Page 1: manual lengkap ABC 33kV

MANUAL PEPASANGAN HV

ABC 33kV

MANUAL PEPASANGAN HV

ABC 33kV

Perak Sentiasa Bersinar

Page 2: manual lengkap ABC 33kV

AKSESORI TALIAN ABC 33kV

AKSESORI TALIAN ABC 33kV

Perak Sentiasa Bersinar

Page 3: manual lengkap ABC 33kV

LV SUSPENSION CLAMPHV SUSPENSION

CLAMP

LV DEAD END CLAMP

HV DEAD END CLAMP

AKSESORI TALIAN ABC 33KV

Page 4: manual lengkap ABC 33kV

J HOOK

TRIANGULAR BREAKET

AKSESORI TALIAN ABC 33KV

UNIVERSAL BAND

Page 5: manual lengkap ABC 33kV

CABLE SLAB CONCRETE (33KV)

KABEL ABC 33KV 3x150mmp+70mmp- 500m/drum

AKSESORI TALIAN ABC 33KV

TIANG SPUN 10m 5kN

Page 6: manual lengkap ABC 33kV

KAEDAH PENOMBORAN

TIANG 10 mTALIAN ABC 33kV

KAEDAH PENOMBORAN

TIANG 10 mTALIAN ABC 33kV

Perak Sentiasa Bersinar

Page 7: manual lengkap ABC 33kV

CONTOH PENOMBORAN TIANG ABC 33KV

TIANG SESALUR LURUS / TAMATAN/SUDUT

TIANG SAMBUNGAN TERUS

Page 8: manual lengkap ABC 33kV

DANGERHV 33kV

• Ukuran 15cm x 30cm• Latarbelakang - putih• Tulisan dan logo - merah• Mesti dilekatkan pada

semua tiang

LABEL A - DANGER

Page 9: manual lengkap ABC 33kV

TEL: 15454

LMT - PR

234

Cat MerahCat Biru

• Ukuran 15cm x 30cm• Latarbelakang Hitam• Tulisan Putih• No. bersiri bermula dari

LMT-PR 234• No. Tel - tulisan Hitam• Merah - cat Tenaga Red• Biru - cat Tenaga Blue

• Lain-lain: Rujuk Edaran Kejuruteraan Bil 61/96

LABEL B – NOMBOR PADA TIANG

Page 10: manual lengkap ABC 33kV

TEL: 15454

LMT - PR

JOINT NO: 1258

Cat Merah

Cat Biru

• Ukuran 15cm x 30cm• Latarbelakang hitam• Tulisan Putih• No. tiang bersiri bermula dari

LMT-PR 234• No. Joint bersiri bermula dari

LMT-PR 234• No. Tel tulisan hitam• Merah cat Tenaga Red• Biru cat Tenaga Blue

• Lain-lain: Rujuk Edaran Kejuruteraan Bil 61/96

LABEL C – TIANG SAMBUNGAN

Page 11: manual lengkap ABC 33kV

KAEDAH MENANAM TIANG 10m 5kN

MENGGUNAKAN KREN AUGER

KAEDAH MENANAM TIANG 10m 5kN

MENGGUNAKAN KREN AUGER

Perak Sentiasa Bersinar

Page 12: manual lengkap ABC 33kV

LUBANG TIANG DIKOREK MENGGUNAKAN KREN AUGERSEDALAM 1.7m

TIANG TELAH SELESAI DITANAM

TIANG DIANGKUT DAN DITANAM/DITEGAKKAN MENGGUNAKAN KREN AUGER

KAEDAH MENANAM TIANG 10m 5kN MENGGUNAKAN KREN AUGER

Page 13: manual lengkap ABC 33kV

PERATURAN KESELAMATAN LALULINTAS HENDAKLAH DI PATUHI APABILA KERJA-KERJA DILAKUKAN DI TEPI JALAN MENGIKUT

PERATURAN KESELAMATAN LALULINTAS OLEH SPESIFIKASI JKR

KAEDAH MENANAM TIANG 10m 5kN

MENGGUNAKAN KREN AUGER

Page 14: manual lengkap ABC 33kV

SAMBUNGAN TAMATAN KABEL

HV ABC

SAMBUNGAN TAMATAN KABEL

HV ABC

Perak Sentiasa Bersinar

Page 15: manual lengkap ABC 33kV

4.2 SAMBUNGAN TAMATAN KABEL HV ABC

TERMINAL LUG

INSULATION SLEEVE

SHED

SAMBUNGAN TAMATAN YANG TELAH SIAP SEDANG DIUJI DENGAN 5kV MEGGER

(UJIAN PENGENALAN FASA-BACAAN =0 ohmUJIAN PENEBATAN -BACAAN >1000M ohm)

SAMBUNGAN TAMATAN YANG TELAH SIAP

MEGGER 5kV

Page 16: manual lengkap ABC 33kV

SAMBUNGAN TAMATAN KABEL

HV ABC PADA ALATSUIS 33KV

SAMBUNGAN TAMATAN KABEL

HV ABC PADA ALATSUIS 33KV

Perak Sentiasa Bersinar

Page 17: manual lengkap ABC 33kV

TAMATAN KABEL HV ABC PADA ALATSUIS 33KV

TAMATAN KABEL

DISAMBUNGKAN

PADA ALATSUIS

(CIRCUIT)

LUBANG KABELMASUK DITUTUPRAPI

DI DALAM’CABLE BOX’ALATSUIS 33KV

DI DALAM ALATSUIS 33KV

Page 18: manual lengkap ABC 33kV

TAMATAN KABEL HV ABC PADA ALATSUIS 33KV

PANDANGAN DARI BAWAH

(CABLE CELLER)

- DITUTUP KEMAS

- KABEL DITANDAKAN R,Y,B- EARTH WIRE DISATUKAN & DIBUMIKAN

-TIADA LINK BOX

Page 19: manual lengkap ABC 33kV

TIANG SPUN 10-5kNTIANG SPUN 10-5kN

Perak Sentiasa Bersinar

Page 20: manual lengkap ABC 33kV

5.1 REKABENTUK TIANG SPUN 10m – 5kN

1) PANJANG TIANG = 10m

2) TIANG DITANAM PADA KEDALAMAN 1.7m DARI PARAS TANAH

3) PANJANG TIANG DARI PARAS ATAS TANAH = 8.3m

JENIS TIANG

TAHAN PJG TIANG

GARIS PUSAT ATAS TIANG (mm)

TEBAL (mm)

GARIS PUSAT BAWAH TIANG

PJG DALAM TANAH (m)

BERAT (kg)

10m

19-5kN

5.0kN 10.0 190 42 323 1.70 730

10m 8.3m

1.7m DITANAM

Page 21: manual lengkap ABC 33kV

5.2 PEMASANGAN

TIANG SPUN 10m-5kN MENAMPUNG PEPASANGAN MAKSIMUN- 2 LITAR HV ABC- 2 LITAR LV ABC

H V A B CH V A B C

LV A B CLV A B C

Page 22: manual lengkap ABC 33kV

5.3& 5.4 EARTWIRE DAN PEMBUMIAN

-EARTHWIRE DI DALAM TIANG DISEDIAKAN UNTUK MEMBUMIKAN DAWAI NEUTRAL DAN AKSESORI SISTEM LV ABC SAHAJA

-TAMBAHAN EARTHWIRE YANG BERASINGAN DIGUNAKAN UNTUK MEMBUMIKAN SAMBUNGAN (EARTH BONDING JOINT) SAHAJA.

- PEMASANGAN EARTH WIRE INI KEPADA HV ABC MESSENGER WIRE ATAU AKSESORI HV ABC ADALAH TIDAK DIBENARKAN.

EARTHING WIRE DI LUAR TIANG UNTUK SAMBUNGAN (EARTH BONDING JOINT)

Page 23: manual lengkap ABC 33kV

HV DEAD END

CLAMP

HV DEAD END

CLAMP

Perak Sentiasa Bersinar

Page 24: manual lengkap ABC 33kV

6.1 REKABENTUK DAN PEMASANGAN HV DEAD END CLAMP

FUNGSI :– MEMEGANG DAN MENAHAN HUJUNG MESSENGER

WIRE DALAM KEADAAN TEGANG DALAM MERENGANG

SISTEM TALIAN HV ABC

PENYANGKUT

TURNBUCKLE

PENCENGKAM

2) TIANG SUDUT

– MELEBIHI 900

3) TIANG SAMBUNGAN1) TIANG TAMATAN

PEMASANGAN PADA :

Page 25: manual lengkap ABC 33kV

6.2 PEMASANGAN HV DEAD END CLAMP

HV DEAD END CLAMP

STUD 13in x 5/8 in

150mm

PANDANGAN ATAS TIANG SAMBUNGAN

DOUBLE DEAD END CLAMP BRACKET

PANDANGAN SISI TIANG SAMBUNGAN

NUT 5/8 in

Page 26: manual lengkap ABC 33kV

HV SUSPENSION

CLAMP

HV SUSPENSION

CLAMP

Perak Sentiasa Bersinar

SITI RAFIDAH BINTI MUKIARJURUTERA PEMBINAAN (PERAK)

UNIT PERKHIDMATAN KEJURUTERAANTNB PERAK

Page 27: manual lengkap ABC 33kV

7.1 REKABENTUK DAN PEMASANGAN HV SUSPENSION CLAMP

– BOLT DAN NUT

BAGI MENCENGKAM

MESSENGER WIRE

SUPAYA TIDAK

MENGGELONGSOR

- BERTEBAT HINGGA

KE TAHAP 19kN

(1minit)

CLAMP MAIN BODY

BOLT WITH A LOCK NUT

MECHANICAL LINK

2) TIANG SUDUT

– KURANG 900

1) TIANG SESALUR TERUS

PEMASANGAN PADA :

CABLE TIE

HV SUSPENSION CLAMP

TRIANGULARBRACKET

Page 28: manual lengkap ABC 33kV

TRIANGULAR

BRACKET

TRIANGULAR

BRACKET

Perak Sentiasa Bersinar

Page 29: manual lengkap ABC 33kV

8.1 REKABENTUK DAN PEMASANGAN TRIANGULAR BRACKET

U BOLTC CHANNEL 1 1/2x3x6mm

MS FLAT BAR 4Omm x 5mm

CABLE TIE

HV SUSPENSION CLAMP

TRIANGULARBRACKET

KELENGKAPAN NUT DAN STUD :

BAHAN KUANTITI

TRIANGULAR

BRACKET

1 UNIT

NUT 5/8” + WASHER

4 UNIT

STUD 5/8” x 11 2UNIT

-FUNGSI – MENGGANTUNG HV SUSPENSION CLAMP PD TIANG- PEMASANGAN 2 LITAR SECARA SELARI PD PARAS SAMA.- BOLEH DIPASANG SECARA MEMBELAKANG SESAMA SENDIRI- KADAR BREAKING LOAD MINIMUM 30kN (1minit).- BAHAN MELALUI PROSES HOT DIP GALVANISED – ELAK KARAT

LUBANG UTK CABLE ROLLER

Page 30: manual lengkap ABC 33kV

HV CABLE TRAYHV CABLE TRAY

Perak Sentiasa Bersinar

Page 31: manual lengkap ABC 33kV

13.1 REKABENTUKHV CABLE TRAY

100mm

SAMBUNGAN TERUS HV ABC

CABLE TIECABLE TRAY

75 75100

275mm450mm275mm

HV CABLE TRAY – PANDANGAN BAWAH

HV CABLE TRAY – PANDANGAN ATAS

TAG NAMA IDENTITI SAMBUNGAN

LEBAR = 400mPANJANG = 1000m

LUBANG

- CABLE TRAY MEMPUNYAI LUBANG DI BAHAGIAN BAWAH UNTUK MENGELAKKAN AIR BERTAKUNG

Page 32: manual lengkap ABC 33kV

13.1 KEBAIKANHV CABLE TRAY

1) MEMUDAHKAN KERJA PENYAMBUNGAN TERUS PENGALIR FASA HV ABC.

2) SAMBUNGAN BERADA DALAM KEADAAN KEMAS DAN STABIL

3) MENINGKATKAN TAHAP DAYA HARAP SAMBUNGAN KABEL

KETAHANAN BEBAN = 100kg

KETAHANAN KEPANASAN CUACA = 0.48mpa

BERTEBAT = 19kN

SETIAP FASA SAMBUNGAN KABEL PERLU DI IKAT SECARA BERASINGAN KEPADA HV CABLE TRAY MENGGUNAKAN CABLE TIE

Page 33: manual lengkap ABC 33kV

KAEDAH PEMASANGAN HV

CABLE TRAY

KAEDAH PEMASANGAN HV

CABLE TRAY

Perak Sentiasa Bersinar

Page 34: manual lengkap ABC 33kV

4

CABLE JOINT TRAYUntuk ABC Voltan Tinggi

Spasifikasi Utama Pemasangan:•Dipasang mendatar.•Berkedudukan 0.75-0.8m dari paras pengalir.•Messenger Wire dicantum dan bersambung.•Joint Earth Braid Wire dibumikan dengan pembumian asing.

Page 35: manual lengkap ABC 33kV

13.1 HV CABLE TRAY- MEMENUHI SPESIFIKASI

- SAMBUNGAN KEMAS- TIADA GELUNG

-LITAR KEDUA ATAU TALIAN LV TIDAK MENGGANGGU LITAR SEDIA ADA

Page 36: manual lengkap ABC 33kV

13.1 HV CABLE TRAY- TIDAK MEMENUHI SPESIFIKASI

- SAMBUNGAN TIDAK MENGGUNAKAN CABLE TRAY

-SAMBUNGAN TERDEDAH KEPADA DAYA TEGANGAN

- GELUNG YANG TERLALU BESAR

- TIDAK KEMAS

MENGGANGGU SEKIRANYATERDAPAT LITAR KEDUA ATAU TALIAN LV

Page 37: manual lengkap ABC 33kV

13.1 HV CABLE TRAY- TIDAK MEMENUHI SPESIFIKASI

- TIDAK KEMAS- TERLALU HAMPIR DENGAN TALIAN LV

- GELUNG YANG TERLALU BESAR- MENGGANGGU SEKIRANYA TERDAPAT TALIAN KEDUA ATAU LV

BAHAYA KEPADA ANGGOTA KERJAYANG MENGENDALIKANTALIAN LV ATAU LAMPU JALAN

Page 38: manual lengkap ABC 33kV

PERALATAN DAN KAEDAH

PEMASANGAN CABLE TRAY

PERALATAN DAN KAEDAH

PEMASANGAN CABLE TRAY

Perak Sentiasa Bersinar

Page 39: manual lengkap ABC 33kV

13.2 PEMASANGAN HV CABLE TRAY

- PERALATAN

Page 40: manual lengkap ABC 33kV

13.2 PEMASANGAN HV CABLE TRAY

DEAD END CLAMP

CROSBY CLIP

- Joint earth braid wire

MESSENGER WIRE

-50mmp Galvanisedsteel wire

750-800mm

KERJA PEMASANGAN CABLE TRAY SEDANG DIJALANKAN

Page 41: manual lengkap ABC 33kV

“PERAK SENTIASA BERSINAR”

STAY WIRE 7/8 SWG

STAY WIRE AKAN DIPASANG PADA

HALF STAY CLIP PADA JARAK O.4M DI

BAWAH CABLE TRAY

13.2 PEMASANGAN HV CABLE TRAY

HV CABLE TRAY PADA PANDANGAN SISI

HV CABLE TRAY PADA PANDANGAN HADAPAN

Page 42: manual lengkap ABC 33kV

13.2 PEMBUMIANHV CABLE TRAY

EARTHING WIRE DI LUAR TIANG UNTUK SAMBUNGAN (EARTH BONDING JOINT)

-TAMBAHAN EARTHWIRE YANG BERASINGAN DIGUNAKAN UNTUK MEMBUMIKAN SAMBUNGAN (EARTH BONDING JOINT) SAHAJA.

- PEMASANGAN CABLE TRAY UNTUK SAMBUNGAN KABEL

Page 43: manual lengkap ABC 33kV

JARAK SPAN

DAN KELEGAAN

JARAK SPAN

DAN KELEGAAN

Perak Sentiasa Bersinar

Page 44: manual lengkap ABC 33kV

14.1 JARAK SPAN

JARAK SPAN = 30-35 METER

SISTEM HV ABC

JARAK SPAN ANTARA TIANG ADALAH 30-35M UNTUK MENGELAKKAN KEKENDURAN TALIAN ABC 33KV

Page 45: manual lengkap ABC 33kV

14.2 KELEGAAN

KELEGAAN SISTEM HV ABC KE BUMI :

KADAR VOLTAN

KELEGAAN DARI PARAS

TANAH

- MELINTASI JALANRAYA

(m)

KELEGAAN DARI PARAS

TANAH- BAHU JALAN

(m)

KAWASAN TIDAK

DIMASUKI KENDERAAN

(m)

33 kV 6.10 6.10 5.18

11 kV 5.79 5.49 4.88

LV 4.57 5.18 5.49

KELEGAAN DENGAN BANGUNAN : - MESSENGER WIRE TIDAK BERTEBAT – KELEGAAN MINIMUM = 1 m

6.10m

Page 46: manual lengkap ABC 33kV

• SEMUA DAHAN POKOK DAN POKOK-POKOK PERLU DICANTAS :

1) 1 METER DI KIRI, KANAN DAN BAWAH SISTEM HV ABC.2) SEMUA DAHAN YANG DI ATAS DARI SISTEM HV ABC

14.3 KELEGAAN DARI DAHAN POKOK DAN POKOK-POKOK

1 METER

1 METER

Page 47: manual lengkap ABC 33kV

• TALIAN HV ABC HENDAKLAH DIRENTANG DI BAWAH TANAH APABILA MELINTASI TALIAN VOLTAN TINGGI TIDAK BERTEBAT TERMASUK TALIAN PENGHANTARAN.

• TALIAN ABC 33KV DIRENTANG DI DALAM PAIP CORRUGATED / PAIP PVC DAN PEPARIT KABEL DIALAS DENGAN PASIR DAN CONCRETE SLAB.

14.5 MELINTASI TALIAN ATAS VOLTAN TINGGI TIDAK BERTEBAT

TALIAN PENGHANTARAN

KABEL DIBAWAH TANAH

Page 48: manual lengkap ABC 33kV

14.5 MELINTASI TALIAN ATAS VOLTAN TINGGI TIDAK BERTEBAT

PEPARIT KABEL HV ABC SEDANG DIKOREK- SEDALAM 1.2m- DIALAS DENGAN PASIR DAN CONCRETE SLAB

150mm PASIR

150mm PASIR

50mm (CONCRETE SLAB1000x300x50mm)

TANAH ASAL SEHINGGA PARAS TANAH

1220mmPAIP CORRUGATED 150mmp

KABEL ABC 33kV XLPE3X150+50mmp

500mm

Page 49: manual lengkap ABC 33kV

PEPASANGAN UMBANG

PEPASANGAN UMBANG

Perak Sentiasa Bersinar

Page 50: manual lengkap ABC 33kV

14.6.1 PEPASANGAN UMBANG

• FUNGSI UMBANG• MENAHAN ARAH DAYA

TEGANGAN YANG DIKENAKAN OLEH MESSENGER WIRE PADA TIANG.

• TEGANGAN AKIBAT MENGUBAHSUAI KENDURAN TALIAN

CARA PEMASANGAN- ELAKKAN

BERSENTUH DENGAN MESSENGER WIRE

- STAY INSULATOR DIGUNAKAN

• BAHAN-BAHAN PEMBINAAN UMBANG- GALVANISED STAY WIRE GRED 700 BERSAIZ

7/10 SWG (BREAKING LOAD 40.6 kN)- UNIVERSAL BAND FOR 10m-5kN SPUN POLE- STAY INSULATOR (BREAKING LOAD = 31kN)- TIMBLE FOR STAY WIRE 7/10 SWG- BOW AND TIMBLE- STAY ROD 2.0m x 16 mm- STAY PLATE WITH 17mm DIAMETER HOLE- KAYU BAKAU UNTUK TANAH LEMBUT (2 IKAT,

0.6mx75m)

Page 51: manual lengkap ABC 33kV

14.6.1 BAHAN-BAHAN PEMBINAAN UMBANG

STAY INSULATOR (BREAKING LOAD = 31kN)

GALVANISED STAY WIRE GRED 700 BERSAIZ 7/10 SWG (BREAKING LOAD 40.6 kN)

STAY ROD 2.0m x 16 mm

BOW AND TIMBLE

UNIVERSAL BAND FOR 10m-5kN SPUN POLE

STAY PLATE WITH

7mm DIAMETER HOLE

(DITANAM DLM TANAH)

Page 52: manual lengkap ABC 33kV

14.6.6 BILANGAN UMBANG

GAMBAR – SILA RUJUK 14.6.7

JENIS TIANG BILANGAN UMBANG

KEDUDUKAN UNIVERSAL

BAND (UKURAN DARI HUJUNG PARAS TIANG)

TIANG TAMATAN 2 720mm

TIANG PEMBAHAGIAN 2 KIRI DAN

2 KANAN

1300mm

TIANG SUDUT

(SUDUT PERALIHAN <300)

1 720mm

TIANG SUDUT

(SUDUT PERALIHAN >300)

2 720mm

Page 53: manual lengkap ABC 33kV

14.6.7 LOKASI UMBANG

A) TIANG SUDUT = BIL. UMBANG 2

B) TIANG SAMBUNGAN TERUS

= BIL. UMBANG 2

Page 54: manual lengkap ABC 33kV

14.6.7 LOKASI UMBANG

C) TIANG TAMATAN = BIL. UMBANG 2

D) TIANG PEMBAHAGIAN = 2 KIRI & 2KANAN

Page 55: manual lengkap ABC 33kV

14.6.7 LOKASI UMBANG PADA TIANG SUDUT

720m

STAY WIRE 7/10SWG

UNIVERSALBAND

DEAD END CLAMP

CABLE TIE

TIANG SUDUT >300 = BILANGAN UMBANG 2

Page 56: manual lengkap ABC 33kV

14.6.7 LOKASI UMBANG PADA TIANG SAMBUNGAN TERUS

1300 mm

STAY WIRE 7/10SWG

UNIVERSALBAND

DEAD END CLAMP

CABLE TIE

750-800mm

MESSENGER WIRE

Page 57: manual lengkap ABC 33kV

14.6.8 UNIVERSAL BAND

FUNGSI – PEMASANGAN DAWAI UMBANG PADA TIANG.

KELENGKAPAN

– 2 TIMBLE UNTUK PEMASANGAN 2 DAWAI UMBANG

- 3 LUBANG BOLEH LARAS = MEMUDAHKAN PEMASANGAN DAWAI UMBANG- BOLT AND NUT :

- BERGALVANIS

- KETAHANAN 62kN

BLADE A BLADE B

THIMBLED =35

Page 58: manual lengkap ABC 33kV

15.4 HV ABC ROLLER

FUNGSI – MEMUDAHKAN PERGERAKAN KABEL HV ABC TANPA MEROSAKKAN PENEBAT KABEL SEMASA MERENTANG DAN MENEGANGKAN SISTEM HV ABC DI TIANG.

SPESIFIKASI

– KADAR BREAKING LOAD HV ABC ROLLER > 30kN

- BERAT KESELURUHAN HV ABC ROLLER <0.5kN

PENYENDAL

PENYANGKUT

RODA

ROLLER • ROLLER DI PASANG PADA TIANG SEMASA MERENTANG KABEL.

Page 59: manual lengkap ABC 33kV

KAEDAH MERENTANG

KABEL

KAEDAH MERENTANG

KABEL

Perak Sentiasa Bersinar

Page 60: manual lengkap ABC 33kV

HV CABLE ROLLER PEMBAWA DRUM(DRUM JACK)

15.6 KAEDAH MERENTANG TALIAN HV ABC 33kV

LUM UNTUK MENARIK KABEL PULLY EYE & CABLE STOCKING

Page 61: manual lengkap ABC 33kV

DRUM KABEL ABC AKAN DILETAKKAN PADADRUM JACK UNTUK MEMUDAHKAN KABEL ABC

DIRENTANG KELUAR DARI DRUM KABEL

15.6 KAEDAH MERENTANG TALIAN HV ABC 33kV

COME ALONG TONG - MEMEGANG DAN MENARIK MESSENGER WIRE CABLE HV ABC SEMASA MERENGGANG TALIAN

Page 62: manual lengkap ABC 33kV

KABEL DI TARIK

KELUAR DARI

DRUM

15.6 KAEDAH MERENTANG TALIAN HV ABC 33kV

TAYAR DRUM JACK DIHALANG DARI BERGERAK UNTUK MENGELAKKAN DRUM JACK BERGERAK BILA KABEL DITARIK KELUAR

- DRUM KABEL DI

LETAK PD JARAK 8-9m

DR TIANG PERTAMA

- KABEL BERGERAK

KELUAR DARI BAHAGIAN

ATAS DRUM

- PENYELIA KHAS UTK

MENGAWAL PERGERAKAN

KELUAR KABEL.

9m

Page 63: manual lengkap ABC 33kV

- ROLLER AKAN DILETAKKAN DI ATAS 14 TIANG BERTURUTAN UNTUK SETIAP KABEL 500m (1DRUM).- HUJUNG KABEL DIMASUKKAN KE DALAM CABLE STOCKING MENGIKUT SAIZ KABEL DAN DIIKAT

PADA KABEL.- PASANG PULLY EYE DIHUJUNG CABLE STOCKING.

15.6 KAEDAH MERENTANG TALIAN HV ABC 33kV

- LUM DISAMBUNG DIHUJUNG PULLY EYE.- LUM AKAN MEMASUKI SETIAP ROLLER SEDIA ADA DI ATAS TIANG.

LUM

PULLY EYE &CABLE STOCKING

Page 64: manual lengkap ABC 33kV

- KENDERAAN BERAT MENARIK LUM DAN DIIKUTI OLEH KABEL.- DRUM KABEL DIBANTU PERGERAKAN IKUT ARAHAN PUSINGAN KABEL KELUAR.- KABEL AKAN DIRENTANG MELALUI ROLLER

DAN DITARIKH SEHINGGA MENDAPAT KETEGANGAN YANG DIPERLUKAN.- SETELAH TALIAN TEGANG KABEL AKAN DISANGKUTKAN PADA SUSPENSION CLAMP PADA TRIANGULAR BRACKET.

15.6 KAEDAH MERENTANG TALIAN HV ABC 33kV

HUJUNG TAMATAN KABEL KABEL TELAH DISANGKUT PADA SUSPENSION CLAMP

Page 65: manual lengkap ABC 33kV

TIANG TAMATANTIANG TAMATAN

Perak Sentiasa Bersinar

Page 66: manual lengkap ABC 33kV

16.1 TIANG TAMATAN

TIANG TAMATAN = BIL. UMBANG 2

Page 67: manual lengkap ABC 33kV

TIANG SESALUR TERUS

TIANG SESALUR TERUS

Perak Sentiasa Bersinar

Page 68: manual lengkap ABC 33kV

16.2 TIANG SESALUR TERUS

TIANG SESALUR TERUS – PANDANGAN HADAPAN

CABLE TIE

HV SUSPENSION CLAMP

TRIANGULARBRACKET

TIANG SESALUR TERUS – PANDANGAN SISI

150mm

MESSENGER WIRESTAY WIRE

FASA HV KABEL

Page 69: manual lengkap ABC 33kV

TIANG SUDUT > 900TIANG SUDUT > 900

Perak Sentiasa Bersinar

Page 70: manual lengkap ABC 33kV

16.3 TIANG SUDUT

720m

STAY WIRE 7/10SWG

UNIVERSALBAND

DEAD END CLAMP

CABLE TIE

TIANG SUDUT >300 = BILANGAN UMBANG 2

Page 71: manual lengkap ABC 33kV

SAMBUNGAN TERUS HV ABCSAMBUNGAN TERUS HV ABC

Perak Sentiasa Bersinar

Page 72: manual lengkap ABC 33kV

16.6 SAMBUNGAN TERUS HV ABC

1300 m

STAY WIRE 7/10SWG

UNIVERSALBAND

DEAD END CLAMP

CABLE TIE

750-800m

MESSENGER WIRE

SAMBUNGAN TERUS HV ABC - PANDANGAN DEPAN

SAMBUNGAN TERUS HV ABC - PANDANGAN ATAS

Page 73: manual lengkap ABC 33kV

16.6 SAMBUNGAN TERUS HV ABC

SAMBUNGAN TERUS HV ABC

CABLE TIECABLE TRAY

SAMBUNGAN TERUS HV ABC – PANDANGAN ATAS

TAG NAMA IDENTITI SAMBUNGAN

SAMBUNGAN TERUS HV ABC – IKATAN CABLE TIE

Page 74: manual lengkap ABC 33kV

16.6 SAMBUNGAN TERUS HV ABC

SAMBUNGAN TERUS HV ABC – PANDANGAN BELAKANG

SAMBUNGAN TERUS HV ABC – PANDANGAN HADAPAN & SISI

Page 75: manual lengkap ABC 33kV

16.6 SAMBUNGAN TERUS HV ABC - PEMBUMIAN

SAMBUNGAN TERUS HV ABC – PANDANGAN BELAKANG

PANDANGAN SISI

-SETIAP SAMBUNGAN AKAN DIBUMIKAN PADA TIANG TERSEBUTTIDAK BERSENTUH DGN MESSENGERWIRE

JOINT EARTH BRAID WIREUTK DIBUMIKAN

SAMBUNGAN DI IKAT MENGGUNAKAN CABLE TIE PADA CABLE TRAY UNTUK MENETAPKAN KEDUDUKAN BERASINGAN

Page 76: manual lengkap ABC 33kV

SAMBUNGAN TERUS HV ABC – PANDANGAN PENUH

16.6 SAMBUNGAN TERUSHV ABC

STAY WIRE 7/10SWG-UTK PEMBUMIAN SAMBUNGAN TERUS HV ABC

PANGKAL TIANG SAMBUNGAN

Page 77: manual lengkap ABC 33kV

SAMBUNGAN TERUS HV ABC DI ATAS SCAFOLDING

- SCAFOLDING MUDAH DIBAWAOLEH PASUKAN PENYAMBUNG KABEL

-SCAFOLDING BOLEH DIGUNAKAN DI KAWASAN YANG SUKAR DILALUI.

SCAFOLDING YANG TELAH SIAP DIDIRIKAN DAN BERSEDIAUNTUK DIGUNAKAN SEMASA SAMBUNGAN KABEL DILAKUKAN

Page 78: manual lengkap ABC 33kV

KAEDAH MEMBUAT SAMBUNGAN

TERUS

KAEDAH MEMBUAT SAMBUNGAN

TERUS

Perak Sentiasa Bersinar

Page 79: manual lengkap ABC 33kV

PENYAMBUNG KABEL AKAN BERDIRI DI ATAS SCAFTFOLDING UNTUK MEMBUAT

KERJA-KERJA SAMBUNGAN TERUS KABEL HV ABC.

CRIMPING

4.1 KAEDAH MEMBUATSAMBUNGAN TERUS

PAYUNG UNTUK MELINDUNGI DARI PANAS ATAU HUJAN

TIANG SAMBUNGAN

SCAFTFOLDING

Page 80: manual lengkap ABC 33kV

KAEDAH MEMBUATSAMBUNGAN TERUS

Page 81: manual lengkap ABC 33kV

KAEDAH MEMBUAT SAMBUNGAN TERUS

Page 82: manual lengkap ABC 33kV

KAEDAH MEMBUAT SAMBUNGAN TERUS

Page 83: manual lengkap ABC 33kV

KAEDAH MEMBUAT SAMBUNGAN TERUS

Page 84: manual lengkap ABC 33kV

KAEDAH MEMBUAT SAMBUNGAN TERUS

Page 85: manual lengkap ABC 33kV

H-POLEH-POLE

Perak Sentiasa Bersinar

Page 86: manual lengkap ABC 33kV

SISTEM HV ABC DAN H-POLE

PPU/PMU

PPU/PMU

H-POLE

H-POLE

H-POLE

U/G CABLE

U/G CABLE

U/G CABLE

U/G CABLE

U/G CABLE

U/G CABLE

O/H CABLE

O/H CABLE

- H-POLE PD PPU/PMU ADALAH UTKPERLINDUNGAN DARI SEBARANGKEROSAKAN KEPADA ALATSUIS

-SEBELUM DAN SELEPAS H-POLE KABEL HENDAKLAH DIRENTANGDI BAWAH TANAH UNTUK MENGELAKKAN BINATANG MUDAH MELOMPAT ATAU MEMANJAT PADAH-POLE

-TUJUAN H-POLE DIPERTENGAHAN: 1) UTK MEMBAHAGIKAN SISTEM. 2) UTK MENJALANKAN UJIAN VLF. 3) PENGASINGAN SISTEM/BEBAN MUDAH DIJALANKAN.4)KEMUDAHAN MENCARI KEROSAKAN PADA BAHAGIAN TERTENTU.

-SISTEM HV ABC AKAN DITAMATKANPADA ALATSUIS DI DLM PMU/PPU.

H –POLE BERFUNGSI SEBAGAI PENGASING BEBAN / SISTEM.

TALIAN HV ABC – KABEL 1TERAS-TIADA EARTHING LINK BOX PADA PMU/PPU.

Page 87: manual lengkap ABC 33kV

SISTEM HV ABC DAN H-POLE

2

13

4

2)TIANG TAMATANSEBELUM H-POLE

4) TIANG TAMATANSELEPAS H-POLE

5) U/G CABLE

H-POLE

1 1

1 12 435 5

5

5

1) O/H CABLE

3) H-POLE

Page 88: manual lengkap ABC 33kV

PEMBINAAN TAPAK H-POLE

PENYEDIAAN EARTH UTK MEWUJUDKAN VOLTAGE POTENTIAL YANG SAMA PADA

KESELURUHAN TAPAK H-POLE

TAPAK DISEDIAKAN DENGAN KEMAS SEBELUM DISIMEN.PEMBUMIAN DIPASTIKAN LENGKAP

Page 89: manual lengkap ABC 33kV

PEMBINAAN TAPAK H-POLE

KERJA-KERJA PEMBINAAN TAPAK SEDANG DIJALANKAN

TAPAK H-POLE TELAH SIAP DIKONKRIT

Page 90: manual lengkap ABC 33kV

PEMASANGAN H-POLE

H-POLE – PADANGAN HADAPAN

H-POLE – PADANGAN SISI

H-POLE

– PADANGAN SISI

Page 91: manual lengkap ABC 33kV

PEMASANGAN H-POLE

ANTI PANJAT DIBINA LENGKAP UNTUK MENGHALANG H-POLE DIPANJAT.

LBS = LOAD BREAK SWITCH / ISOLATOR

ANTI PANJAT – PANDANGAN DARI ATAS

ANTI PANJAT

HANDLE LBS

Page 92: manual lengkap ABC 33kV

PEMASANGAN H-POLE

1) SEMUA EARTHING WIRE DISATUKAN UNTUK MEMASTIKAN ZERO POTENTIAL

2) HANDLE LBS HENDAKLAH PADA KEDUDUKAN BERTENTANGAN DENGAN LBS

TAMATAN KABEL DIPASTIKAN TIDAK TERTONGGENG

HANDLE LBS

EARTHING WIRE

LIGHTNING ARRESTER

2 SETSETIAPFASA(R,Y,B)

TAMATAN

Page 93: manual lengkap ABC 33kV

TAMATAN KABEL HV ABC PADA ALATSUIS 33KV

C) TIANG TAMATAN

D) TIANG PEMBAHAGIAN

Page 94: manual lengkap ABC 33kV

TAMATAN KABEL HV ABC PADA ALATSUIS 33KV

C) TIANG TAMATAN

D) TIANG PEMBAHAGIAN

Page 95: manual lengkap ABC 33kV

TAMATAN KABEL HV ABC PADA ALATSUIS 33KV

C) TIANG TAMATAN

D) TIANG PEMBAHAGIAN

Page 96: manual lengkap ABC 33kV

TAMATAN KABEL HV ABC PADA ALATSUIS 33KV

C) TIANG TAMATAN

D) TIANG PEMBAHAGIAN

Page 97: manual lengkap ABC 33kV

TATACARATATACARA

Perak Sentiasa Bersinar

Page 98: manual lengkap ABC 33kV

TATACARA

PEMBERSIHAN KAWASAN

Page 99: manual lengkap ABC 33kV

PERATURAN KESELAMATAN LALULINTAS HENDAKLAH DI PATUHI APABILA KERJA-KERJA DILAKUKAN DI TEPI JALAN MENGIKUT

PERATURAN KESELAMATAN LALULINTAS OLEH JKR

TATACARA – BEKERJA DI TEPI JALAN ATAU KAWASAN BANDAR