM-100, XDM-300, and XDM-900 common cards
Cards and modules used in the three products
Tributary Protection Unit (TPU)
Accessories
Additional functionality
Document ConventionsWhen applicable, this manual uses the following conventions.
Convention Indicates Example
Bold Names of windows, dialog boxes, menus, buttons, and
most other GUI elements
On the Alarms menu...
Menu > Option Selection from a menu, or
leading to anothercommand
Select Update > View
Objects
Italics New terms, emphasizedtext, and names of manualsand documents
Examples in text
Borders around text Notes, cautions, andwarnings
See examples below
-
8/9/2019 Xdm-100 Product Line Rm Etsi b02 8.3 En
19/325
XDM-100 Product Line Reference
Manual
About This Manual
417006-2709-0H3-B02 ECI Telecom Ltd. Proprietary xvii
NOTE: Text set off in this manner presents clarifying
information, specific instructions, commentary, sidelights, orinteresting points of information.
CAUTION: Text set off in this manner indicates that failure tofollow directions could result in damage to equipment or lossof information.
WARNING: Text set off in this manner indicates that failureto follow directions could result in bodily harm or loss of life.
LASER WARNING: Text set off in this manner indicates howto avoid personal injury. All personnel involved in equipmentinstallation, operation, and maintenance must be aware thatlaser radiation is invisible. Therefore, although protectivedevices generally prevent direct exposure to the beam, personnel must strictly observe the applicable safety
precautions and, in particular, must avoid staring into opticalconnectors, either directly or using optical instruments.
ESD: Text set off in this manner indicates information onhow to avoid discharge of static electricity and subsequentdamage to the unit.
TIP: Text set off in this manner includes helpful informationand handy hints that can make your task easier.
IMPORTANT: Text set off in this manner presents essentialinformation to which you must pay attention.
-
8/9/2019 Xdm-100 Product Line Rm Etsi b02 8.3 En
20/325
About This Manual XDM-100 Product Line Reference
Manual
xviii ECI Telecom Ltd. Proprietary 417006-2709-0H3-B02
Related DocumentationThe following publications may be of assistance to you in the installation and
commissioning processes of the XDM-100 Product Line:
Multiservice Packet-Optical Transport Platform General Description
XDM-50 Installation and Maintenance Manual
XDM-100 Installation and Maintenance Manual
XDM-300 Installation and Maintenance Manual
XDM-900 Installation and Maintenance Manual
EMS-XDM User Manual
LightSoft®
User Manual
Obtaining Technical
DocumentationTo obtain technical documentation related to ECI Telecom products, contact:
ECI Telecom Ltd.
Documentation Department
30 Hasivim St.
Petach Tikva 49130Israel
Fax: +972-3-9268060
Email: [email protected]
-
8/9/2019 Xdm-100 Product Line Rm Etsi b02 8.3 En
21/325
XDM-100 Product Line Reference
Manual
About This Manual
417006-2709-0H3-B02 ECI Telecom Ltd. Proprietary xix
Technical AssistanceThe configuration, installation, and operation of the XDM-100 Product Line
and its operation in a network are highly specialized processes. Due to the
different nature of each installation, some planning aspects may not be covered
in this manual.
If you have questions or concerns about your network design or if you require
installation personnel to perform the actual installation process, ECI Telecom
maintains a staff of design engineers and highly trained field service personnel.
The services of this group are available to customers at any time.
If you are interested in obtaining design assistance or a network installation
plan from ECI Telecom's Customer Support team, contact your ECI Telecom
sales representative. With any support related issues, technical or logistic,
contact the ECI Telecom Customer Support center at your location or our
central customer support center action line at:
Telephone +972-3-9266000
Telefax +972-3-9266370
Email [email protected]
ECI Telecom's XDM and BroadGate® product lines arecertified to comply with MEF9 and MEF14 standards.
ECI Telecom's qualification lab is accredited by A2LA forcompetence in electrical testing according to the InternationalStandard ISO IEC 17025-2005 General Requirements for theCompetence of Testing and Calibration Laboratories.
mailto:[email protected]:[email protected]:[email protected]
-
8/9/2019 Xdm-100 Product Line Rm Etsi b02 8.3 En
22/325
About This Manual XDM-100 Product Line Reference
Manual
xx ECI Telecom Ltd. Proprietary 417006-2709-0H3-B02
-
8/9/2019 Xdm-100 Product Line Rm Etsi b02 8.3 En
23/325
417006-2709-0H3-B02 ECI Telecom Ltd. Proprietary 1-1
In this chapter:
XDM-50 Platform Overview ........................................................................... 1-2
XDM-50 Shelf Options ................................................................................... 1-3
XDM-100 Platform Overview ......................................................................... 1-5
XDM-100 Shelf Configurations ...................................................................... 1-6
XDM-100 I/O Protection Options ................................................................... 1-8
XDM-100H Overview ................................................................................... 1-10
XDM-300 Platform Overview ....................................................................... 1-16
XDM-300 I/O Protection Options ................................................................. 1-17
XDM-900 Platform Overview ....................................................................... 1-23 XDM-900 I/O Protection Options ................................................................. 1-25
DCC Functionality ......................................................................................... 1-30
Management Architecture ............................................................................. 1-33
1
Introduction
-
8/9/2019 Xdm-100 Product Line Rm Etsi b02 8.3 En
24/325
Introduction XDM-100 Product Line Reference
Manual
1-2 ECI Telecom Ltd. Proprietary 417006-2709-0H3-B02
XDM-50 Platform OverviewECI Telecom's XDM-50 is a miniature add/drop multiplexer optimized
especially for metro-access and cellular networks.
The XDM-50 compact multiservice platform delivers a cost-effective and
affordable mix of Ethernet, SDH and PDH services, resulting in new revenue-
generating opportunities. It offers a wide variety of features and benefits,
including:
Highly cost-effective, redundant, and flexible ADM-1/4 and TM-1/4
solution in line with the XDM build-as-you-grow architecture™, providing
significant savings in both OPEX and CAPEX.
Minimal physical size, broad flexibility, and scalability.
Operational within an extended range of environmental conditions.
Ample versatility, supporting PDH, SDH, and Ethernet interfaces and
services.
Compatible with XDM family counterparts, including most I/O TPU and
SFP modules.
Upgradable to SDH/CWDM sublambda grooming for transporting SAN
and data services in the metro-access portion of the network.
The XDM-50 is compact and resilient, making it perfectly suited for both
indoor and outdoor enclosures. Due to its extended operating temperature
range, it is also well suited for harsh environmental conditions.The XDM-50 shelf was designed to facilitate simple installation and
maintenance. Hot insertion of cards and modules is allowed, supporting quick
maintenance and repair without affecting traffic.
For a detailed description of the XDM-50 platform, see the Multiservice
Packet-Optical Transport Platform General Description.
Figure 1-1: XDM-50 shelf
-
8/9/2019 Xdm-100 Product Line Rm Etsi b02 8.3 En
25/325
XDM-100 Product Line Reference
Manual
Introduction
417006-2709-0H3-B02 ECI Telecom Ltd. Proprietary 1-3
XDM-50 Shelf OptionsThe XDM-50 boasts an extremely high modular structure and is offered in two
shelf configurations:
Basic XDM-50 shelf with two identical MXC50 (Main Cross Connect)
cards for supporting system redundancy.
The lower part of the shelf consists of the INF50 redundant input DC
modules and the External Connection Unit (ECU50/ECU50-R). Above are
the MXC50 cards and the CCP50-2 connection and I/O protection module.
The upper part of the shelf consists of the modules cage which houses up to
four I/O modules. Various types of interface modules supporting PDH,
SDH, and data services are available.
All electrical connections are located directly in the tributary modules;
therefore, the XDM-50 does not need additional electrical interface
connections.
The FCU50 (Fan Control Unit) at the right of the shelf provides cooling air
to the system. It contains six separate fans for added system redundancy.
Air is drawn in by the fans from the right side of the chassis and exhausted
through the horizontally mounted cards and modules and the left side of the
chassis. Redundant controllers, located on the two MXC50 cards, activate
the fans.
In case of failure of one of the fans, the remaining fans provide redundancy
and start to operate in turbo mode until the FCU50 is replaced. The FCU50can be extracted and replaced without interrupting the multiplexer
operation, provided the replacement does not exceed a few minutes.
The basic XDM-50 cage contains slots for I/O interface modules and
dedicated slots for the MXC50 cards, the CCP50-2, INF50, FCU50, and
ECU50/ECU50-R. The cage's design and mechanical practice conform to
international mechanical standards and specifications.
The module and card slots are distributed as follows:
Four (4) slots, I1 to I4, optimally allocated for I/O interface modules
One (1) slot allocated for the ECU50 or ECU50-R card
The ECU50 or ECU50-R card is located beneath the MXC50 cards. Itsfront panel features several interface connectors for management, external
timing, alarms, and orderwire. It also includes alarm severity colored LED
indicators.
-
8/9/2019 Xdm-100 Product Line Rm Etsi b02 8.3 En
26/325
Introduction XDM-100 Product Line Reference
Manual
1-4 ECI Telecom Ltd. Proprietary 417006-2709-0H3-B02
Expanded XDM-50 shelf consists of the XDM-50 basic shelf and the TPU
expansion shelf mounted on top, to add protection of electrical I/O
modules.The TPU is a single-shelf cage with slots for the Tributary Protection
Modules (TPMs), and a Tributary Control (TC) or Tributary Control and
Fan (TCF) module. The modules are distributed as follows:
Four (4) slots flexibly allocated for TPMs (single-slot or double-slot
modules are supported)
One (1) slot allocated for the TC or TCF module
Each TPM is connected to the operating and protection modules of the
XDM-50 shelf respectively. If a failure is detected in one of the operating
I/O modules, the XDM-50 control system sends control signals to the
appropriate TPM to switch traffic from the operating I/O module to the protection module. Several types of TPM modules for 1:1, 1:2, or 1:3
protection schemes are supported.
The TC or TCF is connected to the DC and control buses of the MXC50
cards via the TPU backplane. It controls the switching of traffic from the
main to protection I/O module by relays in the corresponding TPM. In
addition, the optional TCF has three fans that provide cooling air to the
modules installed in the TPU.
The TPU is a 231 mm deep, 443 mm wide, and 75 mm high unit. It
connects to a connector on top of the XDM-50 shelf that provides the
power and control buses required for its operation. When the TPU is not
installed, a protection cap covers this connector.
Figure 1-2: Basic XDM-50 shelf layout
-
8/9/2019 Xdm-100 Product Line Rm Etsi b02 8.3 En
27/325
XDM-100 Product Line Reference
Manual
Introduction
417006-2709-0H3-B02 ECI Telecom Ltd. Proprietary 1-5
XDM-100 Platform OverviewECI Telecom's XDM-100 compact multiservice platform delivers a cost-
effective and affordable mix of Ethernet, SDH, and PDH services, resulting in
new revenue-generating opportunities. It offers a wide variety of features and
benefits, including:
Gradual in-service capacity expansion based on service provisioning needs.
An optical connection operating at a specific STM rate can be upgraded
from STM-1 to STM-4/STM-16 without affecting traffic.
Sublambda grooming enabling high utilization of existing fibers and top
efficiency in transmission of different types of services.
Multi-ADM and cross-connect functionality for deployment in flexible
network topologies, such as ring, mesh, and star.
The XDM-100 is compact and resilient. Due to its extended operating
temperature range, it is well suited to harsh environmental conditions.
The XDM-100 shelf was designed to facilitate simple installation and
maintenance. Hot insertion of cards and modules is allowed, supporting quick
maintenance and repair without affecting traffic.
For a detailed description of the XDM-100 platform, see the Multiservice
Packet-Optical Transport Platform General Description.
Figure 1-3: XDM-100 shelf
-
8/9/2019 Xdm-100 Product Line Rm Etsi b02 8.3 En
28/325
Introduction XDM-100 Product Line Reference
Manual
1-6 ECI Telecom Ltd. Proprietary 417006-2709-0H3-B02
XDM-100 Shelf ConfigurationsThe XDM-100 shelf is available in the following shelf configurations:
Pure MSPP (also known as XDM-100) for pure SDH and data services.
By default, the pure MSPP is configured with two matrix cards and an
optional TPU shelf. The pure SDH platform may be configured with two
matrix cards or, alternatively, with a single matrix card and a single MXC-
BR card. The exact configuration can be tailored to meet specific client
requirements.
Converged MSPP/CWDM platform (also known as XDM-100H)
supports the complete range of SDH and data services and adds CWDM
functionality, serving as a single converged platform for both data and
optical features. By default, the converged platform is configured with two
matrix cards and a TPU/OCU (Optical CWDM Unit) shelf. A second
optional TPU is also available. The exact configuration can be tailored to
meet specific client requirements.
Pure CWDM platform (also known as XDM-200) focuses on pure
CWDM optical services. By default, the pure CWDM platform is
configured with one matrix card and a TPU/OCU shelf. As with all XDM
platforms, the exact configuration can be tailored to meet specific client
requirements.
Pure SDH MSPP Configuration (XDM-100)In its maximum configuration, the pure SDH MSPP accommodates thefollowing modules:
Eight (8) slots, I1 to I8, allocated for I/O interface modules.
Two (2) slots, A and B respectively, allocated for the MXC cards (main and
protection). Each MXC card has two slots (A1 and A2 and B1 and B2) to
accommodate SDH aggregate modules.
One (1) slot allocated for the ECU card.
A TPU single-shelf cage with slots for the TPMs and TC or TCF modules.
The modules are distributed as follows:
Four (4) slots flexibly allocated for TPMs (single-slot or double-slot
modules are supported).
One (1) slot allocated for the TC or TCF module.
-
8/9/2019 Xdm-100 Product Line Rm Etsi b02 8.3 En
29/325
XDM-100 Product Line Reference
Manual
Introduction
417006-2709-0H3-B02 ECI Telecom Ltd. Proprietary 1-7
Converged MSPP/CWDM Configuration
(XDM-100H)The converged configuration of the XDM-100 integrates the modularity
features of both the pure MSPP and the pure CWDM:
Pure MSPP XDM-100 shelf, as described in Pure SDH MSPP
Configuration (XDM-100) (page 1-6), including:
ECU
Two (2) MXC-100/B cards
I/O modules cage with eight slots as described in Pure SDH MSPP
Configuration (XDM-100) (page 1-6)
FCU
TPU/OCU mounted on top of the basic shelf. Either one or two TPU/OCU
units may be mounted on top of the shelf, including:
Four (4) slots for supporting any mix of Mux/DeMux, splitter/coupler,
OADM, optical amplifiers, or TPM modules
One (1) TC or TCF module for carrying the power and control from the
main shelf to the TPU/OCU backplane
-
8/9/2019 Xdm-100 Product Line Rm Etsi b02 8.3 En
30/325
Introduction XDM-100 Product Line Reference
Manual
1-8 ECI Telecom Ltd. Proprietary 417006-2709-0H3-B02
XDM-100 I/O Protection OptionsThe XDM-100 shelf boasts an extremely high modular structure and can be
configured with or without I/O protection:
Basic XDM-100 shelf housed in a compact equipment cage. I/O protection
is not supported in this option.
Expanded XDM-100 with I/O protection. A TPU is mounted on top of the
basic shelf providing protection to the I/O modules.
Double-expanded XDM-100 shelf with I/O protection and enhanced
CWDM networking capabilities. An OCU is mounted on top of the
expanded XDM-100 shelf and provides increased CWDM networking
functions in addition to I/O protection.
NOTE: It is recommended that the XDM-100 shelf beinstalled in an ETSI A rack (2200 mm or 2600 mm). However,
it can also be installed in 19" 600 mm depth racks (without airfilters) that have been approved by ECI Telecom. (For detailedinformation about ETSI A racks, see section Rack Installationin the XDM-100 IMM.)
Basic XDM-100 Shelf
The basic XDM-100 shelf is housed in a 231 mm (9.1 in.) deep, 443 mm(17.44 in.) wide, and 200 mm (7.87 in.) high equipment cage. The lower part of
the shelf consists of the card cage and accommodates the MXC cards (main
and protection) and the ECU. The upper part of the shelf consists of the module
cage and houses up to eight I/O modules.
I/O protection is not supported in this option.
Figure 1-4: Basic XDM-100 shelf
-
8/9/2019 Xdm-100 Product Line Rm Etsi b02 8.3 En
31/325
XDM-100 Product Line Reference
Manual
Introduction
417006-2709-0H3-B02 ECI Telecom Ltd. Proprietary 1-9
Expanded XDM-100 with I/O Protection
A TPU is mounted on top of the basic shelf and provides protection to the I/Omodules. Each TPM is connected to both operating and protection I/O modules
in the shelf in a 1:1, 1:2, or 1:3 configuration. If a failure is detected in one of
the operating I/O modules, the active MXC via the TC module in the TPU
switches the traffic from the active I/O module to the protection module.
Figure 1-5: Expanded XDM-100 shelf
Double-Expanded XDM-100An OCU is mounted on top of the expanded XDM-100 shelf. This option
provides I/O protection as the expanded XDM-100, and adds CWDMnetworking capabilities to the XDM-100.
Figure 1-6: Double-expanded XDM-100 shelf
-
8/9/2019 Xdm-100 Product Line Rm Etsi b02 8.3 En
32/325
Introduction XDM-100 Product Line Reference
Manual
1-10 ECI Telecom Ltd. Proprietary 417006-2709-0H3-B02
XDM-100H OverviewThe XDM-100H integrates the Ethernet, SDH, and PDH capabilities of the
XDM-100 with the Coarse Wavelength Division Multiplexing (CWDM)
functionality of the XDM-200. It is compact, fully modular, and redundant.
NOTE: The XDM-100H is a cost option and can only beimplemented if your XDM-100 is licensed appropriately.
A TPU/OCU shelf can be mounted on top of the XDM-100 basic shelf to add
I/O protection and optical CWDM networking capabilities. The TPU/OCU is
identical in physical dimensions to the TPU and supports any mix of TPMs,
OADMs, Mux/DeMux, and couplers/splitters. Up to two TPU/OCU shelvescan be installed on the basic XDM-100 shelf.
Due to the high capacity of the traffic carried by the XDM-100H, protection is
of the utmost importance. The protection mechanisms incorporated into the
system ensure traffic reliability. These include hardware redundancy of
specified critical circuits, highly reliable trail protection mechanisms, and
Optical Channel (OCH) 1+1 protection and Optical Multiplex Section
Protection (OMSP) for line protection.
-
8/9/2019 Xdm-100 Product Line Rm Etsi b02 8.3 En
33/325
XDM-100 Product Line Reference
Manual
Introduction
417006-2709-0H3-B02 ECI Telecom Ltd. Proprietary 1-11
XDM-100H Description
The XDM-100H consists of the following units:
Basic XDM-100 shelf as described in Basic XDM-100 Shelf (page 1-8).
The shelf includes the ECU or ECU-F, two MXC cards, the I/O modules
cage with eight slots, and the FCU.
Each MXC houses an NVM module which contains the licensed optional
software.
The eight slots of the I/O modules cage support installation of XDM-100
I/O modules, as well as XDM-200 CWDM I/O modules (transponders and
combiners).
A TPU/OCU shelf mounted on top of the basic XDM-100 shelf with five
slots: four for supporting any mix of Mux/DeMux, OADM,
splitters/couplers, and TPMs, and one for a TC module. One or two
TPU/OCUs can be mounted on the basic XDM-100 shelf.
NOTE: When two TPU/OCUs are installed, the second(upper) TPU/OCU does not support low order (E1 or DS-1)signals due to cabling limitations.
Figure 1-7: XDM-100 with a TPU/OCU shelf
-
8/9/2019 Xdm-100 Product Line Rm Etsi b02 8.3 En
34/325
Introduction XDM-100 Product Line Reference
Manual
1-12 ECI Telecom Ltd. Proprietary 417006-2709-0H3-B02
XDM-100H Configuration Options
The XDM-100H has three configuration options:
Basic shelf
Expanded shelf (with one TPU/OCU)
Double-expanded shelf (with one TPU/OCU and one OCU)
All these options can be configured based on the type of system license
purchased.
TPU/OCU slots designation
One or two TPU/OCUs can be mounted on top of the basic XDM-100. Thecage on top of the basic shelf is designated M1; the cage on top of the M1 cage
is designated M2.
Slots in M1 are M1-1 to M1-5.
Slots in M2 are M2-1 to M2-5.
Figure 1-8: TPU and OCU slots designation
When the hybrid option is enabled, the M1 cage is designated TPU/OCU. It
can accommodate any mix of TPM and CWDM modules. The M2 cage is
always designated OCU and can accommodate only CWDM modules.
-
8/9/2019 Xdm-100 Product Line Rm Etsi b02 8.3 En
35/325
XDM-100 Product Line Reference
Manual
Introduction
417006-2709-0H3-B02 ECI Telecom Ltd. Proprietary 1-13
Assignment options for TPU/OCU cages
The following figure shows the layout of the basic XDM-100 shelfconfiguration.
Figure 1-9: Basic XDM-100
Table 1-1: Suppor ted modules in basic and hybrid XDM-100
I/O modules cage slots I1 to I8
Regular Hybrid
Only XDM-100 I/O modules (PIMs,SIMs, EISMBs, EISMs, DIOMs)
Any mix of I/O modules (PIMs, SIMs,EISMBs, EISMs, DIOMs) and CWDMmodules (transponders and combiners)
-
8/9/2019 Xdm-100 Product Line Rm Etsi b02 8.3 En
36/325
Introduction XDM-100 Product Line Reference
Manual
1-14 ECI Telecom Ltd. Proprietary 417006-2709-0H3-B02
The following figure shows the layout of the expanded XDM-100 shelf
configuration.
Figure 1-10: Expanded XDM-100
Table 1-2: Suppor ted modules in expanded XDM-100
I/O modules cage slots I1 to I8 M1 modules cage slots M1-1 to M1-4
Regular Hybrid Regular Hybrid
Only XDM-100I/O modules(PIMs, SIMs,EISMBs, EISMs,DIOMs)
Any mix of I/Omodules (PIMs,SIMs, EISMBs,EISMs, DIOMs) andCWDM modules
(transponders andcombiners)
Only TPMs Any mix of TPM andCWDM opticalmodules (Mux/DeMux,
splitters/couplers,OADM)
NOTE: Slot M1-5 can accommodate TC modules only.
-
8/9/2019 Xdm-100 Product Line Rm Etsi b02 8.3 En
37/325
XDM-100 Product Line Reference
Manual
Introduction
417006-2709-0H3-B02 ECI Telecom Ltd. Proprietary 1-15
The following figure shows the layout of the double-expanded XDM-100 shelf
configuration.
Figure 1-11: Double-expanded XDM-100
Table 1-3: Suppor ted modules in double-expanded XDM-100
I/O modu les cage slot s I1 to I8 M1 modu les cage slot s M1-1 toM1-4
M2 modules cage slots M2-1to M2-4
Regular Hybrid Regular Hybrid Regular Hybrid
Only I/O
modules (PIMs,
SIMs, EISMBs,EISMs, DIOMs)
Any mix of I/O
modules (PIMs,
SIMs, EISMBs,EISMs,
DIOMs) and
CWDMmodules
(transponders
and combiners)
Only TPMs Any mix of TPM
and CWDMoptical modules
(Mux/DeMux,
splitters/couplers,
OADM)
-- Only CWDM
optical modules(Mux/DeMux,
splitters/couplers,
OADM)
NOTE: Slots M1-5 and M2-5 can accommodate TC modulesonly.
-
8/9/2019 Xdm-100 Product Line Rm Etsi b02 8.3 En
38/325
Introduction XDM-100 Product Line Reference
Manual
1-16 ECI Telecom Ltd. Proprietary 417006-2709-0H3-B02
XDM-300 Platform OverviewECI Telecom's XDM-300 is a powerful flexible MSPP optimized for metro
networks. It supports multitude technologies in a cost-effective fashion to
address the market increasing traffic demands.
The XDM-300 supports scalable STM-1/4/16/64/OTN aggregates and flexible
access topologies. It offers a wide range of features and benefits including:
Carrier class Ethernet as well as traditional SDH voice-centric services.
Gradual in-service capacity expansion based on service provisioning needs.
An optical connection operating at a specific STM rate can be upgraded
from STM-1 to STM-4/STM-16/STM-64 without affecting traffic.
Sublambda grooming resulting in high utilization of existing fibers and top
efficiency in transmission of different types of services.
Supporting CWDM, OADM, transponder, combiner, OFA, and other
optical cards and modules used to process, amplify, and monitor
multichannel signals.
The XDM-300 shelf was designed to facilitate simple installation and
maintenance. Hot insertion of cards and modules is allowed, supporting quick
maintenance and repair without affecting traffic.
For a detailed description of the XDM-300 platform, see XDM General
Description.
Figure 1-12: XDM-300 shelf
-
8/9/2019 Xdm-100 Product Line Rm Etsi b02 8.3 En
39/325
XDM-100 Product Line Reference
Manual
Introduction
417006-2709-0H3-B02 ECI Telecom Ltd. Proprietary 1-17
XDM-300 I/O Protection OptionsThe XDM-300 features an extremely high modular structure and can be
configured with or without I/O protection:
Basic XDM-300 shelf housed in a compact equipment cage. I/O protection
is not supported in this option.
Expanded XDM-300 with I/O protection as follows:
A TPU mounted on top of the basic shelf, providing protection to the
I/O modules in the upper module cage.
A TPU mounted at the bottom of the basic shelf, providing protection
to the I/O modules in the lower module cage.
Two TPUs mounted, one on top and one at the bottom of the basic
shelf, providing protection to the I/O modules installed in both the
upper and the lower module cages.
Expanded XDM-300 shelf with I/O protection and enhanced CWDM
networking capabilities. Two TPUs mounted one on top of the basic shelf
and one under it, for I/O protection. In addition, an OCU is mounted on top
of the upper TPU, which provides increased CWDM networking functions.
Basic XDM-300 ShelfThe basic XDM-300 shelf is housed in a 246 mm (9.68 in.) deep, 443 mm
(17.44 in.) wide, and 350 (13.78 in.) mm high equipment cage. The upper partof the shelf consists of a module cage (upper module cage) and houses up to
eight I/O modules. In the middle of the shelf is a card cage that accommodate
the MXC300 cards (main and protection), the External Connection Unit
(ECU300), and up to two I/O cards. The lower part of the shelf consists of an
additional module cage (lower module cage) that can be equipped with up to
eight I/O modules.
I/O protection is not supported in this option.
-
8/9/2019 Xdm-100 Product Line Rm Etsi b02 8.3 En
40/325
Introduction XDM-100 Product Line Reference
Manual
1-18 ECI Telecom Ltd. Proprietary 417006-2709-0H3-B02
The XDM-300 shelf can be installed in a horizontal or vertical position.
Figure 1-13: Basic XDM-300 shelf, horizontal i nstallation
-
8/9/2019 Xdm-100 Product Line Rm Etsi b02 8.3 En
41/325
XDM-100 Product Line Reference
Manual
Introduction
417006-2709-0H3-B02 ECI Telecom Ltd. Proprietary 1-19
Figure 1-14: Basic XDM-300 shelf, vertical Ins tallation
-
8/9/2019 Xdm-100 Product Line Rm Etsi b02 8.3 En
42/325
Introduction XDM-100 Product Line Reference
Manual
1-20 ECI Telecom Ltd. Proprietary 417006-2709-0H3-B02
Expanded XDM-300 with I/O Protection
TPUs can be attached to the XDM-300 shelf to protect installed I/O modules.Each TPM is connected to both operating and protection I/O modules in the
shelf in a 1:1, 1:2, or 1:3 configuration. If a failure is detected in one of the
operating I/O modules, the active MXC300/MXC900 via the TC module in the
TPU switches the traffic from the active I/O module to the protection module.
Several protection configurations are possible:
A TPU mounted on top of the basic shelf, protects I/O modules residing in
the upper module cage.
A TPU mounted at the bottom of the basic shelf, protects I/O modules
installed in the lower module cage.
Two TPUs mounted one on top and one at the bottom of the basic shelf,
provide protection to I/O modules in both the upper and lower module
cages.
Figure 1-15: XDM-300 with TPU on top
-
8/9/2019 Xdm-100 Product Line Rm Etsi b02 8.3 En
43/325
XDM-100 Product Line Reference
Manual
Introduction
417006-2709-0H3-B02 ECI Telecom Ltd. Proprietary 1-21
Figure 1-16: XDM-300 with TPUs on top and at the bottom
-
8/9/2019 Xdm-100 Product Line Rm Etsi b02 8.3 En
44/325
Introduction XDM-100 Product Line Reference
Manual
1-22 ECI Telecom Ltd. Proprietary 417006-2709-0H3-B02
Expanded XDM-300 with CWDM Networking
CapabilitiesAn OCU can be mounted on top of a basic XDM-300 shelf or on top of an
expanded shelf to add enhanced CWDM networking capabilities to the
platform.
NOTE: An OCU is not supported at the bottom of the XDM-300 shelf.
Figure 1-17: XDM-300 with two TPUs and an OCU
-
8/9/2019 Xdm-100 Product Line Rm Etsi b02 8.3 En
45/325
XDM-100 Product Line Reference
Manual
Introduction
417006-2709-0H3-B02 ECI Telecom Ltd. Proprietary 1-23
XDM-900 Platform Overvi