2009 iecc: residential provisions

93
RESIDENTIAL PROVISIONS for the 2009 International Energy Conservation Code Forrest Fielder [email protected] 1

Upload: philip-beere

Post on 21-Feb-2017

9 views

Category:

Real Estate


0 download

TRANSCRIPT

Page 1: 2009 IECC: Residential Provisions

RESIDENTIAL PROVISIONSfor the

2009 International Energy Conservation Code

Forrest [email protected]

1

Page 2: 2009 IECC: Residential Provisions

Course Objectives

• Understand the importance of the IECC in the built environment

• Understand the development of the IECC/IRC

• Understand the roles of code officials in the IECC

• Understand the application of the IECC requirements to building systems

2

Page 3: 2009 IECC: Residential Provisions

What’s Changed from the IECC 2006?

Stringency CZ4 – fenestration U-factor reduced from .40

to .35 CZ5,6 – wood frame wall U-factor reduced

from .06 to .057, minimum R-value (batt only) raised from R-19 to R-20

CZ1,2,3 – Glazed fenestration SHGC reduced from .40 to .30 (except in IRC!)

CZ3 - Basement wall R-value requirements added – 5/13

Reductions allowed in 402.2.1 and 402.2.2 may not be used in the UA tradeoff calculation.

Provisions for attic hatches added (402.2.3) Requirements added for the location (interior vs.

exterior) of insulation in mass walls CZ1,2 - Exceptions for steel frame walls 24”oc (see table 402.2.5)

3

Page 4: 2009 IECC: Residential Provisions

What’s Changed from the IECC 2006? Moisture control requirements moved to the IRC (R601.3) Exemptions for 15sf glazed fenestration and opaque doors may not be

used in the UA tradeoff calculation. Envelope air tightness requirements added – blower door or envelope

inspection required (402.4.2 and Table 402.2.2) (2) of (3) options for recessed lighting eliminated – testing per ASTM

E283 now required. Site-built option deleted. Specific mandatory requirements for elements of mechanical systems

specified, replacing Sec 403 (Mandatory) language. Minimum R-8 for attic “supply” ducts – all others min R-6, except if

located in conditioned space. New requirements for snow melt systems and heated pools. High efficacy lighting required for 50% of permanently installed fixtures For performance design, exception added for multiple orientations For performance design, mechanical tradeoffs disallowed, i.e. proposed

design =standard design

4

Page 5: 2009 IECC: Residential Provisions

Overview of IECC Requirements

5

• Focus is on building envelope– Ceilings, walls, windows, floors, foundations– Sets insulation levels, window U-factors and

solar heat gain coefficients– Infiltration control - caulk and seal to prevent

air leaks• Ducts – seal and insulate• Limited space heating, air conditioning,

and water heating requirements– Federal law sets most equipment efficiency

requirements, not the I-codes• Lighting equipment – 50% of lamps to be

high-efficacy lamps

Page 6: 2009 IECC: Residential Provisions

Does My Project Need to Comply?

• One- and two-family residential – IECC/IRC

• R-2, R-3, R-4 three stories or less in height – IECC/IRC?

• Townhomes – IECC/IRC

6

Page 7: 2009 IECC: Residential Provisions

Are These Projects Considered Residential or Commercial?

7

Page 8: 2009 IECC: Residential Provisions

Mixed Use Buildings

8

• Mixed occupancies– Treat the residential

occupancy under the applicable residential code

– Treat the commercial occupancy under the commercial code

– – Three stories or less– 10% rule (not found in code, in

commentary) www.energycodes.gov

ww

w.energycodes.gov

Page 9: 2009 IECC: Residential Provisions

What Types of Residential Projects are Exempt from the IECC/IRC?

Unconditioned SpacesVery Low Energy use

buildings (<3.4 Btu/h-ft2 or 1 watt/ft2) – envelope

exemption onlyExisting BuildingsUnmodified Parts of ResidenceHistoric Buildings

9

Page 10: 2009 IECC: Residential Provisions

Special Topics - Additions

AdditionsWhat is an Addition?

Extension or increase in the conditioned space floor area or height of a building or structure

What Must Comply in an Addition?

New building thermal envelope

New heating and cooling system

New ductworkNew water heating

system10

Page 11: 2009 IECC: Residential Provisions

Special Topics - Additions

How do I Show Compliance for the Addition?Treat addition as a stand alone building

Prescriptive (Component) approachTotal UA AlternativeSimulated Performance Alternative

Demonstrate compliance for the entire house (addition + existing)Used for major renovationPrescriptive (Component) approachTotal UA AlternativeSimulated Performance Alternative

11

Conditioned Addition

ExistingHouse

Treat Addition As Stand Alone Building

Conditioned Addition

ExistingHouse

Demonstrate Compliance for Entire House

Page 12: 2009 IECC: Residential Provisions

Special Topics - Alterations

Change to the building envelope, heating and cooling system or water heating system that requires a permit

Must show compliance with the applicable provisions in Code

ExceptionsInstalling storm windows over existing fenestrationReplacing only the glass in an existing sash and

frameExposing existing ceiling, wall or floor cavities that

are already filled with insulationConstruction that does not expose existing roof,

wall or floor cavities

12

Page 13: 2009 IECC: Residential Provisions

Special topics - Alterations(Exceptions)• Re-roofing where neither the sheathing or

the insulation is exposed.• Alterations replacing <50% of the

luminaires in a space, provided that interior lighting power is not increased

• Alterations that replace only bulb and ballast, provided the interior lighting power is not increased.

13

Page 14: 2009 IECC: Residential Provisions

Regulated Items

14

HVAC

DHW

Building ThermalEnvelope Conditioned

SpaceDHWConditioned

Space

Lighting

Page 15: 2009 IECC: Residential Provisions

Structure of the IECC

Chapter 1 – Administration2009 includes new provisions to add exempt elements,

and to align the IECC with administrative provisions in the other I-codes.

Chapter 2 – DefinitionsChapter 3 – Climate Zones, and Materials, Systems, and

Equipment (relocated from 2006 Ch 1)Chapter 4 – Residential RequirementsChapter 5 – Commercial RequirementsChapter 6 – Referenced Standards

15

Page 16: 2009 IECC: Residential Provisions

Chapter 1

• Scoping

• Intent

• Third party programs – must meet Mandatory Measures

• Sections 103 (Construction Documents), & 104 (Inspections) – see extensive Commentary notes

16

Page 17: 2009 IECC: Residential Provisions

Chapter 2 - DefinitionsAir barrier – Materials “assembled and joined together”, a

single material or combination of materials, i.e. sealants, acting as a system.

Basement wall – “…enclosing conditioned space.” If unconditioned, is classified as a crawl space.

Fenestration – includes skylights & doors.U-value/R-value – Reciprocal values between transmittance

and resistance. Note that U-value includes air films. U-value is calculated through a “component or assembly”, and R-value through a “body”. 402.1.2 (components) and 402.1.3 (assembly) make the difference more clear. C-factor is very similar to U-value (surface to surface instead of air to air) and is used in SHGC calculations.

High-efficacy lamps – minimum lumens/watt requirementLabeled and Listed – borrowed from the IBC

17

Page 18: 2009 IECC: Residential Provisions

Chapter 3 – Climate Zones

• Climate Zone map

• Design conditions

• Materials, systems, and equipment – relocated from 2006 IECC Chapter 1

18

Page 19: 2009 IECC: Residential Provisions

2009 IECC Climate Zones

19

Page 20: 2009 IECC: Residential Provisions

2009 IECC Climate Zones

20

Zone 5

Zone 3

Zone 4

Zone 2

Page 21: 2009 IECC: Residential Provisions

Climate Zones

• Warmer Zones (1 – 4B)– Based on Heating and Cooling Degree

Days– Accounts for Humidity

• Requirements include features that reduce cooling energy

21

Page 22: 2009 IECC: Residential Provisions

Climate Zones

• Predominately Colder Zones (4C – 8) – Based on Heating Degree Days– Accounts for Humidity– Requirements include features that

reduce heating energy– Higher the climate zone number the

more stringent the requirement

22

Page 23: 2009 IECC: Residential Provisions

Code Compliant Attic Insulation

• Attic insulation markers required every 300 square feet for blown-in insulation• Markers must be installed

so that R-value mark is readily observable

• Insulation R-value Required to be Labeled on Pieces ≥ 12” width, or provide certificate for blown or sprayed insulation

23

Page 24: 2009 IECC: Residential Provisions

Code Compliant Attic InsulationProvide Certification, Listing (All):

Insulation typeManufacturerR-value Installed

Blown or Sprayed Insulation (Fiberglass or Cellulose)Initial installed thicknessSettled thicknessSettled R-valueInstalled densityCoverage area and number of

bagsSprayed Polyurethane Foam (SPF)

Installed thicknessR-value

24

Page 25: 2009 IECC: Residential Provisions

Default U-factors

25

IECC Table 303.1.3(1) and IRC Table N1101.5(1)

IECC Table 303.1.3(2) and IRC Table N1101.5(2)

Page 26: 2009 IECC: Residential Provisions

Energy Code Compliance Process

26

Mandatory Provisions

Prescriptive

Envelope Section 402

Envelope ProvisionsSection 402.2, 402.3.3 thru 402.3.6 & 402.5 (As Applies)

Simulated Performance Section 405Insulation

Requirements Fenestration

Section 403.2.1 & 404.1

Table 402.1.3

Section 402.3.1 & 402.3.2 (Trade-Off)

Section 402.1.1 & 402.1.2 (Tabular)

Section 402.1.3 & 402.1.4 (Trade-Off)

Project Complies

OR OR

Page 27: 2009 IECC: Residential Provisions

Prescriptive Approach

• Compliance Based on Look-Up Tables• Calculations May be Required (See following)

What Information Do You Need?

• Climate Zone of Proposed Building• Types of Building Assemblies that are Proposed

for the Project

27

Page 28: 2009 IECC: Residential Provisions

Prescriptive Approach

You Don’t Need to be concerned with Window (i.e. Fenestration) Area

• Minimum Area Set by Chapter 3 of the IRC

• Maximum Area Set bystructural Constraints and By Cost

28

Page 29: 2009 IECC: Residential Provisions

What is Considered Part of the Building Thermal

Envelope?

• Roof/Ceiling Assembly

• Wall Assembly• Windows, Skylights,

and Doors

• Floor Assembly• Slab Edge• Basement Wall• SHGC, U-Factor

29

Climate Specific Requirements: Boundary Between Conditioned Space and the

Great Outdoors or Unconditioned Space Includes:

Page 30: 2009 IECC: Residential Provisions

Envelope R-Value• What Counts Towards R-Value?

– Add• Insulation Layers• Insulation between Framing• Insulation over Framing

– Don’t Add• Non Insulation Products• Sheathing less than R-2• Air Films• Air Spaces

– Framing Spaces (or amount) Doesn’t Matter

30

Page 31: 2009 IECC: Residential Provisions

Building Envelope

• Roof/Ceiling Assembly

• Wall Assembly

31

Page 32: 2009 IECC: Residential Provisions

Building Envelope

• Vertical Fenestration and Skylights

• Floor Assembly

32

Page 33: 2009 IECC: Residential Provisions

Overview of Tables 402.1.1(IECC) and N1102.1(IRC) – Component

ApproachCLIMATE

ZONE FENESTRATION

U-FACTORb SKYLIGHTb U-FACTOR

GLAZED FENESTRATIONb,e

SHGC

CEILING R-VALUE

WOOD FRAME WALL

R-VALUE

MASS WALL

R-VALUEi

FLOOR R-

VALUE

BASEMENTc WALL

R-VALUE

SLABd R-VALUE & DEPTH

CRAWL SPACEc

WALL R-VALUE

1 1.20 0.75 0.30 30 13 3 / 4 13 0 0 0 2 0.65j 0.75 0.30 30 13 4 / 6 13 0 0 0 3 0.50j 0.65 0.30 30 13 5 / 8 19 5 / 13f 0 5 / 13

4 except Marine

0.35 0.60 NR 38 13 5 / 10 19 10 / 13 10, 2ft 10 / 13

5 and Marine 4

0.35 0.60 NR 38 20 or 13+5h 13 / 17 30g 10 / 13 10, 2 ft 10 / 13

6 0.35 0.60 NR 49 20 or 13+5h 15 / 19 30g 15 / 19 10, 4 ft 10 / 13 7 and 8 0.35 0.60 NR 49 21 19 / 21 38g 15 / 19 10, 4 ft 10 / 13

33

Table 402.1.1Insulation and Fenestration Requirements by Componenta

a. R-values are minimums, U-factors and SHGC are maximums, R-19 batts compressed into a nominal 2 x 6 framing cavity such that the R-value is reduced by R-1 or more shall be marked with the compressed batt R-value in addition to the full thickness R-value.b. The fenestration U-factor column excludes skylights. The SHGC column applies to all glazed fenestration.c. “15/19” means R-15 continuous insulated sheathing on the interior or exterior of the home or R-19 cavity insulation at the interior of the basement wall. “15/19” shall be permitted to be met with R-13 cavity insulation on the interior of the basement wall plus R-5 continuous insulated sheathing on the interior or exterior of the home. “10/13” means R-10 continuous insulated sheathing on the interior or exterior of the home or R-13 cavity insulation at the interior of the basement wall.d. R-5 shall be added to the required slab edge R-values for heated slabs. Insulation depth shall be the depth of the footing or 2 feet, whichever is less in Zones 1 through 3 for heated slabs.e. There are no SHGC requirements in the Marine Zone.f. Basement wall insulation is not required in warm-humid locations as defined by Figure 301.1 and Table 301.1.g. Or insulation sufficient to fill the framing cavity, R-19 minimum.h. “13+5” means R-13 cavity insulation plus R-5 insulated sheathing. If structural sheathing covers 25 percent or less of the exterior, insulating sheathing is not required where structural sheathing is used. If structural sheathing covers more than 25 percent of exterior, structural sheathing shall be supplemented with insulated sheathing of at least R-2.i. The second R-value applies when more than half the insulation is on the interior of the mass wall.j. For impact rated fenestration complying with Section R301.2.1.2 of the IRC or Section 1608.1.2 of the IBC, maximum U-factor shall be 0.75 in Zone 2 and 0.65 in Zone 3.

0.75

0.650.40

0.40

0.400.40

19

30

0

10/13

Page 34: 2009 IECC: Residential Provisions

U-factor Alternative to Meeting the Table 402.1.1/N1102.1 R-Value Requirements

CLIMATE ZONE

FENESTRATION U-FACTOR

SKYLIGHT U-FACTOR

CEILING U-FACTOR

FRAME WALL

U-FACTOR

MASS WALL

U-FACTORb

FLOOR U-FACTOR

BASEMENT WALL

U-FACTORd

CRAWL SPACE WALL

U-FACTORc 1 1.20 0.75 0.035 0.082 0.197 0.064 0.360 0.477 2 0.65 0.75 0.035 0.082 0.165 0.064 0.360 0.477 3 0.50 0.65 0.035 0.082 0.141 0.047 0.091c 0.136

4 except Marine

0.35 0.60 0.030 0.082 0.141 0.047 0.059 0.065

5 and Marine 4

0.35 0.60 0.030 0.057 0.082 0.033 0.059 0.065

6 0.35 0.60 0.026 0.057 0.060 0.033 0.050 0.065 7 and 8 0.35 0.60 0.026 0.057 0.057 0.028 0.050 0.065

34

Table 402.1.3 (IECC) and N1102.2 (IRC)

a. Non-fenestration U-factors shall be obtained from measurement, calculation or an approved source.b. When more than half the insulation is on the interior, the mass wall U-factors shall be a maximum of 0.17 in Zone 1, 0.14 in Zone 2, 0.12 in Zone 3, 0.10 in Zone 4 except Marine, and the same as the frame wall U-factor in Marine Zone 4 and Zones 5 through 8.c. Basement wall U-factor of 0.360 in warm-humid locations as defined by Figure 301.1 and Table 301.2.

Page 35: 2009 IECC: Residential Provisions

U-factor Calculation

U-factors Are To Be Calculated Based On ASHRAE Handbook of Fundamentals– Include

thermal bridging affects of framing

35

Percent of wall with framing

Percent of wall without framing

0.10060.0572Total Unadjusted U-factors

9.9417.48Total Unadjusted R-values

0.170.17Outside Air Film

0.180.187/8” Stucco

5.005.001” Cellular Polyurethane

3.46-----2 X 4 @ 16” O.C.

----11.00R-11 Fiberglass Batt Insulation

0.450.451/2” Gypsum Board

0.680.68Inside Air Film

Frame R-valueCavity R-valueList of Components

Percent of wall with framing

Percent of wall without framing

Uo = (0.0572 X 0.85) + (0.1006 X 0.15) = 0.0637

0.10060.0572Total Unadjusted U-factors(1/R-value)

9.9417.48Total Unadjusted R-values

0.170.17Outside Air Film

0.180.187/8” Stucco

5.005.001” Cellular Polyurethane

3.46-----2 X 4 @ 16” O.C.

----11.00R-11 Fiberglass Batt Insulation

0.450.451/2” Gypsum Board

0.680.68Inside Air Film

Frame R-valueCavity R-valueList of Components

Page 36: 2009 IECC: Residential Provisions

Total UA Alternative

• Allows Efficiency Trade-offs Between Building Assemblies– Whole building approach allowing portions

of the building to under comply if portions over comply with the code

– Based on Table 402.1.3/N1102.1.2 Equivalent U-factors

• Basis for US DOE REScheck software

36

Page 37: 2009 IECC: Residential Provisions

UA Alternative eliminates exceptions

Eliminates the following exceptions:– Opaque door, 24 ft2

– Fenestration U-factor, 15 ft2

– Fenestration SHGC, 15 ft2

– Ceiling tradeoff, R49 to R38 / R38 to R30

– Ceiling w/o attic space, R30, 500ft2

37

Page 38: 2009 IECC: Residential Provisions

Total UA AlternativeSample Calculation• UA = (Uw X Aw) + (Ug X Ag) + (Ud + Ad) + (Uf X Af) + (Ur x Ar)Where:

– UA = Total U-factor X Area for Whole Building– Uw = U-factor of Wall Assembly– Ug = U-factor of Glass Assembly– Ud = U-factor of Door Assembly– Uf = U-factor of Floor Assembly– Ur = U-factor of Roof Assembly– Aw = Area of Wall Assembly– Ag = Area of Glass Assembly– Ad = Area of Door Assembly– Af = Area of Floor Assembly– Ar = Area of Roof Assembly

38

Page 39: 2009 IECC: Residential Provisions

Fenestration U-factorGlazed Fenestration

Exemption - Up to 15 ft2 of glazed fenestration

Does not apply to U-factor approach

• Example Uses– Stained glass

windows– Glass block– Door side lites

39

Page 40: 2009 IECC: Residential Provisions

Glazed Fenestration SHGC

What is Solar Heat Gain Coefficient?– A simple way to explain SHGC is

in terms of a ratio; where 1 is the maximum amount of solar heat gain that can come through a window and 0 is the least amount. An SHGC of 0.40 then means that 40% of the available solar heat is coming through the window .

40

Page 41: 2009 IECC: Residential Provisions

Glazed Fenestration SHGC

How are fenestration products rated?– NFRC 200

• Default U-factors from Table 303.1.3(3) – IECC or N1101.5(3) - IRC

41

Page 42: 2009 IECC: Residential Provisions

Glazed Fenestration SHGC

SHGC Area Weighted Average

– An area weighted average (including skylights) may be used to meet the SHGC requirement.

Example:

Window 1 SHGC- 0.35 100 ft2

Window 2 SHGC- 0.50 50 ft2

Window 3 SHGC- 0.40 50 ft2 (100 ft2 X 0.35) + (50 ft2 X 0.50) + (50 ft2

X 0.40) = 200 ft2

Average SHGC of .40

42

Page 43: 2009 IECC: Residential Provisions

Fenestration U-Factor, UA Alternative

Special Rules– Maximum fenestration U-factor

• Area weighted average maximum vertical fenestration U-factor

– IECC – Zones 4 – 5: 0.48– IECC – Zones 6 – 8: 0.40– IRC – Zones 6 – 8: 0.35

• Thermally isolated sunroom maximum skylight U-factor

– IECC – Zones 4 – 8: 0.75– IRC – Zones 4 – 8: 0.75

43

Page 44: 2009 IECC: Residential Provisions

Fenestration U-factorU-factor Area Weighted Average may be used to meet the u-factor requirement.

Example:

Window 1 U- 0.35 100 ft2

Window 2 U- 0.50 50 ft2

Window 3 U- 0.40 50 ft2

(100 ft2 X 0.35) + (50 ft2 X 0.50) + (50 ft2 X 0.40) 200 ft2

=U-0.40 Average

44

Page 45: 2009 IECC: Residential Provisions

Fenestration U-factor

What is considered fenestration in Tables 402.1.1and N1102.1?Vertical windowsOpaque doorsGlazed doorsGlazed blockCombination

opaque/glazed doors

45

Page 46: 2009 IECC: Residential Provisions

Fenestration U-factor

How are fenestration products rated?

– NFRC 100

46

U-Factor

Now:CZ2 u-0.65CZ3 u-0.50CZ4 u-0.35

Was:CZ2 u-0.75CZ3 u-0.65CZ4 u-0.40

Page 47: 2009 IECC: Residential Provisions

Door U-Factor

All Doors are Considered Fenestration

• Must Meet Fenestration U-factor Requirement– Can exempt one

“side hinged” opaque door assembly up to 24 ft2 47

Courtesy Jeldwen Doors

Page 48: 2009 IECC: Residential Provisions

Skylight U-Factor

What is a Skylight?– Installed at a slope of

15 degrees or more from vertical

• No Limit on Skylight Area

• NFRC 100• Default U-factors per

Table 303.1.3(1) – IECC, N1101.5(1) – IRC

48

Page 49: 2009 IECC: Residential Provisions

Wood Frame Wall R-Value

Walls: 50% above grade and Enclosing conditioned space, wood framed

IncludesBetween floor spandrelsPeripheral edges of floors,

roof and basement knee wallsDormer wallsGable end wallsWalls enclosing a mansard

roofSkylight shafts

49

Page 50: 2009 IECC: Residential Provisions

R-Value computation

How Do I Insulate to Meet the Requirements?– Install insulation

between framing– Install insulation

between framing and over the face of the stud (continuous)

– Insulation R-values can be added

50

Page 51: 2009 IECC: Residential Provisions

Wood Frame Wall R-Value

Structural Sheathing AllowanceR-5 where there is no structural sheathingIf structural sheathing covers > 25%,

supplement with R-2 insulating sheathing over structural sheathing

51

Page 52: 2009 IECC: Residential Provisions

Advanced Framing – Optimum Value Engineering

• Building codes allow for advanced wall framing• Insulated corners, two-stud corner• Ladder framing for interior walls• Increased insulation

• Single Top Plate• Insulated Headers (non bearing exterior

walls) Span requirements can dictate a full bearing header.

52

Page 53: 2009 IECC: Residential Provisions

Code Compliant Wall Insulation Installation

Batt Insulation Required to be Labeled on Pieces ≥ 12” Wide, or provide Certification Listing:

Insulation typeManufacturerR-value Installed (R-19 Marked if Compressed)Blown or Sprayed Insulation (Fiberglass or Cellulose)R-valueInstalled densityCoverage area and number of bagsSprayed Polyurethane Foam (SPF)Installed thickness R-value

53

Page 54: 2009 IECC: Residential Provisions

Ceiling R-value

Ceiling R-value Requirements Based on Ceiling Assembly Type– Ceilings with attic spaces– Ceilings without attic spaces

54

Page 55: 2009 IECC: Residential Provisions

Ceiling R-value - Ceilings With Attic Spaces

Options for meeting requirements

– Standard truss system – Install R-value of insulation to meet the requirements specified in Table 402.1.1/N1102.1

55

Cold corners contribute to condensation and mold growth.

Possibility of ice dam formations.

Potential Cold Climate Issues:

Page 56: 2009 IECC: Residential Provisions

Ceiling R-value - Ceilings With Attic Spaces

Options for meeting requirements Oversized Truss / Energy

Truss / Raised Heel Truss Substitute R- 30 for

R-38 Insulation Substitute R- 38 for

R-49 Insulation Goal – Provide full height,

uncompressed insulation over exterior wall plate at the eaves

56

Baffling to preventinsulation from blocking ventilation

Raised Heel Truss

Baffling to preventinsulation from blocking ventilation

Page 57: 2009 IECC: Residential Provisions

Ceiling R-value – Ceilings Without Attic Spaces

Can install minimum R-30 insulation in roof assemblies that require > R-30Only allowed in

assemblies with insufficient space to install greater than R-30

Only allowed in ceiling areas up to 500 ft2 or 20% whichever is less

57

Page 58: 2009 IECC: Residential Provisions

Conditioned Attics

• IRC recognizes conditioned attics (Chapter 8)• Sets requirements (e.g. vapor retarders, air-

impermeable insulation, application)• Recognizes interaction between

roofing materials and impermeableinsulation

• US Department of Energy (DOE) building guides

• http://www.eere.energy.gov/buildings/building_america/for_builders.html

58

Page 59: 2009 IECC: Residential Provisions

Steel Framed Assemblies

• Steel Frame Assemblies Must Meet the Requirements of Table 402.2.5-IECC or N1102.2.5 - IRC

59

Page 60: 2009 IECC: Residential Provisions

Floor R-Value

What Floors Types Are Covered? – Floors Over:

• Unconditioned space

• Vented crawlspace

• Unconditioned garage

• Outside air

60

Page 61: 2009 IECC: Residential Provisions

Code Compliant Raised Floor Insulation

• Insulation must fill the floor joist cavity from joist to joist and be in permanent contact with the subfloor

61

Insulation Must FillFrom Joist to Joist

Page 62: 2009 IECC: Residential Provisions

Section 403 - Systems

Section 403.1 - Controls • Each heating or cooling system shall have a

thermostat• For forced-air systems, a programmable thermostat

is required, with a setback range of 55 ̊F to 85 ̊F, and initial programming of 70 ̊F (heating) and 78 ̊F (cooling)

• Heat pumps with supplementary electric heat shall have controls to prevent operation of the supplemental heat when the heat pump can meet the load.

62

Page 63: 2009 IECC: Residential Provisions

Section 403.2.1 - Ducts Insulation

(Prescriptive)Heating and Cooling Equipment

– Duct Insulation • Supply ducts in attics shall

be insulated to an R-8• All other ducts (returns) shall

be insulated to an R-6• Ducts inside the building

thermal envelope are exempt

63

Page 64: 2009 IECC: Residential Provisions

Section 4.3.3 – Mechanical System Piping Insulation

• (Minimum) R-3 for piping carrying fluids above

105 ̊F or below 55 ̊F.

64

Page 65: 2009 IECC: Residential Provisions

Section 403.2.1 – Duct Sealing • Ducts, air handlers, filters, cavities used as ducts

to be sealed per IRC M1601.4.1 • Duct tightness to be verified by Postconstruction test – leakage to outdoors @

(max ) 8 cfm/100sf(25Pa) of conditioned space, or Rough-in test – total leakage @ (max) 6cfm/100sf(25PA) of conditioned spaceException – testing not required if air handler and

all ducts are located within conditioned space

65

Page 66: 2009 IECC: Residential Provisions

Building Envelope Mandatory Requirements

Air Leakage Controls– Goal is to limit infiltration– Limit both heat and moisture flow– Air sealant materials must allow for

differential expansion and contraction between dissimilar materials

66

Page 67: 2009 IECC: Residential Provisions

What Options are Available as an Air Sealant?

• Caulking• Gasketing• Weatherstripping• Sealed with an air barrier

material, suitable film or solid material

• Self sealing continuous materials - examples– Concrete– SIPS– ICF

67

Page 68: 2009 IECC: Residential Provisions

Air Sealing

• Required Sealing around Tub/Shower Enclosure and Attic Knee wall

• Recessed Lighting IC-Rated

68

Section 402.4.1 Air LeakageThermal Envelope Requirements1. All joints, seams and penetrations2. Site-built windows, doors and skylights3. Between window and door assemblies

and framing4. Utility penetrations5. Dropped ceilings or chases 6. Knee walls7. Walls and ceilings separating a garage8. Behind tubs and showers on exterior

walls9. Common walls between dwelling units10. Attic access openings.11. Rim joists junction12. Other sources of infiltration

Page 69: 2009 IECC: Residential Provisions

402.4.2.1 Testing option. Building envelope tightness and insulation installation shall be considered acceptable when tested air leakage is less than 7 ACH when tested with a blower door at a pressure of 50 Pascal's. Testing shall occur after rough in and after installation of penetrations of the building envelope, including penetrations for utilities, plumbing, electrical, ventilation, and combustion appliances.

402.4.2 Air sealing and insulation. …shall be demonstrated to comply with one of the following options :

Air Sealing

69

Page 70: 2009 IECC: Residential Provisions

402.4.2.2 Visual inspection option: Building envelope tightness and insulation installation shall be considered acceptable when the items listed in Table 402.4.2, applicable to the method of construction, are field verified. Where required by the code official, an approved party independent from the installer of the insulation, shall inspect the air barrier and insulation.

Air Sealing

70

Page 71: 2009 IECC: Residential Provisions

Air barrier and thermal barrier

Ceiling / attic

Walls

Windows and doorsRim joists

Floors (including above garage and cantilevered floors)Crawlspace walls

Exterior thermal envelope insulation for framed walls is installed in substantial contact and continuous alignment with building envelope air barrier.Breaks or joints in the air barrier are filled or repaired.Air permeable insulation is not used as a sealing material.Air permeable insulation is inside of an air barrier.Air barrier in any dropped ceiling / soffit is substantially aligned with insulation and any gaps are sealed. Attic access (except unvented attic), knee wall door, or drop down stair is sealed. Corners and headers are insulated. Junction of foundation and sill plate is sealed. Space between window/door jambs and framing is sealed. Rim joists are insulated and include an air barrier.

Insulation is installed to maintain permanent contact with underside of subfloor decking.

Air barrier is installed at any exposed edge of insulation.

Insulation is permanently attached to walls. Exposed earth in unvented crawlspaces is covered with class I vapor retarder with overlapping joints taped.

COMPONENT CRITERIA

AIR BARRIER AND INSULATION INSPECTIONTable 402.4.2 - Air Sealing

71

Page 72: 2009 IECC: Residential Provisions

Shafts, penetrations

Narrow cavities

Garage separationRecessed lighting

Plumbing and Wiring

Shower/tub on ext. wall

Electrical / phone box on exterior wallsCommon wallHVAC register boots

Fireplace

Duct shafts, utility penetrations, knee walls, and flue shafts opening to exterior or unconditioned space are sealed. Batts in narrow cavities are cut to fit, or narrow cavities are filled by sprayed/blown insulation.

Air sealing is provided between the garage and conditioned spaces. Recessed light fixtures are airtight, IC rated, and sealed to drywall. Exception--fixtures in conditioned space. Insulation is placed between outside and pipes. Batt insulation is cut to fit around wiring and plumbing, or sprayed/blown insulation extends behind piping and wiring.

Showers and tubs on exterior walls have insulation and an air barrier separating them from the exterior wall. Air barrier extends behind boxes or an air sealed type boxes are installed.

Air barrier is installed in common wall between dwelling units. HVAC register boots that penetrate building envelope are sealed to subfloor or drywall. Fireplace walls include an air barrier.

COMPONENT CRITERIA

AIR BARRIER AND INSULATION INSPECTIONTable 402.4.2 - Air Sealing

72

Page 73: 2009 IECC: Residential Provisions

Air Sealing

Recessed Lighting Fixtures 3 Options:– IC-Rated and meeting

ASTM E 283 ≤ 2.0 CFM leakage

– Sealed with a gasket or caulk between the housing and interior wall or ceiling surface.

73

Page 74: 2009 IECC: Residential Provisions

Systems Mandatory Requirements

Systems Include• Heating and

cooling systems• Circulating water

heating systems• Snow melt controls• Pool heaters and

covers

74

Page 75: 2009 IECC: Residential Provisions

Systems Mandatory Requirements

• Heating and Cooling Equipment– System sealing is

required including:• Ducts• Air handlers• Filter boxes• Building cavities

used as ducts

75

Page 76: 2009 IECC: Residential Provisions

Systems Mandatory RequirementsHeating and Cooling Equipment

Duct Sealing Section 403.2.2 IECC and M1601.4.1 IRC

• Can seal with tapes, mastics, gasketing and other approved closure devices

• Rigid fibrous glass ducts– Pressure sensitive tapes UL 181

A “181 A-P”– Mastic UL 181 A “181 A-M”– Heat sensitive tape UL 181 A

“181 A-H”• Flexible air duct

– Pressure sensitive tape UL 181B “181B-FX”

– Mastic UL 181B “181B-M”

76

Page 77: 2009 IECC: Residential Provisions

1. Post construction test: Leakage to outdoors shall be < 8 cfm per 100 ft2 of conditioned floor area

or, < 12 cfm per 100 ft2 of conditioned floor area across entire system

2. Rough-in test: Total leakage shall be < 6 cfm per 100 ft2 of conditioned floor area, at 25 Pa across rough system. If air handler not installed at test, then test at 4 cfm per 100 ft2 of conditioned floor area

3. Exception: Duct tightness testing is not required if air handler and ALL ducts are located within the conditioned space.

403.2.2 All ducts, air handlers, filter boxes and building cavities used as ducts shall be sealed. :

Systems Mandatory RequirementsDucts - Sealing

77

Page 78: 2009 IECC: Residential Provisions

Systems Requirements

• Heating and Cooling Equipment– Each separate space

conditioning system shall have a control

– Special thermostat for heat pump systems

– R-2 for piping carrying fluids > 105 ˚F or < 55˚F

– Outdoor air intakes or exhausts shall have dampers

78

Initially programmed with

heating temperature set point no higher than 70oF and a

cooling temperature set point no lower

than 78oF

Page 79: 2009 IECC: Residential Provisions

Systems Mandatory Requirements

• Heating and cooling equipment shall be sized in accordance with ACCA Manual J (IRC M1401.3) – or approved method– Outdoor design temperatures

per ACCA Manual S– Indoor design temperatures

• ≤ 72 ˚F Heating• ≥ 75 ˚F Cooling

79

Page 80: 2009 IECC: Residential Provisions

Systems Mandatory Requirements

• Water Heating– Circulating hot

water system piping to be insulated to an R-2

– Ability to switch the system off when not in use

• Manual switch• Automatic switch

80

Page 81: 2009 IECC: Residential Provisions

Section 403.5 – Mechanical Ventilation

• Outdoor air intakes and exhausts shall have gravity or automatic dampers that close when the system is not in operation.

81

Page 82: 2009 IECC: Residential Provisions

Section 403.6 – Equipment Sizing

• Equipment to be sized in accordance with

IRC M1401.3 – ACCA Manual S with loads calculated per ACCA Manual J

82

Page 83: 2009 IECC: Residential Provisions

Section 403.7 – Systems Serving Multiple Dwelling Units

• Such systems shall comply with Sec 503 and 504 (Commercial) instead of 403.

83

Page 84: 2009 IECC: Residential Provisions

Section 403.8 – Snow Melt Controls

• Such systems shall be provided with automatic controls to shut off the system when pavement temperature is above 50 ̊F, and with auto or manual controls to shutoff the systems when outdoor temperature is above 40 ̊F.

84

Page 85: 2009 IECC: Residential Provisions

Section 403.0 – Pools

• Pool heaters – All pool heaters shall be provided with a readily accessible shutoff switch, Gas-fired heaters shall not have continuously burning pilots.

• Pool heaters and pumps shall be provided with programmable shutoff switches, except where pumps are required to operate solar or waste heat recovery systems.

• Heated pools shall be provided with vapor retardant covers. Pools heated to more than 90 ̊F shall have R-12 covers, except for pools deriving more than 60% of their energy from a solar or site-recovered source.

85

Page 86: 2009 IECC: Residential Provisions

Section 404 - Lighting

• High-Efficacy LampsT-8 or smaller60 lumens per watt over 40 watts50 lumens per watt over 15 watts to 40

watts40 lumens per watt 15 watts or less

– 50% of lamps

86

Page 87: 2009 IECC: Residential Provisions

Total UA Alternative - REScheck

87

Page 88: 2009 IECC: Residential Provisions

Simulated Performance

• Simulates the Energy Use of a Proposed Residence and Determines the Cost to Operate Annually

• Most Flexible Energy Code Compliance Approach, Accounts for:

• House tightness• Heating and cooling efficiency• Service water heating efficiency• Building orientation• Thermal mass• Duct leakage

88

Page 89: 2009 IECC: Residential Provisions

Simulated Performance

<

ProposedDesign

Energy Estimation

Tool

BuildingComplies

When The:

Energy Costof

Proposed

Energy useof Standard

StandardDesign

<

ProposedDesign

Energy Estimation

Tool

BuildingComplies

When The:

Energy Costof

Proposed

Energy useof Standard

StandardDesign

89

Page 90: 2009 IECC: Residential Provisions

Simulated Performance

Required Documentation– Compliance report

• Address of residence• Inspection checklist• Compliance author• Name and version of

compliance software

Optional documentation– Standard reference

and proposed design documentation

– Certification showing building component characteristics of proposed design

• Must be signed by the builder

90

HVAC trade-off eliminated in 2009 IECC

Page 91: 2009 IECC: Residential Provisions

Energy Code Compliance Process

91

Mandatory Provisions

Prescriptive

Envelope Section 402

Envelope ProvisionsSection 402.2, 402.3.3 thru 402.3.6 & 402.5 (As Applies)

Simulated Performance Section 405Insulation

Requirements Fenestration

Section 403.2.1 & 404.1

Table 402.1.3

Section 402.3.1 & 402.3.2 (Trade-Off)

Section 402.1.1 & 402.1.2 (Tabular)

Section 402.1.3 & 402.1.4 (Trade-Off)

Project Complies

OR OR

Page 92: 2009 IECC: Residential Provisions

Above Code Programs

Allows National, State andLocal Energy EfficiencyPrograms as Alternatives to Complying with the 2009 IECC or IRC

– Program must exceed the current energy code– Must be approved by the code official or the

authority having jurisdiction– Must meet mandatory requirements

92

Page 93: 2009 IECC: Residential Provisions

Additional Resources

Websites

• International Codes Council www.iccsafe.org/• US Department of Energy www.energycodes.gov/• National Fenestration Rating Council, Inc www.nfrc.org• New Buildings Institute www.newbuildings.org• United State Department of Energy, Building Codes Program• Submit a question at Ask an Energy Codes Expert• Locate compliance software - visit U.S. Department of

Energy's Building Energy Software Tools Directory for more information.

• International Codes Council (ICC), Code clarification for ICC Members - 1-888-ICC-SAFE (1-888-422-7233)

• Simplyinsulate.com• CONTACT INFO: Forrest Fielder, [email protected]

93

.